S8VS
5
*1.
Do not use an inverter output for the Power Supply. Inverters with an output frequency of 50/60 Hz are available, but the rise in the internal temperature of the Power Supply may result in
ignition or burning.
*2.
For a cold start at 25
°
C. Refer to
Engineering Data
on page 18 for details.
*3.
If the output voltage adjuster (V. ADJ) is turned, the voltage will increase by more than +15% of the voltage adjustment range (by more than +10% for 240-W models with indication monitor).
When adjusting the output voltage, confirm the actual output voltage from the Power Supply and be sure that the load is not damaged.
*4.
To reset the protection, turn OFF the input power for three minutes or longer and then turn it back ON.
*5.
Displayed on 7-segment LED. (character height: 8 mm)
*6.
Resolution of output voltage indication: 0.1 V, Precision of output voltage indication:
±
2% (percentage of output voltage value,
±
1 digit)
*7.
Resolution of output current indication: 0.1 A; Precision of output current indication:
±
5% F.S.
±
1 digit max. (specified by rated output voltage)
*8.
Resolution of peak-hold current indication: 0.1 A; Precision of peak-hold current indication:
±
5% F.S.
±
1 digit max. (specified by rated output voltage);
Signal width required for peak-hold current: 20 ms
*9.
A Type and B Type: Sinking, AP Type and BP Type: Sourcing, BE Type: No alarm output.
*10.
S8VS-06024A, S8VS-09024A/AP, S8VS-12024A/AP, S8VS-18024A/AP, and S8VS-24024A/AP only
*11.
The range for compliance with EC Directives and safety standards (UL, EN, etc.) is 100 to 240 VAC (85 to 264 VAC).
Power ratings
60 W
90 W
Item
Type
Standard
Maintenance
forecast monitor
Total run time
monitor
Standard
Maintenance
forecast monitor
Total run time
monitor
Efficiency
With 100-VAC input
84% typical
83% typical
83% typical
83% typical
With 200-VAC input
83% typical
85% typical
84% typical
85% typical
Input
Voltage
*
1
100 to 240 VAC (allowable range: 85 to 264 VAC or 80 to 370 VDC
*
11)
Frequency
*
1
50/60 Hz (47 to 450 Hz)
Current
With 100-VAC input
1.7 A max., 1.3 A typical
1.7 A max., 1.3 A typical
2.3 A max., 1.9 A typical
2.3 A max., 1.9 A typical
With 200-VAC input
1.0 A max., 0.68 A typical
1.0 A max., 0.78 A typical
1.4 A max., 1.0 A typical
1.4 A max., 1.2 A typical
Power factor
---
Harmonic current regulation
Conforms to EN61000-3-2
Leakage current
With 100-VAC input
0.5 mA max.
With 200-VAC input
1.0 mA max.
Inrush current
*
2
With 100-VAC input
17.5 A max., 14 A typical
With 200-VAC input
35 A max., 28 A typical
Output
Voltage adjustment range
*
3
−
10% to 15% (with V. ADJ) (The voltage cannot be adjusted for the S8VS-09024
@@@
S-
@
.)
Ripple noise voltage (at rated I/O)
70 mV max.
90 mV max.
250 mV max.
150 mV max.
Input variation influence
0.5% max. (at 85- to 264-VAC input, 100% load)
Load variation influence (rated input voltage)
1.5% max. (with rated input, 0 to 100% load)
Temperature variation influence
0.05%/
°
C max.
Startup time
(at rated I/O)
*
2
With 100-VAC input
620 ms typical
460 ms typical
460 ms typical
660 ms typical
With 200-VAC input
400 ms typical
290 ms typical
300 ms typical
420 ms typical
Output hold time
(at rated I/O)
*
2
With 100-VAC input
34 ms typical
33 ms typical
28 ms typical
28 ms typical
With 200-VAC input
158 ms typical
154 ms typical
132 ms typical
136 ms typical
Additional
functions
Overload protection
*
2
105% to 160% of rated load current (101% to 110% of rated load current for the S8VS-09024
@@@
S-
@
), inverted L voltage drop, intermittent, automatic reset
Overvoltage protection
*
2,
*
4
Yes
Output voltage indication
*
5
No
Yes (selectable)
*
6
No
Yes (selectable)
*
6
Output current indication
*
5
No
Yes (selectable)
*
7
No
Yes (selectable)
*
7
Peak-hold current indication
*
5
No
Yes (selectable)
*
8
No
Yes (selectable)
*
8
Maintenance forecast monitor indication
*
5
No
Yes (selectable)
No
No
Yes (selectable)
