Onan 300-4296 Replacement Download Page 1

Replacement Onan

®

 

300-4296(12V)

300-4297 (24V) 

ENGINE MONITOR 

(FS Part No. 56-4296-00 

or 56-4297-00)

FLIGHT SYSTEMS

207 Hempt Rd. Mechanicsburg, PA 17050  Ph: 717-590-7330  www.flightsystems.com

Designed & Built in USA by

Thank you for choosing Flight Systems P/N 56-4296-00 for the replacement of Onan

®

 P/N 300-4296 (12V), or P/N 56-

4297-00 for the replacement of Onan

®

 P/N 300-4297 (24V).  It will replace all revisions of the original Onan

®

 product 

on systems using 2 to 12 lights.  Revisions made by Onan

®

 over a period of about three decades include the following:

•  Glass fuses replaced by AT-type blade fuses
•  Addition of TB3
•  Addition of feature selection jumpers

•  Addition of W10 to select flashing or steady for SWITCH OFF indication

•  Addition of diagnostic LEDs to aid in troubleshooting

•  AC start disconnect (K10) changed from an AC relay to a DC relay

You will notice that this new Flight Systems replacement board looks quite different from any of the Onan

®

  boards.  

The most striking difference is the microprocessor-based design which enhances reliability and eliminates 17 of the 20 

relays.  Additional features include:
•  Auto-reset on initial power-up
•  Plainly marked DIP switches for feature selection (no jumpers)
•  Plainly marked, user-friendly, on-board LED array for easier system troubleshooting

•  Solid-state AC voltage sensing for crank termination

•  Surge and reverse polarity protection
•  Reverse polarity indication warns of incorrect battery connection

•  Common alarm output is upgraded to 5A

•  Solid-state outputs for annunciators
•  Lamp test for both local and remote annunciators

•  Cranking limited to 60 seconds when continuous crank is selected 

•  Network communications capability possible with Modbus option
You will also notice that the diagnostic LEDs are arranged in an orderly and easy-to-read fashion and that DIP switches 

have replaced movable jumpers for feature selection.  Table 1 below shows how to set the DIP switches.  The “ON” 

position is always to the right.  For example, FAULT 1 is set up using S1, S2 and S3.  If S1 is ON, FAULT 1 is enabled 

15 seconds after RUN is detected.  If S1 is OFF, FAULT 1 is enabled immediately when RUN is detected, without any 

delay.  If S2 is ON, FAULT 1 will cause a shutdown.  If S3 is ON, FAULT 1 is enabled always, running or not, there 

is no shutdown and the settings of S1 and S2 do not matter.  In other words, S3 must be OFF to enable the selection 

of delay or shutdown using S1 and S2.  FAULT 2 works exactly the same way using S4, S5 and S6.  The settings for 

S7 through S10 are explained, along with the factory settings for all of the DIP switches in Table 1 - 

SEE REVERSE.