Service
code
Parameter name
Description
Supported serv-
ices
Classes
Instan-
ces
05 hex
Reset
Resets the built-in EtherNet/IP port.
This parameter is used to reset the built-in EtherNet/IP port
when you change the IP address or other parameter settings
and want to apply them.
Input one of the following values for the
ServiceDat
input vari-
able to the CIPSend instruction to specify the reset method.
00 hex: Resets the built-in EtherNet/IP port.
: Clears the saved tag data link settings and resets
the built-in EtherNet/IP port.
Not sup-
ported
Support-
ed
*1.
The value is 01 hex for a CPU Unit with unit version 1.09 or earlier.
Class ID
Specify 01 hex.
Instance ID
Specify 00 or 01 hex.
Attribute ID
The attribute ID specifies the information to read.
Class Attribute ID
The class attribute ID specifies the attribute of the entire object.
Attribute ID
Parameter name
Description
Attrib-
ute
Read data
Data
type
Value
01 hex
Revision
Revision of the object
Read
UINT
0001 hex
02 hex
Max Instance
The maximum instance num-
ber
Read
UINT
0001 hex
Instance Attribute ID
The instance attribute ID specifies the attribute of the instance.
Attribute ID
Parameter name
Description
Attribute
Read data
Data
type
Value
01 hex
Vendor ID
Vendor ID
Read
UINT
002F hex
02 hex
Device Type
Device type
Read
UINT
000C hex
03 hex
Product Code
Product code
Read
UINT
Refer to (1) Product Codes
for Each Model, below.
8 CIP Message Communications
8-48
NJ/NX-series CPU Unit Built-in EtherNet/IP Port User’s Manual (W506)
Summary of Contents for Sysmac NX1P2-10 1 Series
Page 8: ...Manual Structure 6 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 34: ...Revision History 32 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 388: ...9 Socket Service 9 34 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 430: ...12 FTP Client 12 14 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 569: ...I Index I 1 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506 I...
Page 576: ...Index I 8 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 577: ......