No
Maintenance forecast monitor output
No
Yes (transistor output),
30 VDC max., 50 mA max.
*
9
No
Total run time monitor indication
*
5
No
Yes (selectable)
No
Yes (selectable)
Total run time monitor output
*
5
No
Yes (transistor output),
30 VDC max., 50 mA max.
*
9
Undervoltage alarm indication
*
5
No
Yes (selectable)
No
Yes (selectable)
Undervoltage alarm output terminals
No
Yes (transistor output), 30 VDC max., 50 mA max.
*
9
Parallel operation
No
Series operation
Yes for up to 2 Power Supplies (with external diode)
Other
Operating ambient temperature
Refer to the derating curve in . (with no icing or condensation)
Storage temperature
−
25 to 65
°
C
Operating ambient humidity
25% to 85% (Storage humidity: 25% to 90%)
Dielectric strength
3.0 kVAC for 1 min. (between all inputs and outputs/ alarm outputs; detection current: 20 mA)
2.0 kVAC for 1 min. (between all inputs and PE terminals; detection current: 20 mA)
1.0 kVAC for 1 min. (between all outputs/ alarm outputs and PE terminals; detection current for standard models: 30 mA, detection
current for models with indication monitor: 20 mA)
500 VAC for 1 min. (between all outputs and alarm outputs; detection current: 20 mA)
Insulation resistance
100 M
Ω
min. (between all outputs/ alarm outputs and all inputs/ PE terminals) at 500 VDC
Vibration resistance
10 to 55 Hz, 0.375-mm single amplitude for 2 h each in X, Y, and Z directions
10 to 150 Hz, 0.35-mm single amplitude (5 G max.) for 80 min each in X, Y, and Z directions
Shock resistance
150 m/s
2
, 3 times each in ±X, ±Y, and ±Z directions
Output indicator
Yes (color: green)
EMI
Conducted
Emissions
Models with indication monitor: Conforms to EN61204-3 EN55011 Class A and based on FCC Class A, Conforms to EN61204-3
EN55011 Class B
*
11
Standard models: Conforms to EN61204-3 EN55011 Group 1 Class B and based on FCC Class A
Radiated
Emissions
Models with indication monitor: Conforms to EN61204-3 EN55011 Class A, Conforms to EN61204-3 EN55011 Class B
*
11
Standard models: Conforms to EN61204-3 EN55011 Group 1 Class B
EMS
Conforms to EN61204-3 high severity levels
Approved standards
*
11
UL: UL 508 (Listing; Class 2 Output: Per UL1310), UL UR: UL
60950-1 (Recognition),
cUL: CSA C22.2 No.107.1 (Class 2 Output: Per CSA C22.2 No.
223),
cUR: CSA C22.2 No.60950-1,
EN/VDE: EN 50178 (= VDE 0160), EN 60950-1
(= VDE 0805 Teil 1)
KOSHA S Mark
*
10
UL: UL 508 (Listing)
UL Listed (S8VS-09024
@@@
S-
@
only.): UL 508 (Listing, Class 2
Output: Per UL1310),
UL UR: UL 60950-1 (Recognition),
cUL: CSA C22.2 No.107.1,
cUL (S8VS-09024
-@@@
S-
@
only): CSA C22.2 No.107.1 (Class 2
Output: Per CSA C22.2 No. 223),
cUR: CSA C22.2 No.60950-1,
EN/VDE: EN 50178 (= VDE 0160),
EN 60950-1 (= VDE 0805 Teil 1)
KOSHA S Mark
*
10
SEMI
*
11
F47-0706 (With 200-VAC input)
Weight
330 g max.
490 g max.