S8FS-G

18

Engineering Data

Overload Protection

The load and the Power Supply are automatically protected from 
overcurrent damage by this function. Overload protection is activated 
if the output current rises above 105 to 160% of the rated current.
When the output current returns within the rated range overload 
protection is automatically cleared.

Note: 1.

Internal parts may occasionally deteriorate or be damaged 

if a short-circuited or overcurrent state continues during 

operation.

2.

Internal parts may possibly deteriorate or be damaged if the 

Power Supply is used for applications with frequent inrush 

current or overloading at the load end. Do not use the Power 

Supply for such applications.

Overvoltage Protection

Consider the possibility of an overvoltage and design the system so 
that the load will not be subjected to an excessive voltage even if the
feedback circuit in the Power Supply fails. 
If an excessive voltage that is 120% of the rated voltage or more is 
output, the output voltage is shut OFF. 
Reset the input power by turning it OFF for at least three minutes and 
then turning it back ON again.

Overheating Protection (300 W and 600 W)

If the internal temperature of the Power Supply rises excessively as a 
result of fan failure or any other reason, the overheat protection circuit 
will be triggered to shut OFF the output voltage.
To restore operation, turn OFF the input power supply long enough 
for the Power Supply to cool sufficiently and then turn it ON again.

Remote Control Function (Only Remote control)

This function is to turn ON/OFF the output by applying a voltage to the
remote control connector from a DC power Supply (external power 
supply) other than this Power Supply.

Connectors used:

Applicable crimp tool: YC-110R (J.S.T. Mfg. Co., Ltd.) or

YRS-110 (J.S.T. Mfg. Co., Ltd.)

Note: 1.

When the external power supply is 4.5 to 12.5 V, the current 

limiting resistor R is not required. When it is 12.5 to 24.5 V, 

insert 1.5 k

Ω

 as the current limiting resistor R.

2.

Reverse connection of the connector may cause damage 

on the internal parts.

3.

The +RC and -RC terminals are the secondary circuit of the 

Power Supply. Use an SELV output power supply for an 

external power supply. The remote control circuit is 

insulated from the secondary output of the Power Supply 

(functional insulation).

Reference Value

0

50

100

Output current (%)

Output v

oltage (V)

Intermittent operation

Output current (%)

Output v

oltage (V)

50

0

100

Built-in 

resistance 

Ri (

Ω

)

Voltage bRC and 

RC (V)

Inrush current 

(mA)

Output ON 

Output OFF

780

4.5 to 12.5

0 to 0.5

20 max.

CN61

Applicable 

connector

Applicable 

contact

Model

B2B-XH-AM

XHP-2

SXH-001T-P0.6

or

SXH-002T-P0.6

Manufacturer

J.S.T. Mfg. Co., Ltd.

Reliability 

(MTBF)

Value

Single phase model

15W: 970,000

30W: 970,000

50W: 880,000

100W: 730,000

150W: 620,000

300W: 200,000

600W: 190,000

Definition

MTBF stands for Mean Time Between 

Failures, which is calculated according to the 

probability of accidental device failures, and 

indicates reliability of devices.

Therefore, it does not necessarily represent a 

life of the product.

Life expectancy

10 yrs. Min.

Definition

The life expectancy indicates average 

operating hours under the ambient 

temperature of 40°C and a load rate of 50%. 

Normally this is determined by the life 

expectancy of the built-in aluminum electrolytic 

capacitor.

External
power supply
(SELV output)

 Switch

R

 Inflowing current

+RC

RC

1

2

Ri

Inside the power
supply

Remote control connector (CN61)

Usage example of the remote control

Note 1

Summary of Contents for S8FS-G Series

Page 1: ...below Refer to Safety Precautions for All Power Supplies and Safety Precautions on page 29 Output voltage Power rating 15 W 30 W 50 W 100 W 150 W 300 W 600 W 5 V Yes Yes Yes Yes Yes 12 V Yes Yes Yes Y...

Page 2: ...5CD 24 V 1 5 A S8FS G03024CD 50 W 5 V 8 A 1 S8FS G05005CD 12 V 4 3 A S8FS G05012CD 15 V 3 5 A S8FS G05015CD 24 V 2 2 A S8FS G05024CD 100 W 5 V 16 A 2 S8FS G10005CD 12 V 8 5 A S8FS G10012CD 15 V 7 A S8...

