background image

EMERGENCY 2990

3

2

1

TECHNICAL SPECIFICATION

- Supply voltage: 220÷240VAC/50÷60Hz, 175÷275VDC, 24VDC

Insulation class

: II or III

Protection level

: IP40

Time of operation in emergency mode 

: 1, 2 or 3h

Light source

: 1W, 2W, 3W LED

Battery charging time 

: up to 24h

Ambient temperature 

: 0÷+40°C

- Viewing distance: 30m

MAIN FEATURES

:

Battery charging indication by LED

Electronic protection against total battery discharge

Self-test function (optional)

Operation in emergency or mains and emergency mode available

Using to 

Rubic system

 available

Using to central battery available

Surface assembly

, optional recessed

- Assembly indoors to flat surface
- Polycarbonate body, plexi glass
- The luminaire can be powered maintained or non maintained
- Controlgear supplied within this luminaire performs the function of 

changeover operation from normal to emergency mode

RECOMMENDATIONS FOR USE

:

The following rules must be observed to ensure the correct and reliable 
operation of the fitting:

Battery packs must be compatible with emergency modules

Installation of fitting should be made by appropriate person which is 

authorized for such works

After installation of fitting, the formatting of battery must be made while 

continuous charging for a period of 24 hours and fully discharging it 
through lighting

Three full formatting cycles must be performed to achieve maximum 

battery capacity

Technical inspection of the fitting and, in particular, of the battery must 

be performed once a year

It is important to maintain temperature parameters for battery packs, i.e.

from 0 to + 55°C

It is forbidden to make any changes in electronic system design

If the fitting does not withstand its rated operation time, the battery must 

be renewed

It is recommended by the manufacturer to renew the battery every 4 

years

The light source contained in this luminaire shall only be replaced by the 

manufacturer or his service agent or a similar qualified person

-

 

 Rated luminous flux in emergency mode amounts to 100%

.

TERMS AND CONDITIONS OF WARRANTY

:

The condition to acknowledge the warranty is

:

No mechanical damage

No evidence of changes made by third party in fitting design and, in 

particular, emergency module

Proper use, as recommended

Proper connection of supply voltage and battery pack (attention must be 

paid to the polarity of the battery and converter terminals).

TESTING THE FITTING

 (optional):

It is possible to test the fitting using test button placed in the

 

housing (option).

 

At the 

time when the supply voltage is connected to the

 

fitting, the green LED lights up 

indicating the emergence of voltage in the

 

electronic system and thus the battery 

charging. By pressing the button, the test of fitting is activated through an open 
circuit, and by this the decay of mains voltage is simulated and the switching over by 
electronic system to the emergency operation mode is caused. During emergency 
operation, the LED is no longer lit, the fitting is powered from the battery. When the 
button is released, the mains voltage returns and the fitting is operated in mains mode, 
charging process is started.

AUTOTEST FUNCTION (optional):

Test A is run automatically every 28 days. During test A a conversion kit is switched 
to emergency mode for 1 minute and the following parameters are checked: control 
of battery power discharge, control of battery. Test B is run automatically every 364 
days. During test B a conversion kit is switched to emergency mode for all duration time 
and the following parameters are checked: control of battery power discharge, 
control of minimum battery voltage .

DIMENSION

OPENNING  

LED

24V

DC

Ni-Cd

Ni-MH

IP40

175-275V

DC

220-240V

AC

50-60Hz

d=30m

LiFePO

4

ASSEMBLY INSTRUCTIONS

max. 750 

OMS a.s.
906 02 Dojč,419
Slovakia  
www.omslighting.com

Color of LED indicator shining (blinking), 

G – Green, R - Red

 

Light 

source 

Description 

any 

Confirmation of the reset of timer or errors (only AT) 

shining 

Emergency mode 

not shining 

Standby mode 

any 

Communication error (only RS), no battery 

any 

Communication error (only RS), connected battery 

any 

Battery error 

any 

Light source or electronics error 

Error indication or not shining 

shining 

Performing test or network mode 

Error indication or not shining 

any 

No battery 

not shining 

Battery loading 

not shining 

Standby mode (battery full) 

not shining 

Too much output power for this battery capacity 

Reviews: