V+

CAN H

DeviceNet

Physical Layer

Internal

Circuit

DC/DC

Converter

(Non Isolated)

DC/DC

Converter

(Isolated)

Safety Input

Circuit

Test Output

Circuit

Safety Output

Circuit

USB

DRAIN

CAN L

V-

D+

D-

V0

G0

V1

24VDC

24VDC

24VDC

G

V2

G

T0

T7

IN0

IN39

OUT0

L

L

OUT7

IN0

IN1

IN2

IN3

IN4

IN5

IN6

IN7

IN8

IN9

IN10

IN11

IN12

IN13

IN14

IN15

Reset

KM1-NC

KM2-NC

E2

E1

V2

V1

+

-

+

-

G

G

IN16

IN17

IN18

IN19

T0

T1

T2

T3

OUT0

OUT1

OUT2

OUT3

KM2

E1,E2 : 24VDC Power Source
S1 : Emergency Stop Switch(Positive Opening Contact)
KM1,KM2 : Contactor

KM1

LEDs
MS:Module Status
NS:Network Status
LOCK:Configuration Lock
COMM:USB communication

7-Segment LED

Removable terminal (I/O)

Removable terminal (Power,I/O)

Node Address
Switch

Baud Rate
Switch

USB Port

DeviceNet
Connector

Input LED

Output LED

131.4

135.6

(114.1)

(99)

111.1

Indicates a potentially hazardous situation which, if not avoided, will 
result in minor or moderate injury, or may result in serious injury or 
death. Additionally there may be significant property damage.

Indicates prohibited actions

Indicates mandatory actions

EU Declaration of Conformity

Standards

WARNING

Requirements

Controlling Devices

Use approved devices with Direct Opening Mechanism complying with 
IEC/EN 60947-5-1.

Emergency stop 
switch

Use approved devices with Direct Opening Mechanism complying with 
IEC/EN 60947-5-1 and capable of switching micro loads of 24VDC, 4mA.

Door interlocking 
switch
Limit switch

Use approved devices with forcibly guided contacts complying with 
IEC61810-3.
For feedback purpose, use devices with contacts capable of switching 
micro loads of 24VDC, 4mA.

Relay with forcibly 
guided contacts

Use contactors with forcibly guided mechanism and monitor its auxiliary 
NC contact to detect failures of contactor.
For feedback purpose, use devices with contacts capable of switching 
micro loads of 24VDC, 4mA.

Contactor

Use approved sensors complying with the relevant product standards, 
regulations, and rules in the country where it is used.

Safety sensor

Evaluate whether devices used are appropriate to satisfy the requirements 
of safety category level.

Other devices

Serious injury may possibly occur due to loss of required safety functions. Do not use 
DeviceNet standard I/O data or Explicit message data as any safety data.
Serious injury may possibly occur due to loss of required safety functions. Do not use 
LEDs on the NE1A-SCPU02 for safety operations.

Serious injury may possibly occur due to loss of required safety functions. Do not use 
test outputs of the NE1A-SCPU02 as any safety outputs.

The following alert symbols are used in this manual.

Serious injury may possibly occur due to breakdown of outputs. Do not connect loads 
beyond the rated value to the safety outputs and the test outputs.

Serious injury may possibly occur due to loss of required safety functions.Ground the 
0V line of the power supply for external output devices so that the devices do Not 
turn ON when the safety output line or the test output line is grounded.
Serious injury may possibly occur due to loss of required safety functions. Use 
appropriate components or devices according to the requirements given in the 
following table.

Serious injury may possibly occur due to loss of required safety functions.Wire the 
NE1A-SCPU02 properly so that 24VDC line do NOT touch the outputs accidentally or 
unintentionally.

Thank you for purchasing this NE1A-SCPU02.
This manual primarily describes precautions required in installing and operating the 
NE1A-SCPU02.

• Only qualified person trained in professional electrical technique should be handle the 

NE1A.

• Before operating the NE1A-SCPU02, read this manual through to acquire sufficient 

knowledge of the NE1A-SCPU02.

• To ensure safe and correct use of the NE1A-SCPU02, also read the following manuals:

• Safety Network Controller OPERATION MANUAL(Cat.No.Z906-E1)
•  SYSTEM CONFIGURATION MANUAL(Cat.No.Z905-E1)
•  DeviceNet™ OPERATION MANUAL (Cat. No. W267-E1)

• Keep this manual for future reference.

