3-19
3 Assigning Device Variables for CJ-series Units
CJ-series EtherNet/IP Units Operation Manual for NJ-series CPU Unit (W495)
3-3 User Definition
S
ettin
gs f
o
r the Status
Area
3
3-3-4 Stat
us Inf
o
rm
ation As
signed to
the User-defin
ed Area
This variable gives the operating status of the target PLCs. It is valid only when the EtherNet/IP Unit is
the originator. The elements of this variable are valid only when the corresponding elements in the Nor-
mal Target Node Table is TRUE. If the corresponding element in Normal Target Node Table is FALSE,
the element in the Target Node PLC Operating Flags gives the previous operating status.
x.TargetPLCMdSta.TargetSta [0] to [255]
x. TargetPLCMdSta.TargetStaWd [0] to [15]
x: The name of the user-defined variable that is specified for the status area in the user settings.
This variable indicates Controller errors (an OR of major faults, partial faults, and minor faults) in the tar-
get PLCs.
The elements of this variable are valid only when the corresponding elements in the Normal Target
Node Table is TRUE. If the corresponding element in Normal Target Node Table is FALSE, the element
in the Target Node PLC Error Flags indicates the previous error status.
x.TargetPLCErrSta.TargetSta [0] to [255]
x. TargetPLCErrSta.TargetStaWd [0] to [15]
x: The name of the user-defined variable that is specified for the status area in the user settings.
Target Node PLC Operating Flags (EtherNet/IP Unit to CPU Unit)
Bit
Meaning
Status
Manipulated
by
Unit operation
Reference
---
Target Node PLC
Operating Flags
TRUE
EtherNet/IP
Unit
The target PLC is operating.
3-2-3 Device Vari-
ables for the CJ-
series Unit for Status
FALSE
EtherNet/IP
Unit
Other than the above.
Target Node PLC Error Flags (EtherNet/IP Unit to CPU Unit)
Bit
Meaning
Status
Manipulated
by
Unit operation
Reference
---
Target Node PLC
Error Flags
TRUE
EtherNet/IP
Unit
A major fault, partial fault, or minor fault
occurred in the corresponding PLC.
3-2-3 Device Vari-
ables for the CJ-
series Unit for Status
FALSE
EtherNet/IP
Unit
Other than the above.
Summary of Contents for SYSMAC CJ1W-EIP21
Page 8: ...Manual Structure 6 CJ series EtherNet IP Units Operation Manual for NJ series CPU Unit W495...
Page 42: ...Revision History 40 CJ series EtherNet IP Units Operation Manual for NJ series CPU Unit W495...
Page 68: ...1 Introduction 1 26 CJ series EtherNet IP Units Operation Manual for NJ series CPU Unit W495...
Page 266: ...9 FTP Server 9 20 CJ series EtherNet IP Units Operation Manual for NJ series CPU Unit W495...
Page 431: ...Index 1 CJ series EtherNet IP Units Operation Manual for NJ series CPU Unit W495 I Index...
Page 436: ...Index 6 CJ series EtherNet IP Units Operation Manual for NJ series CPU Unit W495 Index...
Page 437: ......