15
S82H
S82H
Installation
■
Terminal Arrangement
S82H-
@
100
@@
(100 W)
S82H-
@
150
@@
(150 W)
1.
DC Output Terminals
: Connect the load lines to these terminals.
2.
Input Terminals L and N (with fuse inserted into the L side)
: Connect the input lines to these terminals.
3.
Output voltage adjustment trimmer V.ADJ (with adjustment range of
±
10% of rated output)
: Adjusts the output voltage.
4.
Output indicator DC ON (green)
: Lit while a DC output is ON.
5.
Remote sensing terminals
: Corrects the voltage drop in the load lines.
6.
Remote control terminals
: Enables external signals to turn the output ON and OFF while the input voltage is imposed. The
terminals are short-circuited with a short bar before shipping.
7.
ACG Terminal
: The intermediate point of the input filter. The terminal is short-circuited to the ground terminal (GR) before shippi
8.
Ground Terminal (GR)
: Shorted to the housing. Ground the Power Supply through this terminal.
9.
Fan alarm terminals FAN ALM
: Turns ON when the revolution of the built-in fan drops.
10.
Output voltage monitor terminals
: Connected to the DC output terminals internally. No output current can be, however,
obtained from these terminals. Short-circuit the terminals to the remote sensing terS and
−
S if the remote sensing
function is not used.
11.
Short bar
S82H-P300
@@
(300 W)
S82H-P600
@@
(600 W)
(1)
(5)
(3)
(5)
(7)
(2)
(4)
(11)
(8)
(5)
(3)
(4)
(1)
(5)
(2)
(6)
(11)
(7)
(8)
(9)
(6)
(5) (10)
(3) (4)
(2)
(7) (8)
(11)
(9)
(6)
(5) (10)
(3) (4)
(2)
(7)
(8)
(1)
(11)
(1)
(5)
(5)