Page 3: ...V 3 5 A S8FS G05015C 24 V 2 2 A S8FS G05024C 100 W 5 V 16 A 2 S8FS G10005C 12 V 8 5 A S8FS G10012C 15 V 7 A S8FS G10015C 24 V 4 5 A S8FS G10024C 150 W 5 V 21 A 3 S8FS G15005C 12 V 13 A S8FS G15012C 15...

Page 4: ...cator Yes LED Green Insulation Withstand voltage 3 kVAC for 1 min between all input terminals and output terminals current cutoff 20 mA 2 kVAC for 1 min between all input terminals and PE terminals cu...

Page 5: ...s LED Green Insulation Withstand voltage 3 kVAC for 1 min between all input terminals and output terminals current cutoff 20 mA 2 kVAC for 1 min between all input terminals and PE terminals current cu...

Page 6: ...kVAC for 1 min between all input terminals and output terminals current cutoff 20 mA 2 kVAC for 1 min between all input terminals and PE terminals current cutoff 20 mA 1 kVAC for 1 min between all ou...

Page 7: ...current cutoff 20 mA 2 kVAC for 1 min between all input terminals and PE terminals current cutoff 20 mA 1 kVAC for 1 min between all output terminals and PE terminals current cutoff 20 mA Only Remote...

Page 8: ...tput terminals current cutoff 20 mA 2 kVAC for 1 min between all input terminals and PE terminals current cutoff 20 mA 1 kVAC for 1 min between all output terminals and PE terminals current cutoff 20...

Page 9: ...ator Yes LED Green Insulation Withstand voltage 3 kVAC for 1 min between all input terminals and output terminals current cutoff 20 mA 2 kVAC for 1 min between all input terminals and PE terminals cur...

Page 10: ...LED Green Insulation Withstand voltage 3 kVAC for 1 min between all input terminals and output terminals current cutoff 20 mA 2 kVAC for 1 min between all input terminals and PE terminals current cuto...

Page 11: ...d output current are satisfied Leakage current The values are determined according to the Act on Power Supply Safety of Electrical Appliances and Materials Inrush current for a cold start at 25 C For...

Page 12: ...breakers so that external fuses will not burn out or breakers will not operate due to inrush current Ripple Noise Voltage The specified standard for the ripple voltage noise was measured with a measu...

Page 13: ...N Rectifier Smoothing circuit Rectifier smoothing circuit S8FS G015 15 W S8FS G030 30 W S8FS G050 50 W S8FS G100 100 W S8FS G150 150 W V V DC OUTPUT V V RC RC REMOTE CONTROL Only Remote control AC L...

Page 14: ...rcuit Drive circuit 250 VAC 12 A HBC S8FS G300 300 W S8FS G600 600 W Voltage detection circuit Photocoupler Over voltage detection circuit Over current detection circuit Current detection circuit Over...

Page 15: ...h terminal Connect the ground line to this terminal 2 4 V1 DC output terminals Connect the load lines to these terminals 5 V2 6 V1 7 V2 8 Output indicator DC ON green Lights while a direct current DC...

Page 16: ...below the range of the derating curve shown above by the dashed line by multiplying with the coefficient 0 9 Note At a voltage below 100 VAC reduce the load at the rate of 1 3 V Parallel Operation Fo...

Page 17: ...elow 100 VDC reduce the load by multiplying with the coefficient 0 9 300 W and 600 W Note At a voltage below 100 VAC reduce the load at the rate of 1 3 V 70 45 C max 50 C 60 C 70 C 0 500 1 000 1 500 2...

Page 18: ...a DC power Supply external power supply other than this Power Supply Connectors used Applicable crimp tool YC 110R J S T Mfg Co Ltd or YRS 110 J S T Mfg Co Ltd Note 1 When the external power supply i...

Page 19: ...88 5 0 5 40 0 5 Two M3 55 0 5 Two 3 5 dia Two M3 87 0 5 Two 3 5 dia 74 0 5 5 max 5 32 5 117 7 1 14 3 8 2 9 5 Five M3 5 36 2 1 49 5 3 5 Sliding 6 2 max S8FS G015 CD S8FS G030 CD 17 5 55 0 5 20 5 5 40 0...

