6
.
EtherCAT Settings
9
6.2. Device Variable
The process data to communicate with the Dry Vacuum Pump is assigned to the Controller's
device variables. The device variable names and data types are shown below.
Output area (Controller to Dry Vacuum Pump)
Device variable name
Data type
Description
E001_SDP_Default_RxPDO_Mapping_Roughing_Start_Stop_7000_01
BOOL
Roughing Start
E001_SDP_Default_RxPDO_Mapping_Low_Speed_Idle_Sleep_G_7000_04
BOOL
Low Speed Mode
Input area (Dry Vacuum Pump to Controller)
Device variable name
Data type
Description
E001_SDP_Default_TxPDO_Mapping_Roughing_Run_Stop_6000_01
BOOL
Roughing Run/Stop
E001_SDP_Default_TxPDO_Mapping_Booster_Run_Stop_6000_02
BOOL
Booster Run/Stop
E001_SDP_Default_TxPDO_Mapping_Low_Speed_Idle_Sleep_G_6000_04
BOOL
Low Speed Mode
E001_SDP_Default_TxPDO_Mapping_Remote_Local_6000_05
BOOL
Remote/Local
E001_SDP_Default_TxPDO_Mapping_Warning_6000_09
BOOL
Warning
E001_SDP_Default_TxPDO_Mapping_Alarm_6000_0A
BOOL
Alarm
E001_SDP_Default_TxPDO_Mapping_Emergency_Off_6000_0B
BOOL
Emergency Off
E001_SDP_Default_TxPDO_Mapping_N2_Flow_Low_6000_0C
BOOL
N2 Flow Low
E001_SDP_Default_TxPDO_Mapping_N2_Flow_6001_02
INT
N2 Flow
E001_SDP_Default_TxPDO_Mapping_Exhaust_Pressure_6001_03
INT
Exhaust Pressure
E001_SDP_Default_TxPDO_Mapping_Roughing_Case_Temperature_6001_05
INT
Roughing Case
Temperature
E001_SDP_Default_TxPDO_Mapping_Roughing_Current_6001_09
INT
Roughing Current
E001_SDP_Default_TxPDO_Mapping_Roughing_Power_6001_0A
INT
Roughing Power
E001_SDP_Default_TxPDO_Mapping_Roughing_Speed_6001_0B
INT
Roughing Speed
E001_SDP_Default_TxPDO_Mapping_Booster_Case_Temperature_6002_05
INT
Booster Case
Temperature
E001_SDP_Default_TxPDO_Mapping_Booster_Current_6002_09
INT
Booster Current
E001_SDP_Default_TxPDO_Mapping_Booster_Power_6002_0A
INT
Booster Power
E001_SDP_Default_TxPDO_Mapping_Booster_Speed_6002_0B
INT
Booster Speed
Precautions for Correct Use
If you edit the PDO mappings in a PDO entry table (data type: BOOL), add padding (index:
0x0000:00) in order to adjust the data size of the PDO mappings to the byte boundary of 8
bits.
Additional Information
For more information on the assignments in the input and output areas, refer to
4.2 SDP
Default PDO Mapping
of the
Kashiyama Dry Vacuum Pump EtherCAT Communication
Specification
(TDA-00135-01).
Additional Information
The device variables are automatically created by combining the device name and the port
name. The default device names are "E" followed by a serial number starting from "001".