4. Troubleshooting Guide

MO-36E-18Y

No.

Problem

Possible Cause

Corrective Action

Remarks

1

The evaporative air

cooler is not

functioning and

does not respond

when buttons are

pressed.

Blackout or faulty power

connection

Measure the input voltage

and connect to a

designated power supply.

We recommend

that a voltmeter is

used because an

electrician’s

screwdriver

cannot correctly

measure voltage.

AC fuse is damaged or

the circuit stops

functioning in order to

prevent power overload.

Replace the fuse or restart

the unit.

Restart the power

overload

prevention system

and find out the

cause of the

overload.

2

Remote control

does not respond or

is less responsive.

Remote control batteries

have run out or remote

control is out of control

area.

Change the batteries and

use remote control with

control area.

3

No air flows from

the unit after the

“On/Speed” button

is pressed.

Heat protection

equipment inside the

motor is working.

Leave the unit off until the

fan motor is cool enough

to be used as usual.

Damaged motor

Repair or replace the

motor with another of the

same model.

Loose motor connection

Determine whether or not

the motor connections are

in order.

Damaged heat relay

Repair or replace the

control panel with another

of the same model.

5

6

4

The pump functions

but it is not cool

enough.

Air ventilation chamber is

not large enough. Filter

pads are clogged or dirty.

Clean or replace the filters.

Check the

parameters of the

replacement parts.

The filter pads are dry or

contain insufficient water

while the air cooler is

working.

Check the water distribution

system to determine whether

or not there is a clog.

Determine if the pump is

functioning correctly.

Excessively high relative

humidity

When the cooler is used for a

prolonged of time, the room

humidity will be very high, so

the cooler will be unable to

lower temperatures as much

as when the room’s humidity

is lower. Turn the pump off

and increase ventilation.

5

The pump fails to

function and provide

cooling

Damaged pump

Repair or replace the pump

with a pump of the same

model.

Loose motor connection

Tighten connection

6

The pump functions

but does not

circulate water, or

the filter pads

contain too little

water.

Clogged or dirty strainer

Clean the strainer.

Clogged water supply hose

Clean the hose.

Clogged drain

Clean the drain.

7

Undesirable odor

The unit is placed in an

area where undesirable

odors are present, or algae

are present in the water

tank.

Clean the cooling machine.

8

White sediments in

the water tank

Water has a high content

of salt

Drain the tank more

frequently.

Summary of Contents for MO-36E-18Y

Page 1: ...MO 36E 18Y Installation Operation Manual ...

Page 2: ...ions and Functions 1 2 1 For Control Panel and Remote Control 1 2 2 Cleaning and Maintain for Cooling pad 2 3 Construction Diagram 4 4 Troubleshooting Guide 5 5 Product Dimension 6 5 Technical Information 6 6 Circuit diagram 8 7 Exploded view 8 9 ...

Page 3: ...ater tank need to be refilled In the case where the wind speed is high when the Cool button is pressed the cooler will drop to the lowest speed for 80 seconds before resuming the speed previously set Swing Press the Swing button on the control panel or remote control to have the vertical louvers swing automatically and the unit will enter the Swing mode with indicator light on Press again and the ...

Page 4: ...reeding mosquitoes and other insects the water tank should be drained and turn on the cooler by pressing ON OFF button to dry off the cooling pads Shut off the cooler after cooling pads are dried off There is a hole for uncovering By pulling out upward to refill water steadily After removed the supporting rod for cooling pad and air inlet grille the cooling pads can be pulled out 3 Construction Di...

Page 5: ...ay Repair or replace the control panel with another of the same model 5 6 4 The pump functions but it is not cool enough Air ventilation chamber is not large enough Filter pads are clogged or dirty Clean or replace the filters Check the parameters of the replacement parts The filter pads are dry or contain insufficient water while the air cooler is working Check the water distribution system to de...

Page 6: ...Y Air Volume 9216 CFM Voltage Frequency 110 V 60 Hz Power 128 W Water tank capacity 8 45 US gal Overall dimension 12 6x16 54x47 24 in No of Cooling pad 3 PCS Net weight 22 00 lb Area Coverage 322 92ft 7 47 24 in 8 Circuit diagram 8 Exploded view 8 12 6 in 16 54 in ...

Reviews: