5. Output Configuration
Current or Voltage 0-20mA, 4-20mA, 0-5V, 0-10V Configuration
This output will generate a current or voltage output reflecting the full scale of the sensor. This
output is factory set and calibrated to the user’s specified requirements at point of purchase.
If an output type was not specified by the user at time of purchase the default setup is set and
calibrated to 4-20mA. This is user adjustable out in field but will not be as accurate to what it
was originally calibrated to from factory.
The 4-
20ma will drive into a maximum of 680Ω load impedance (line and input impedance) at
24V.
Be cautious when handling the GDA 4350 as there are delicate components that can
easily be damaged by static discharge. Always observe anti static precautions.
To change the output:
1. Isolate the GDA 4350 by removing the incoming power source connector (P1) from the
rear of the board
2. Adjust jumper pins to the desired output configuration (see Table below)
3. Ensure output is configured for the changed output option
4. Revert to normal operation
Output Type
P2 Jumper Configuration (IN or OUT)
P2 Jumper Location
1
Sen
Pwr
2
MCU
Pwr
3
HS/FS
4
0/4-
20mA
5
V Out
6
Reset
4 - 20 mA (Default as
pictured)
IN
IN
IN
IN
OUT
OUT
0 - 20 mA
IN
IN
IN
OUT
OUT
OUT
0 - 5 V
IN
IN
OUT
OUT
IN
OUT
0 - 10 V
IN
IN
IN
OUT
IN
OUT
Table 3: Output Jumper location
P2
P3
P2 Jumper
Description
P1
P2 Jumper Location No.:
1 2 3 4 5 6