16
2. Installation and connection
Are the same as shown above.
➜
When A: Operation is normal. The battery is charged sufficiently.
➜
When B: Operation is normal, but the battery is not sufficiently
charged.
Are not the same as shown above.
➜
Operation is abnormal. Check the status of lamps and beep and
turn off the Power Switch.
• If the display is No.7 or No.8 of "3. Display and beep when a
failure occurs in equipment" of "4-3 Interpreting a beep and dis-
play" on page 21, take necessary measures and then go back
to (1) on page 15.
• If no Battery Mode is performed and the UPS and the connected
devices stop, insufficient charging of the battery is suspected.
Connect the 100 VAC input plug of the UPS to a wall outlet (com-
mercial power), charge the battery for approximately 6 hours,
and then go back to (4) on page 15.
• If the problem persists after checking the 2 points above, con-
tact us; ____
(6) Connect the 100 VAC input plug to a wall outlet (commercial power) again.
The Power Output Lamp stops blinking and turns on without intervals, and the beeper stops.
(The status is as shown below.)
Checking the operation is now complete.
Installation and connection is now complete.
(Red)
Alarm
Off
(Green) Power Output
On
Beep
None
Power Supply Output Receptacles
Supply power (connected devices are powered).