INSTRUCTION MANUAL

Alert Statements

Meaning of Alert Symbols

WARNING

TYPE NE1A-SCPU02
Safety Network Controller

Original instructions

NE1A-SCPU02 is designed and manufactured in accordance with the following standards:

EN ISO13849-1:2015 Cat.4 PL e   

EN62061

IEC61326-3-1 

    EN60204-1

EN 

ISO13850 

    NFPA 

79

IEC61508 parts 1-7 SIL3 

 

 

ANSI RIA 15.06

EN61131-2 

    ANSI 

B11.19

UL508 

     CSA 

C22.2 

No.142, 

No.213

ANSI/ISA 

12.12.01 

   ANSI/UL1998

EN ISO13849-2

• The maximum terminal temperature is 80 °C
• Use SELV Power Source for the DC main power source.

English

OMRON declares that NE1A-SCPU02 is in conformity with the requirements of the following EU 
Directives:

EMC Directive:2014/30/EU 

 

 

Machinary Directive:2006/42/EC

Instructions in the official EU languages and a signed EU Declaration of Conformity in 
English are available on our website at http://www.ia.omron.com/support/models/.

In case that a safety output is configured as “Safety Pulse Test”, while this output is in an ON state, the pulsed 
off signal(pulse width:580µs) is output continuously for fault diagnosis. Confirm response time of device 
connected to safety outputs so the device does not malfunction due to this off pulse.

2)

 T0-T7 total current at the same time:1.4A

1)

 V0-G0: for internal logic circuit, V1-G: for external input devices and test outputs

   V2-G: for external output devices

Item

Specifications

DeviceNet supply voltage

11 to 25VDC (Supplied from communications power supply)

Current consumption V0 (internal logic circuit)

280mA at 24VDC

DeviceNet current consumption

15mA at 24VDC

Device supply voltage V0, V1, V2 

1)

20.4 to 26.4VDC (24VDC, -15% to +10%)

EMC

Conform to IEC61131-2

Operating Temperature

-10 to +55deg.C

Storage Temperature

-40 to +70deg.C

Relative Humidity

10 to 95% non-condensing

Vibration resistance

0.35 mm at 10 to 57Hz, 50m/s

2

 at 57 to 150Hz

Shock resistance

150m/s

2

: 11ms

Over Voltage Category

II (per IEC61131-2: 4.4.2)

Weight

690g

Protection degree

IP20

1. SPECIFICATIONS

Specifications

Current sinking
11VDC min.
5VDC max.
1mA max.
4.5mA

Do not drop the NE1A-SCPU02 to the ground or excessive vibration or mechanical shocks. The NE1A-SCPU02 
may be damaged and may not function properly.

Precautions for Safe Use

• Use the NE1A-SCPU02 within an enclosure with IP54 protection or higher of IEC/EN 60529.
• Use DIN rail (TH35-7.5 according to IEC60715) for placing the NE1A-SCPU02 into the control board.
• Mount the NE1A-SCPU02 to DIN rails with attachments (TYPE PFP-M, not incorporated to this product), not to 

drop out of rails by vibration etc.

• Spacing should be available around the NE1A-SCPU02 at least 50mm from its top and bottom surfaces for 

ventilation and wiring.

• This is a class A product. In residential areas it may cause radio interference, in which case the user may be 

required to take adequate measures to reduce interference.

• Use the following to wire external I/O devices to the NE1A-SCPU02.

• Disconnect the NE1A-SCPU02 from power supply when wiring. Devices connected to NE1A-SCPU02 may 

operate unexpectedly.

• Apply properly specified voltages to the NE1A-SCPU02 inputs. Applying inappropriate DC voltage and any AC 

voltages cause the NE1A-SCPU02 to fail.

• Be sure to separate the communication cable and the I/O cable from the high-voltage/current lines.
• Be cautious not to have your fingers caught when attaching connectors to the plugs on the NE1A-SCPU02.
• Mount screw of DeviceNet Connector and I/O Connector correctly. (0.25-0.3N•m)
• Incorrect wiring may lead to loss of safety function. Wire conductors correctly and verify the operation of the 

NE1A-SCPU02 before commissioning the system in which NE1A-SCPU02 is incorporated.

• After wiring is completed, be sure to remove label for wire clipping prevention on the NE1A-SCPU02 to enable 

heat to escape for proper cooling.

• Disconnect the NE1A-SCPU02 from power supply when replacing. Devices connected to the NE1A-SCPU02 may 

operate unexpectedly.

• Do not dismantle, repair, or modify the NE1A-SCPU02. It may lead to loss of its safety functions.

Use DC power supply satisfying requirements below.
• Secondary circuits of DC power supply is isolated from its primary circuit by double insulations or reinforced 

insulations.

• DC power supply satisfies the requirement for class 2 circuits or limited voltage/current circuit stated in UL 508.
• 20ms or over of the output hold time.
• DC power supply that satisfies the requirements for SELV given in IEC/EN60950-1 or EN 50178.

Solid wire
Standard (Flexible) wire

0.2 to 2.5mm

2

   AWG24 to 12

0.34 to 1.5mm

2  

AWG22 to 16

Do not use or store the NE1A-SCPU02 in any of the following locations.

