1.4 Format
standard
1-3
Overview
Main functions
This section describes main functions of Model KM1.
z
Function by unit
PMU1A (Electric power)
: Provides the power measurement function and 3-STATE
function.
PMU2A (Power two-system) : Provides the power measurement function and 3-STATE
function. Two-system measurements can be done.
EMU8A (Pulse/temperature) : Has an event input and temperature input. It provides
temperature measurement function.
CTD8E (CT expansion)
: CT can be expanded to perform power and current multi-circuit
measurements.
z
Output function
The following function is provided as an output function.
1) Total power consumption pulse output
PMU1A
(Electric power)
PMU2A
(Power two-system)
EMU8A
(Pulse/temperature)
CTD8E
(CT expansion)
{
{
×
×
{
: With function
×
: Without function
When the total power consumption reaches the pulse output unit set by the user, pulses are
output from output terminal 1, output terminal 2, and output terminal 3 (terminal set by the
output terminal function setting).
The pulse ON time is normally fixed to 500 ms. The time for turning OFF the pulse is 100 ms
minimum. However, if it reaches the pulse output unit again within 600 ms after having reached
the pulse output unit, the pulse ON time becomes shorter, because higher priority is given to
the next output. After that, pulse of 100 ms is turned OFF, and then the next pulse is turned ON.
(The minimum pulse ON time is 100 ms.)
Pulse output is judged at sampling intervals.
Pulse output timing
500ms
500ms
500ms
500ms
100ms
100ms
100ms
500ms
100ms
*
▼
indicates that the pulse output unit is reached.