159
Built-in Analog I/O Area (XA CPU Units Only)
Section 4-3
4-3
Built-in Analog I/O Area (XA CPU Units Only)
Built-in Analog Input Bits:
CIO 200 to CIO 203 (4 words)
Built-in Analog Output Bits:
CIO 210 to CIO 211 (2 words)
The built-in analog inputs and built-in analog outputs for XA CPU Units are
always allocated words between CIO 200 and CIO 211.
The Analog I/O Area will be cleared at the following times:
1.
When the operating mode is changed between PROGRAM and RUN or
MONITOR mode (See note.)
2.
When the power is cycled
3.
When analog I/O memory is cleared from the CX-Programmer
4.
When operation fails due to a fatal error other than one created by execut-
ing a FALS(007) instruction (Memory will be retained if operation fails due
to execution of a FALS(007) instruction.)
Note
The built-in analog outputs will operate as follows when the operating mode is
switched between RUN or MONITOR mode and PROGRAM mode:
Note
Control of the built-in analog outputs will temporarily stop when Memory Cas-
sette data is being transferred or verified. Therefore, if the operating mode is
switched between PROGRAM and RUN or MONITOR mode when the built-in
analog output is being used and the I/O Memory Hold Bit is set to ON to retain
analog values output externally, the values will change; the analog values out-
put externally will not be retained while Memory Cassette data is being trans-
ferred or verified. The analog output values will return to the original retained
values when the transfer or verification has been completed.
Data
Allocated
words
Description
Data
1/6000
resolution
1/12000
resolution
Analog input
A/D conversion
data
CIO 200
Analog input 0
−
10 to 10 V:
F448 to 0BB8
hex
Other ranges:
0000 to 1770 hex
−
10 to 10 V:
E890 to 1770 hex
Other ranges:
0000 to 2EE0
hex
CIO 201
Analog input 1
CIO 202
Analog input 2
CIO 203
Analog input 3
Analog output
D/A conversion
data
CIO 210
Analog output 0
CIO 211
Analog output 1
I/O Memory Hold Bit
(A500.12)
Operation
OFF
The analog output values in the words allocated in
memory will be cleared and the 0000 hex will be output
for the output refresh.
ON
The analog output values in the words allocated in
memory will retain their values from right before the
operating mode was changed and the previous values
will be output for the output refresh.
Summary of Contents for Sysmac CP1H
Page 2: ......
Page 3: ...CP1H X40D CP1H XA40D CP1H Y20DT D CP1H CPU Unit Operation Manual Revised October 2014...
Page 4: ...iv...
Page 10: ...x...
Page 18: ...xviii...
Page 22: ...xxii...
Page 34: ...xxxiv Conformance to EC Directives 6...
Page 76: ...42 Function Blocks Section 1 5...
Page 176: ...142 CP series Expansion I O Unit Wiring Section 3 6...
Page 372: ...338 Analog I O XA CPU Units Section 5 5...
Page 578: ...544 Trouble Shooting Section 8 7...
Page 622: ...588 Sample Application Section 9 12 Network Settings Network Tab Network Settings Driver Tab...
Page 668: ...634 Standard Models Appendix A...
Page 744: ...710 Auxiliary Area Allocations by Address Appendix D...
Page 771: ...737 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 772: ...738 Connections to Serial Communications Option Boards Appendix F...
Page 800: ...766 Specifications for External Power Supply Expansion Appendix H...
Page 806: ...772 Index W Work Area 165 work bits 165 work words 165 write protection 379...
Page 808: ...774 Revision History...
Page 809: ......