• Locations subject to direct sunlight.
• Locations subject to temperatures or humidity outside the range specified in the specifications.
• Locations subject to condensation as the result of severe changes in temperature.
• Locations subject to corrosive or flammable gases.
• Locations subject to dust (especially iron dust) or salts.
• Locations subject to water, oil, or chemicals.
• Locations subject to shock or vibration.

Take appropriate and sufficient countermeasures when installing systems in the following locations. Inappropriate 
and insufficient measures may result in malfunction.

• Locations subject to static electricity or other forms of noise.
• Locations subject to strong electromagnetic fields.
• Locations subject to possible exposure to radioactivity.
• Locations close to power supplies.

• Be cautious not to have you injured when dismantling the NE1A-SCPU02.
The above-mentioned is a part of directions. Please use it after reading the operation manual.

Handle with care

Installation and storage environment

Installation/ Mounting

Installation/ Wiring

Power Supply Selection

Periodical Inspection and Maintenance

Disposal

Environmental Specifications

Item

Inputs type
ON voltage
OFF voltage
OFF current
Input current

Specifications

Current sourcing
0.7A max. / channel 

2)

1.2V max.
0.1mA max.

Item

Outputs type
Rated output current
Residual voltage
Leakage current

Safety Input Specifications

Specifications

Current sourcing
0.5A / channel 
1.2V max.
0.1mA max.

Item

Outputs type
Rated output current
Residual voltage
Leakage current

Safety Output Specifications

Test Output Specifications

• Node Address is settable by 2 digit 10-position Rotary Switch.
• Node Address range is from 0 to 63.(Default:63)
• If set from 64 to 99,Node Address is settable by Configuration tool.

X : Don't care

 0  1  2

  3  4

  5 

 6  7

  8

  9 

 0  1  2

  3  4

  5 

 6  7

  8

  9 

x10

x10

x1

x1

1
2

O
N

3
4

 ON

• At normal state, 7-Segment LED displays the node address of the NE1A-SCPU02 itself in decimal number 

(00-63). The node address, depending on the operational state of the NE1A-SCPU02, turns “ON” or “Flashing”.

• If in fault status, error code and error occurrence node address are displayed alternately in the order of node 

address.

• In “standalone mode”,  “nd” is displayed in the normal condition.

(Unit:mm)

LED Designations

MS

(Module Status)

NS

(Network Status)

LOCK

(Configuration

Lock)

COMM

(USB)

IN 0, 1, 2 • • • 39

OUT 0, 1,2 • • • 7

(I/O status)

In Executing
In Idle
In Critical fault
In Recoverable fault
In Self Testing, Waiting for TUNID, or Configuring

LED Color

Green/Red

Green

Red

Failure detected in the Input / Output circuit Discrepancy 

error has occurred in I/O set for dual channel mode
Failure detected in the associated I/O circuit in case of 

dual channel configuration

Indicators

7 segment LEDs

Rotary Switch

Dip Switch

Terminal Designations and functions

Status

Lit
Flashing
Lit
Flashing

Online connection established
Online but connection not established
Critical link failure
Connection time-out

Green

Red

Red

Yellow

Lit
Flashing
Lit
Flashing

Flashing

No power

-

Not lit

Not online / Not powered

-

Not lit

In Waiting for TUNID

Green/Red

Flashing

Locked Valid Configuration
Unlocked Valid Configuration

Lit
Flashing

Invalid Configuration

Not lit

Communicating

Flashing

Not communicating

Not lit

Yellow

Yellow

-

Input / Output signal ON

Lit

Lit

Input / Output signal OFF

Not lit

Flashing

Description

3. INTERNAL CIRCUITRY AND WIRING

Test output terminal for use in conjunction with IN0 through IN19 safety 
inputs. Each test output provides a unique set of test pulse patterns. T3 also 
supports current monitoring of the output signal for e.g. muting applications. 

Descriptions

Power terminal for external input devices and test outputs. 
Power terminal for external input devices and test outputs. 
Power terminal for external output devices e.g. safety outputs. 
Power terminal for external output devices e.g. safety outputs. 
Terminal for Safety input signals.

Power terminal for internal circuit (Logic). 
Power terminal for internal circuit (Logic). 

Terminal

Designations

V0

G0

V1

G

V2

G

IN0 through IN39

Terminal for Safety outputs

OUT0 through OUT7

T0 through T3

Test output terminal for use in conjunction with IN20 through IN39 safety 
inputs. Each test output provides a unique set of test pulse patterns. T7 also 
supports current monitoring of the output signal for e.g. muting applications. 

