4-9
4-2 Function Mode
4
Functions
• If you apply a base frequency of over 60 Hz, a special motor is required. This may require the
Inverter to increase its capacity to accommodate a different applicable motor.
• Select the motor voltage according to the motor specifications. If the voltage exceeds the specified
level, the motor may burn out.
• The Inverter cannot output voltage beyond that of the incoming voltage.
Maximum Frequency
Set the maximum value of the output frequency.
• The value set here is the maximum value (e.g.,10 V in the range from 0 to 10 V) of the external
analog input (frequency reference).
• The maximum Inverter output voltage from base to maximum frequencies is the voltage set in AVR
voltage selection A082.
• The Inverter cannot output voltage beyond that of the incoming voltage.
* To switch to the 2nd max. frequency, allocate 08 (SET) to the multi-function input and then turn it on.
Output
voltage
Motor
voltage
selection
(A082)
Base frequency
(A003/A203)
Output frequency (Hz)
Output
voltage
Motor
voltage
selection
(100%)
(A082)
Base frequency
(A003/A203)
Max. frequency
(A004/A204)
Parameter No.
Function name
Data
Default setting
Unit
A004
Maximum frequency
30 to 400
60.0
Hz
A204
* 2nd maximum
frequency
Related functions
A003, A203, A081, A082
Summary of Contents for SYSDRIVE 3G3MX-A2002
Page 1: ...Cat No I559 E1 01 USER S MANUAL SYSDRIVE MXSERIES Multi function Compact Inverter...
Page 17: ...Chapter 1 Overview 1 1 Functions 1 1 1 2 Appearance and Names of Parts 1 3...
Page 24: ......
Page 25: ...Chapter 2 Design 2 1 Installation 2 1 2 2 Removing and Mounting Each Part 2 5 2 3 Wiring 2 10...
Page 90: ......
Page 91: ...Chapter 4 Functions 4 1 Monitor Mode 4 1 4 2 Function Mode 4 5...
Page 180: ......
Page 181: ...Chapter 5 Maintenance Operations 5 1 Special Display List 5 1 5 2 Troubleshooting 5 5...
Page 188: ......
Page 189: ...Chapter 6 Inspection and Maintenance 6 1 Inspection and Maintenance 6 1 6 2 Storage 6 7...
Page 212: ...7 15 7 5 Options 7 Specifications 3G3AX RBU41 95 75 2 5 208 218 5 145 35 100 5...
Page 230: ......
Page 231: ...Appendix Appendix 1 Parameter List App 1 Appendix 2 Product Life Curve App 17...
Page 249: ...INDEX...