15-3 I/O Response Time in Tag Data Links
Additional Information
This section describes built-in EtherNet/IP ports on the NX and NJ-series CPU Units.
Compared to those built-in EtherNet/IP ports, EtherNet/IP Units, and built-in EtherNet/IP ports
on CJ2H CPU Units (CJ2H-CPU6
£
-EIP) and CJ2M CPU Units (CJ2M-CPU3
£
) support differ-
ent data processing performance. For details, refer to
7-4 Tag Data Links with Other Models
15-3-1
Timing of Data Transmissions
The following figure shows the timing of transmitting data for tag data link between a built-in
EtherNet/IP port and a CPU Unit.
Data is transmitted at the timing of executing the system common processing 2 of the refreshing task.
I/O refresh
Refreshing
Execution of
programs
System common
processing 1
Control processing
Out
put data
proces
sin
g
Inp
ut data
proces
sin
g
Sys
tem co
mmon
processing 1
Moti
on
con
tro
l
Sys
tem co
mmon
processing 2
Output
d
a
ta
proces
sin
g
Primary periodic task
Data received.
Controller
Processing
Data exchange processing
Controller task period
You can specify either of the following task types for a refreshing task.
• Primary periodic task
The primary periodic task has the highest execution priority. It is executed with high speed and high
precision.
• Periodic task
A periodic task is executed during the interval between executions of a primary periodic task.
You do not need to specify a refreshing task for tags (variables) with AT specifications; the tag data is
transmitted as a primary periodic task. (For NX102, NX1P2 and NJ-series CPU Units)
Specify a task type for each tag for tag data link processing.
On the Sysmac Studio, set a refreshing task for each variable assigned as a tag.
Refer to the
Sysmac Studio Version 1 Operation Manual (Cat. No. W504)
for details on setting refresh-
ing tasks.
15 Communications Performance and Communications Load
15-22
NJ/NX-series CPU Unit Built-in EtherNet/IP Port User’s Manual (W506)
Summary of Contents for Sysmac NX1P2-10 1 Series
Page 8: ...Manual Structure 6 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 34: ...Revision History 32 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 388: ...9 Socket Service 9 34 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 430: ...12 FTP Client 12 14 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 569: ...I Index I 1 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506 I...
Page 576: ...Index I 8 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 577: ......