7-4
Tag Data Links with Other Models
The performance of tag data links depends on the CPU Unit model and EtherNet/IP Unit model as
shown below.
When you use tag data links between the built-in EtherNet/IP port on an NJ/NX-series CPU Unit and
another CPU Unit or EtherNet/IP Unit, configure the tag data link settings based on either Unit, which-
ever has the lower level of communications performance.
Differences in Tag Data Link Performance Specifications
Item
NX-series CPU Unit
NJ-series CPU Unit
CJ2M-CPU3
£
CS1W-EIP21
CJ1W-EIP21
CJ2H-CPU6
£
-
EIP
NX701
NX102
NX1P2
Unit version
Unit ver-
sion 1.00
to 1.02
Unit ver-
sion 1.03
or later
2.0
2.1 or lat-
er
Tag
Total size
of all tags
184,832
words
(total of
369,664
words with
the two
ports)
9,600
words (to-
tal of
19,200
words with
the two
ports)
9,600 words
640 words
184,832 words
Maximum
size of tag
722 words
(721
words
when the
tag set in-
cludes the
Controller
status)
300 words
(299 words when the tag set includes the Control-
ler status)
20 words
(19 words
when the
tag set in-
cludes the
Controller
status)
640 words
(639
words
when the
tag set in-
cludes the
Controller
status)
722 words
(721 words when
the tag set in-
cludes the Con-
troller status)
Number of
registrable
tags
256
(total of 512 with the
two ports)
256
32
256
Tag set
Maximum
size of tag
set
722 words
(721
words
when the
tag set in-
cludes the
Controller
status)
300 words
(299 words when the tag set includes the Control-
ler status)
20 words
(19 words
when the
tag set in-
cludes the
Controller
status)
640 words
(639
words
when the
tag set in-
cludes the
Controller
status)
722 words
(721 words when
the tag set in-
cludes the Con-
troller status)
Number of
tags per
tag set
8
(7 tags when the tag set includes the Controller status)
Note: Input and output variables cannot be combined in one tag set.
Number of
registrable
tag sets
256
(total of
512 with
the two
ports)
32 (total of
40 with the
two
ports)
32
32
256
7 Tag Data Link Functions
7-86
NJ/NX-series CPU Unit Built-in EtherNet/IP Port User’s Manual (W506)
Summary of Contents for Sysmac NX1P2-10 1 Series
Page 8: ...Manual Structure 6 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 34: ...Revision History 32 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 388: ...9 Socket Service 9 34 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 430: ...12 FTP Client 12 14 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 569: ...I Index I 1 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506 I...
Page 576: ...Index I 8 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 577: ......