15-3-2
Built-in EtherNet/IP Port Data Processing Time
This section describes the data processing time required to transfer data between the built-in Ether-
Net/IP port and the CPU Unit.
Data Processing Time Overview
The time required for data processing consists of the following three elements.
1.
Variable Access Time
Calculate the time required to transfer tag data, which is regarded as the time required to access
the variable.
This calculation is performed for each task. Therefore, if multiple tag sets are set for the same re-
freshing task, use the total for all tag values in the tag sets.
Use the following equation for calculating the variable access time.
Variable access time [μs] = total size of variables [bytes] × a + number of variables × b + number of
accesses × c + d
Number of accesses: equal to the number of tag sets
a to d: Constant values as given below
CPU Unit model
Constant value (μs)
a
b
c
d
NX701-
££££
0.0005
0.033
2.67
7.22
NX102-
££££
0.0040
0.240
3.27
25.21
NX1P2-
££££
0.0040
0.240
3.27
25.21
NJ501-
££££
0.0010
1.41
6.68
NJ301-
££££
0.0015
2.15
7.52
NJ101-
££££
0.0015
0.560
3.83
7.52
*1.
The value is 0.58 for CPU Units with unit version 1.02 or earlier.
*2.
The value is 0.0009 for CPU Units with unit version 1.02 or earlier.
*3.
The value is 1.03 for CPU Units with unit version 1.02 or earlier.
2.
Number of Data Transfers
Tag data transfer is executed as part of the task processing.
If the time required to process the data transfer is greater than the variable access time (*2), the
entire data cannot be sent in one task period and needs to be split and sent over multiple times
instead.
Number of data transfers = Time required to send the entire data (*1) / Variable access time (*2)
set for the task
*1. This is the variable access time as calculated in step 1 above.
*2. The variable access time is the maximum processing time for accessing the variable. Double-click
Task
Settings
under
Configurations and Setup
on the Sysmac Studio to display the
Task Settings
Tab
Page, and configure the settings for each task.
15 Communications Performance and Communications Load
15-23
NJ/NX-series CPU Unit Built-in EtherNet/IP Port User’s Manual (W506)
15-3
I/O Response T
ime in T
ag Data Links
15
15-3-2 Built-in EtherNet/IP Port Data Processing T
ime
Summary of Contents for Sysmac NX1P2-10 1 Series
Page 8: ...Manual Structure 6 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 34: ...Revision History 32 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 388: ...9 Socket Service 9 34 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 430: ...12 FTP Client 12 14 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 569: ...I Index I 1 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506 I...
Page 576: ...Index I 8 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 577: ......