Page 20: ...Two M3 55 0 5 Two 3 5 dia 87 0 5 Two M3 74 0 5 Two 3 5 dia 8 2 9 5 5 117 7 1 14 3 37 2 1 49 5 47 5 5 5 Sliding 8 2 max 5 max Five M3 5 S8FS G050 CD 18 5 55 0 5 20 5 5 55 5 0 5 45 5 97 1 36 1 29 3 5 3...

Page 21: ...3 5 dia Three M3 Depth 6 mm max S8FS G100 C Panel mounting holes dimensions Using the mounting holes in the Power Supply Using the screw holes in the Power Supply Side Mounting Bottom Mounting 122 5 0...

Page 22: ...Input L Input N 3 5 dia 3 5 dia Three M3 Depth 6 mm max Two M3 Depth 5 mm max S8FS G100 E Panel mounting holes dimensions Using the mounting holes in the Power Supply Using the screw holes in the Powe...

Page 23: ...even M3 5 Two M3 Depth 5 mm max S8FS G150 C Panel mounting holes dimensions Using the mounting holes in the Power Supply Using the screw holes in the Power Supply Side Mounting Bottom Mounting 152 5 0...

Page 24: ...mm max Three M3 Depth 6 mm max 3 5 dia 3 5 dia Output Output Input L Input N S8FS G150 E Panel mounting holes dimensions Using the mounting holes in the Power Supply Using the screw holes in the Power...

Page 25: ...C Panel mounting holes dimensions Using the screw holes in the Power Supply Side Mounting Bottom Mounting 64 0 5 Two 4 5 dia 74 0 5 20 0 5 Four 4 5 dia 8 2 9 5 201 1 14 1 5 48 5 53 5 42 5 1 4 8 Seven...

Page 26: ...Panel mounting holes dimensions Using the screw holes in the Power Supply Side Mounting Bottom Mounting 150 0 5 100 0 5 Four 4 5 dia 150 0 5 38 0 5 Four 4 5 dia S8FS G600 CD Four M4 8 2 9 5 20 5 10 8...

Page 27: ...is provided with the Power Supply as a standard accessory You can purchase another one if your Cover is damaged or lost Power rating Mounting direction Model 15 W 30 W 50 W 100 W 150 W and 300 W Fron...

Page 28: ...at the Unit will be subject to vibration or shock use a steel DIN Rail Otherwise metallic filings may result from aluminum abrasion 4 5 15 25 25 10 10 1 000 500 25 25 15 5 35 0 3 7 3 0 15 27 0 15 1 Va...

Page 29: ...asures to ensure proper heat dissipation to increase the long term reliability of the Power Supply Be sure to allow convection in the atmosphere around devices when mounting Do not use in locations wh...

Page 30: ...00 20 A S8FS G600 30 A Use two terminals together if the current flow is higher than the rated terminal current Terminals and Wiring Connector type Note 1 The current capacity per output terminal is 5...

Page 31: ...If the list of models that support series connection of outputs says that an external diode is not required an external diode is also not required for positive negative outputs Use the following info...

Page 32: ...s short circuited Checking Overvoltage or Internal Protection Turn the power supply OFF leave it OFF for at least three minutes and then turn it ON again to see if this clears the condition Checking O...

Page 33: ...rect operation of these components to achieve the original Power Supply functions and performance However the influence of the ambient temperature on aluminum electrolytic capacitors is large and the...

Page 34: ...MEMO 34...

Page 35: ...CONNECTED WITH THE PRODUCTS WHETHER SUCH CLAIM IS BASED IN CONTRACT WARRANTY NEGLIGENCE OR STRICT LIABILITY Further in no event shall liability of Omron Companies exceed the individual price of the Pr...

Page 36: ...169 U S A Tel 1 847 843 7900 Fax 1 847 843 7787 Regional Headquarters OMRON EUROPE B V Wegalaan 67 69 2132 JD Hoofddorp The Netherlands Tel 31 2356 81 300 Fax 31 2356 81 388 Contact www ia omron com K...

Reviews: