Chapter 3
3-2
Communications Data
3-1
Variable Area Setting Range List
The following table lists the data ranges for each type of variable. Refer to the individual items for
details.
●
Variable Type C0
●
Variable Type C1
• The unit for the frequency reference, output frequency, output current, accumulated operating time,
frequency references 1 to 4, acceleration time, and deceleration time is 0.1.
Examples:
0.7
→
H’
00000007
50.0
→
H’
000001F4
120 (120.0)
→
H’
000004B0
• The frequency reference range depends on the frequency reference upper limit and the frequency
reference lower limit.
• The acceleration time, deceleration time, and application selection cannot be written during opera-
tion. (They can be read during operation.)
• 1 kh = 1,000 hours
Address
Name
Setting range
Communications notation
Default
Unit
0000
Frequency reference
0.0 to 120
H’00000000 to H’000004B0
10.0
Hz
0001
Output frequency
---
H’00000000 to H’000004B0
---
Hz
0002
Output current
---
H’00000000 to H’00000032
---
A
0003
Accumulated operat-
ing time
---
H’00000000 to H’000003E7
---
kh
0004
Status
---
---
---
---
Address
Name
Setting range
Communications notation
Default
Unit
0000
Frequency reference
0.0 to 120
H’00000000 to H’000004B0
10.0
Hz
0001
Frequency reference 1
H’00000000 to H’000004B0
10.0
Hz
0002
Frequency reference 2
H’00000000 to H’000004B0
0.0
Hz
0003
Frequency reference 3
H’00000000 to H’000004B0
0.0
Hz
0004
Frequency reference 4
H’00000000 to H’000004B0
0.0
Hz
0005
Acceleration time
0.1 to 999
H’00000001 to H’00002706
10.0
s
0006
Deceleration time
0.1 to 999
H’00000001 to H’00002706
10.0
s
0007
Application selection
0: Fan applica-
tion or pump
application
1: Conveyor
application
H’00000000
H’00000001
1
---