T4 through T7

2. PART NAMES AND FUNCTION / DIMENSIONS

Baud Rate

125Kbit/s (default) 
250Kbit/s 
500Kbit/s

Auto Baud Rate Detection

Software setting 

1

2

3

4

Switch

OFF
OFF
OFF
OFF

OFF
OFF

OFF

OFF

OFF

OFF

OFF
OFF

OFF

OFF

OFF

OFF
OFF
OFF
OFF

ON

ON
ON

ON
ON
ON
ON

ON

ON

ON

ON

ON

ON

1

X

X

X

V+

CAN H

Drain

CAN L

V-

Color

Description

Red

V+

White

Signal(CAN H)
Drain

Blue

Signal(CAN L)

Black

V-

DeviceNet Connector

Internal Circuitry and wiring example

I/O Wiring example: Emergency Stop (dual channel) with manual reset

Omron Companies shall not be responsible for conformity with any standards, codes 
or regulations which apply to the combination of the Product in the Buyer’s application 
or use of the Product. At Buyer’s request, Omron will provide applicable third party 
certification documents identifying ratings and limitations of use which apply to the 
Product. This information by itself is not sufficient for a complete determination of the 
suitability of the Product in combination with the end product, machine, system, or 
other application or use. Buyer shall be solely responsible for determining 
appropriateness of the particular Product with respect to Buyer’s application, product 
or system. Buyer shall take application responsibility in all cases.

NEVER USE THE PRODUCT FOR AN APPLICATION INVOLVING SERIOUS RISK 
TO LIFE OR PROPERTY OR IN LARGE QUANTITIES WITHOUT ENSURING THAT 
THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS, 
AND THAT THE OMRON PRODUCT(S) IS PROPERLY RATED AND INSTALLED 
FOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT OR SYSTEM.

Suitability for Use

Additional Precautions According to ANSI/ISA 12.12.01

1. This equipment is suitable for use in Class I, Div.2, Group A, B, C, D or Non-Hazardous Locations Only.
2. WARNING: Explosion Hazard-Substitution of Components may Impair Suitability for Class I, Div.2.
3. WARNING: Explosion Hazard. Do not Disconnect Equipment Unless Power Has Been Switched off or the Area Is

    Known to Be Non-Hazardous.
4. This device is open-type and is required to be installed in an enclosure suitable for the environment and can only be

    accessed with the use of a tool or key.
5. WARNING: Explosion Hazard - Do not connect USB Connector Unless Power Has Been Switched Off Or The Area 
    Is Known To Be Non-Hazardous.

1. Cet equipement convient a l'utilisation dans des emplacements de Classe I, Division 2, Groupes A, B, C, D, ou ne 
    convient qu'a l'utilisation dans des endroits non dangereux.
2. AVERTISSEMENT - Risque d'explosion - La substitution de composants peut rendre ce materiel inacceptable pour 
    les emplacements de Classe I, Division 2
3. AVERTISSEMENT - Risque d'explosion - Avant de debrancher l'equipement, couper le courant ou s'assurer que 
    l'emplacement est designe non dangereux.
4. Ce dispositif est de type ouvert et doit etre installe dans un coffret adapte a l'environnement et auquel on ne pourra  
    acceder uniquement au moyen d'un outil ou d'une cle.
5. AVERTISSEMENT - Risque d'explosion - Ne pas déconnecter l'USB avant que l'alimentation ait été coupée ou que 
    la zone soit reconnue comme non dangereuse.

Altitude

Max. 2000m

Pollution Degree

2

11

12

21

22

S1

KM2

KM1

M1

Regional Headquarters
OMRON EUROPE B.V. (Importer in EU)

Note:

 Specifications subject to change without notice.

Wegalaan 67-69,2132 JD Hoofddorp
The Netherlands
Tel: (31)2356-81-300
Fax: (31)2356-81-388

OMRON ASIA PACIFIC PTE. LTD.

No. 438A Alexandra Road #05-05/08
(Lobby 2), Alexandra Technopark, 
Singapore 119967
Tel: (65) 6835-3011
Fax: (65) 6835-2711

OMRON ELECTRONICS LLC

2895 Greenspoint Parkway, Suite 200 
Hoffman Estates, IL 60169 U.S.A.
Tel: (1) 847-843-7900
Fax: (1) 847-843-7787

OMRON (CHINA) CO., LTD.

Room 2211, Bank of China Tower,
200 Yin Cheng Zhong Road,
Pu Dong New Area, Shanghai, 
200120, China
Tel: (86) 21-5037-2222
Fax: (86) 21-5037-2200

OMRON Corporation (Manufacturer)

Shiokoji Horikawa, Shimogyo-ku, Kyoto, 600-8530 JAPAN

Contact:  www.ia.omron.com

© OMRON Corporation 2006-2021 All Rights Reserved.

0631730-2 I