4 Installation and Wiring
4 - 46
NX-series System Units User’s Manual (W523)
Securing Wires
It is necessary to secure wires to the screwless clamping terminal block depending on the wire types
that are used or the current flows on the wires.
The following table gives the necessity for securing wires.
Use the following procedure to secure the wires.
1
Prepare a cable tie.
A cable tie can be used with a width of 4 mm or less and a thickness of 1.5 mm or less.
Select a cable tie correctly for the operating environment.
2
Pass a cable tie through the hole for securing wires on the bottom of the screwless clamping ter-
minal block.
Terminals
Wire type
Ferrule
Twisted wires
Solid wire
Classifica-
tion
Current
capacity
Plated
Unplated
Plated
Unplated
All terminals
except
ground
terminals
2 A max.
No
No
No
No
No
Greater than
2 A and 4 A or
less
Not Possible
Yes
Not Possible
Greater than
4 A
Yes
Not Possible
Ground
terminals
---
No
No
No
No
1.5 mm or less
4.0 mm or less
Hole for securing wires
Cable tie
Summary of Contents for Sysmac NX-TBX01
Page 7: ...5 CONTENTS NX series System Units User s Manual W523 ...
Page 34: ...Sections in this Manual 34 NX series System Units User s Manual W523 ...
Page 48: ...2 Specifications 2 4 NX series System Units User s Manual W523 ...
Page 116: ...4 Installation and Wiring 4 56 NX series System Units User s Manual W523 Unit ...
Page 136: ...6 Inspection and Maintenance 6 6 NX series System Units User s Manual W523 ...
Page 158: ...Appendices A 22 NX series System Units User s Manual W523 Installation Height 100 71 Unit mm ...
Page 166: ...Appendices A 30 NX series System Units User s Manual W523 ...
Page 167: ...I 1 I NX series System Units User s Manual W523 Index ...
Page 170: ...I 4 NX series System Units User s Manual W523 Index ...
Page 171: ......