Parameter name
Data type
Description
Size of Additional Status
USINT
Size of Additional Status: 00 hex
When the processing failed
Parameter name
Data type
Description
Reply Service
USINT
Write NX object service response: B4 hex
Reserved
USINT
Reserved: 00 hex
General Status
USINT
Current error code defined by CIP
Size of Additional Status
USINT
Size of Additional Status: 00 hex or 01 hex
Additional Status
UINT
Additional Status
*1.
When the General Status of the response code is 1F hex (Vendor specific error), becomes 01 hex.
*2.
This is stored only when the Size of Additional Status is 01 hex.
CIP Error Codes
General sta-
tus code
(hex)
Error name
Cause
02
Resource unavailable
Resources needed for the object to perform the requested
service were unavailable.
0C
Object state conflict
The object cannot perform the requested service in its cur-
rent mode/state.
0E
Attribute not settable
The NX object which is not modifiable is specified.
10
Device state conflict
•
Carried out writing in a state that was not the parameter
write mode.
•
The state of the NX object is not in a state to execute the
required service.
13
Not enough data
Data required for the execution of the required service is in-
sufficient.
15
Too much data
Extra data for the execution of the required service is includ-
ed.
1F
Vendor specific error
The service could not be executed due to internal reasons.
20
Invalid parameter
•
The Unit number is out of the supported range.
•
The sizes of the specified object and Length do not match.
•
The object of the index specified for the NX object does
not exist.
•
The Index specified for the NX object exists, but the Sub
Index does not exist.
•
Write data is out of the range.
Restart NX Unit (Service Code: 35 hex)
Restart the specified NX Units.
Request Data Format
Parameter name
Data type
Description
Service
USINT
Restart NX Unit service: 35 hex
Request Path Size
USINT
Size of Request Path: 02 hex
8 CIP Message Communications
8-54
NJ/NX-series CPU Unit Built-in EtherNet/IP Port User’s Manual (W506)
Summary of Contents for Sysmac NX1P2-10 1 Series
Page 8: ...Manual Structure 6 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 34: ...Revision History 32 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 388: ...9 Socket Service 9 34 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 430: ...12 FTP Client 12 14 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 569: ...I Index I 1 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506 I...
Page 576: ...Index I 8 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 577: ......