3 Installation and Wiring
3 - 10
NA-series Programmable Terminal Hardware(-V1) User’s Manual (V125)
Use the enclosed power supply connector to connect the power supply to the NA Unit.
• We recommend that you use a power supply cable with the following stranded wires. Wire the power
supply giving sufficient consideration to the voltage drop and heat generation for the cable length in
the installation environment.
Applicable Wires (Stranded Wires)
Power Supply Connector
Wiring Materials
Size
Conductor cross-section
AWG12 to AWG22
0.35 to 3.31 mm
2
Pin No.
Signal name
Name
1
+24 V
+24-V input
2
0 V
0 V
3
FG
Functional ground
Wiring
Pin No.
1
2
3
Functional ground
(Refer to
Grounding
, below.)
Breaker
24-VDC
power supply
Summary of Contents for NA-series
Page 8: ...Sections in this Manual 6 NA series Programmable Terminal Hardware V1 User s Manual V125 ...
Page 12: ...CONTENTS 10 NA series Programmable Terminal Hardware V1 User s Manual V125 ...
Page 82: ...3 Installation and Wiring 3 22 NA series Programmable Terminal Hardware V1 User s Manual V125 ...
Page 164: ...5 Troubleshooting 5 18 NA series Programmable Terminal Hardware V1 User s Manual V125 ...
Page 179: ...I 1 I NA series Programmable Terminal Hardware V1 User s Manual V125 Index ...
Page 181: ......