background image

16

Power Supply 

Technical Information

Selection of Wires

Wires for the Power Supply should must be carefully selected. Refer to this table when selecting the wires.

Recommended Maximum Current: The table is applicable to wires with 1 to 4 conductors. Keep the current value to within 80% of the values shown in this table when 

using wires having 5 or more conductors. The following chart shows the voltage drop per meter in terms of the relationship between 
the current and conductor diameter. Make sure that the current value does not exceed the recommended maximum current value.

Voltage Drop per Meter

 (UL1015 Vinyl-sheathed Wires for Heat-resistant Equipment)

Note. The current indicates the allowable current. In practice, application must be below the recommended current values.

AWG 

No.

Cross-sectional 

area 

(mm

2

)

Configuration 

(number of 

conductors/mm)

Voltage drop per 1 A

(mV/meter)

Recommended maximum current (A)

UL1007 

(300 V 80

°

C)

UL1015 

(600 V 105

°

C)

30

0.051

7/0.102

358

0.12

---

28

0.081

7/0.127

222

0.15

0.2

26

0.129

7/0.16

140

0.35

0.5

24

0.205

11/0.16

88.9

0.7

1.0

22

0.326

17/0.16

57.5

1.4

2.0

20

0.517

26/0.16

37.6

2.8

4.0

18

0.823

43/0.16

22.8

4.2

6.0

16

1.309

54/0.18

14.9

5.6

8.0

14

2.081

41/0.26

9.5

---

12.0

12

3.309

65/0.26

6.0

---

22.0

10

5.262

104/0.26

3.8

---

35.0

Voltage drop (mV)

1,000

900

AWG28

AWG26

AWG24

AWG20

AWG18

AWG16

AWG14

AWG12

AWG10

(See note.)

AWG22

800

700

600

500

400

300

200

100

90

80

70

60

50

40

30

20

10

0.1

0.2

0.3

0.4

0.5 0.6 0.7 0.8 0.9 1

2

3

4

5

6

7

8 9 10

20

30

40

50

60 70 80 90 100

Current (A)

In the interest of product improvement, specifications are subject to change without notice.

ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.

To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527.

Cat. No. T901-E1-01A

Summary of Contents for S82J Series

Page 1: ...d efficient that they are used as power supplies by most electronic devices Advantages Disadvantages Power Supply Selection Basic Selection Points Factors to consider when selecting a Power Supply are...

Page 2: ...ipple and Noise on page 3 Input variation influence The variation in the output voltage when the input voltage gradually varies within the input voltage fluctuation range Refer to Input Variation Infl...

Page 3: ...circuit is short circuited to the terminal by the short bar Leakage current can be reduced by removing the short bar When the leakage current poses a problem such as when using more than one Power Su...

Page 4: ...gram Overcurrent Protection Applicable Models All Models This protection function prevents damage to the Power Supply itself due to overcurrent including output short circuits The protection function...

Page 5: ...the output side Models with the Zener diode clamp system do not restart after the protection circuit operates Send the product for repair For further details refer to the datasheet for individual mod...

Page 6: ...odels that Support Parallel Operation of Outputs Up to two of the same model can be connected in parallel for the S82K 100 W up to four of the same model can be connected in parallel for the S8TS and...

Page 7: ...iciently cooled so that their temperatures remain below the catalog value This is necessary to control the power loss output current of Power Supply IOUT diode forward voltage VF resulting across the...

Page 8: ...from electrical household appliances and electrical equipment Japanese manufacturers have been voluntarily issuing and abiding by the guidelines Main Applicable Models S82K P 24 200 V Series only S8T...

Page 9: ...e of 50 C up to 50 of load rate Mounting direction Standard Horizontal Face up Face down Model S82K OK No Conditional No S8TS OK No No No S8VS 15 30W OK No OK No S8VS 60 90 120 180 240 W OK No No No S...

Page 10: ...3 Consider the allowable current for load short circuits guideline 1 6 times the Power Supply s rated output current or higher Voltage drop mV 1 000 AWG28 See note 700 500 300 100 70 50 30 10 0 1 0 3...

Page 11: ...nd wires as short and as thick as possible Connect a noise filter Include a noise filter on the input side of the Power Supply if faulty operation in electric circuits connected to the output from the...

Page 12: ...ore turning ON the power make sure that the voltage specifications are the same as the voltage of the device The Product is shipped with the input voltage selector terminals open i e set to 200 VAC In...

Page 13: ...ill cause the output to enter the protection range when it turns ON If inrush current flows to the load consider selecting a capacity that allows for the inrush current The output voltage is high The...

Page 14: ...to low input voltage thereby activating the overcur rent protection function Use an input voltage within the allowable range The voltage applied to the load is unstable The Power Supply s output volt...

Page 15: ...ying parts 2 3 rated voltage AC for 1 min Double insulation between current carrying parts and non current carrying metal parts AC 1 min Up to 150 V 1 000 V Over 150 V 1 500 V Up to 150 V Over 150 V F...

Page 16: ...Cross sectional area mm2 Configuration number of conductors mm Voltage drop per 1 A mV meter Recommended maximum current A UL1007 300 V 80 C UL1015 600 V 105 C 30 0 051 7 0 102 358 0 12 28 0 081 7 0...

Reviews: