9 Communications Functions
9 - 16
High-function General-purpose Inverter RX2 Series User’s Manual
Query
Response
*1. During a broadcast, no response will be sent back.
*2. Note that the coil start number is 0004, which is 1 less than the coil number 0005.
*3. Since the change data comprises both MSB and LSB as a set, make the byte to be an even number by add-
ing 1, even if the byte which actually needs to be changed is an odd number.
Input terminal is recognized as ON when either the terminal block input or the communications setting
turns ON.
If the Write to Holding Register function is not executed normally, refer to
No.
Field name
Example [hex]
Remarks
1
Slave address
*1
05
2
Function code
0F
3
Coil start number (MSB)
*2
00
(Coil address) = (Coil number) – 1
4
Coil start number (LSB)
*2
04
5
Number of coils (MSB)
00
6
Number of coils (LSB)
06
7
Number of bytes
*3
02
8
Change data (MSB)
*3
17
17 hex = 0 0 0 1 0 1 1 1
Input terminal 6 Input terminal 1
9
Change data (LSB)
*3
00
10
CRC-16 (MSB)
DB
11
CRC-16 (LSB)
3E
No.
Field name
Example [hex]
1
Slave address
05
2
Function code
0F
3
Coil start number (MSB)
00
4
Coil start number (LSB)
04
5
Number of coils (MSB)
00
6
Number of coils (LSB)
06
7
CRC-16 (MSB)
34
8
CRC-16 (LSB)
4C
Summary of Contents for RX - 2
Page 1: ...High function General purpose Inverter RX2 Series User s Manual I620 E1 01 3G3RX2...
Page 54: ...1 Overview 1 22 High function General purpose Inverter RX2 Series User s Manual...
Page 136: ...2 Design 2 82 High function General purpose Inverter RX2 Series User s Manual...
Page 592: ...8 Applied Settings 8 192 High function General purpose Inverter RX2 Series User s Manual...
Page 754: ...11 Options 11 56 High function General purpose Inverter RX2 Series User s Manual...
Page 794: ...12 Troubleshooting 12 40 High function General purpose Inverter RX2 Series User s Manual...
Page 919: ......