100
FINS Commands and Responses
Section 5-1
5-1
FINS Commands and Responses
5-1-1
FINS Message Service Communications
FINS
FINS (Factory Intelligent Network Services) commands are message service
communications commands developed by OMRON for Factory Automation
control devices. They do not depend on a particular transmission path, and an
be used for reading from and writing to PLC memory or the Unit’s memory,
sending or receiving acyclic messages over a network, or for controlling vari-
ous operations.
The FINS communications can be issued from a CPU Unit, Special I/O Unit,
or host computer, and they can also be sent to any of these. The specific com-
mands that can be sent depend on the destination.
When the source of the commands is a PLC CPU Unit, e.g. invoked by a user
program, the FINS commands are sent by means of CMND(490). For details
on FINS commands, refer to the
Communications Commands Reference
Manual (W342)
Command Codes
Command codes are represented by a 2-byte hexadecimal code. FINS com-
mands always begin with a 2-byte command code; any parameters required
follow the command code.
Response Codes
The response code consists of a 2-byte hexadecimal code indicating the
results of command execution. The first byte provides the main response
code (MRES), which classifies the results, the second byte provides the sub-
response code (SRES), which contains details about the results.
5-1-2
Command Code List
The command codes listed in the following table are supported by the PROFI-
BUS-DP Master Unit. A PLC program can send these to the Unit
.
5-1-3
Response Code List
Response codes are 2-byte codes which indicate the results of command
execution. They are returned in the response following the command code.
The first byte of a response code is the MRES (main response code), which
categorizes the results of command execution. The second byte is the SRES
(sub-response code) which specifies the results.
Command code
Name
Page
MRC
SRC
01
01
MEMORY AREA READ
04
01
RUN
02
STOP
05
01
CONTROLLER DATA READ
21
02
ERROR LOG READ
03
ERROR LOG CLEAR
Command
code
Response
code
MRC: Main request code
SRC: Sub-request
code
MRES: Main response code
SRES: Sub-response code
MRC SRC MRES SRES
Summary of Contents for SYSMAC CJ1W-PRM21
Page 2: ...iv...
Page 36: ...22 Basic Operating Procedure Section 1 5...
Page 52: ...38 Defining PROFIBUS DP in the Software Section 2 5...
Page 112: ...98 Allocated CIO Area Words Section 4 2...
Page 122: ...108 Command Response Reference Section 5 2...
Page 160: ...146 Replacing the Unit Section 7 8...
Page 174: ...160 Appendix...
Page 180: ...166 I O Data Conversions Appendix D...
Page 186: ...172 Configurator Error and Warning Messages Appendix E...
Page 187: ...173 Index...
Page 188: ...174 Index...
Page 190: ...176 Revision History...