Screw Mounting

1.

Pull out the two hooks on the back of the Relay to the outside until 

you hear them click in place.

2.

Insert M3 screws into the hook holes and secure the Relay.

Adjusting the Setting Knobs

• Use a flat-blade screwdriver to adjust the setting knobs. The knobs 

have a stopper that prevents them from turning beyond the full right 
or left position. Do not force a knob beyond these points.

• To reduce the error in the setting knob, always turn the setting knob 

from the minimum setting toward the maximum setting.

Connecting Wires to the Push-In Plus Terminal Block

Part Names of the Terminal Block

Connecting Wires with Ferrules and Solid Wires

Insert the solid wire or ferrule straight into the terminal block until the 
end strikes the terminal block.

If a wire is difficult to connect because it is too thin, use a flat-blade 
screwdriver in the same way as when connecting stranded wire.

Connecting Stranded Wires

Use the following procedure to connect the wires to the terminal block.

1.

Hold a flat-blade screwdriver at an angle and insert it into the 

release hole. The angle should be between 10° and 15°.

If the flat-blade screwdriver is inserted correctly, you will feel the 

spring in the release hole.

2.

With the flat-blade screwdriver still inserted into the release hole, 

insert the wire into the terminal hole until it strikes the terminal block.

3.

Remove the flat-blade screwdriver from the release hole.

Checking Connections

• After the insertion, pull gently on the wire to make sure that it will 

not come off and the wire is securely fastened to the terminal block.

• If you use a ferrule with a conductor length of 10 mm, part of the 

conductor may be visible after the ferrule is inserted into the 
terminal block, but the product insulation distance will still be 
satisfied.

Removing Wires from the Push-In Plus Terminal Block

Use the following procedure to remove wires from the terminal block.
The same method is used to remove stranded wires, solid wires, and 
ferrules.

1.

Hold a flat-blade screwdriver at an angle and insert it into the 

release hole.

2.

With the screwdriver still inserted into the release hole, remove the 

wire from the terminal insertion hole.

3.

Remove the flat-blade screwdriver from the release hole.

(1)

(1)

(2)

(2)

Two M3 screw holes or
two 3-dia. holes

108

Mounting Hole Dimensions

Note: 1.

Pull out the hooks to mount

the Relay with screws.

2.

Recommended tightening 

torque: 0.5 to 0.6 N·m.

Setting knob

Release hole

Terminal 
(Insertion) hole

Release hole

Terminal 
(Insertion) hole

<Upper side>

<Lower side>

Ferrule

Release hole

Terminal 
(Insertion) hole

Ferrule

Release hole

Terminal 
(Insertion) hole

<Upper side>

<Lower side>

Wire

Flat-blade screwdriver

(1)

(3)

(2)

Wire

Flat-blade screwdriver

(1)

(2)

(3)

10 to 15°

10 to 15°

Flat-blade 
screwdriver

Flat-blade 
screwdriver

<Upper side>

<Lower side>

Wire

Flat-blade screwdriver

(1)

(3)

(2)

Wire

Flat-blade screwdriver

(1)

(2)

(3)

10 to 15°

10 to 15°

Flat-blade 
screwdriver

Flat-blade 
screwdriver

<Upper side>

<Lower side>

Summary of Contents for K8DT-VW

Page 1: ... for commonly asked questions Setting range Power supply voltage Output Model 1 to 10 V AC DC 3 to 30 V AC DC 15 to 150 V AC DC 24 VAC DC Relay SPDT contact output K8DT VW2CD Transistor K8DT VW2TD 100 to 240 VAC Relay SPDT contact output K8DT VW2CA Transistor K8DT VW2TA 20 to 200 V AC DC 30 to 300 V AC DC 60 to 600 V AC DC 24 VAC DC Relay SPDT contact output K8DT VW3CD Transistor K8DT VW3TD 100 to...

Page 2: ...8 mm Ferrule length 8 mm Recommended flat blade screwdriver XW4Z 00B Omron SZF 0 4 2 5 Phoenix Contact 210 719 Wago SDI 0 4 2 5 75 Weidmuller Current capacity 10 A per pole Number of insertions 50 times Case color N1 5 Case material PC UL 94 V 0 Weight Approx 100 g Mounting Mounts to DIN Track or screw mounting Dimensions 17 5 90 90 mm W H D Allowable operating voltage range 85 to 110 of rated pow...

Page 3: ... Output Note Use copper wires with a rating of 75 C or an equivalent rating Inside Inside 2 Output C Relay Output T Transistor Output 3 Power Supply Voltage A 100 to 240 VAC D 24 VAC DC No polarity 14 11 12 A1 A2 A1 A2 14 11 1 Voltage Input VW2 10V max 30V max 150V max VW3 200V max 300V max 600V max A1 V2 V1 14 A2 V3 11 12 C K8DT VW2 C A 1 2 3 V2 V1 V3 C V2 V1 V3 C DIP SW DIP SW Single phase power...

Page 4: ... voltage t Operating time 0 1 to 30 s t1 t1 Power ON lock 1 s or 5 s t t Operating time 0 1 to 30 s Delay time 250 ms reference value t Operating time 0 1 to 30 s Flashing Lit Flashing Lit Hysteresis Fixed at 5 Hysteresis Fixed at 5 AL1 alarm indicator AL2 alarm indicator Contacts 11 14 or transistor output Overvoltage setting AL2 Overvoltage setting AL1 Input Power supply voltage t1 Power ON lock...

Page 5: ...he Unit Note Open the DIP switch cover to set the DIP switch Keep the DIP switch cover closed while the power supply to the Relay is ON Model Setting range Wiring connection K8DT VW2 1 to 10 V AC DC V1 COM 3 to 30 V AC DC V2 COM 15 to 150 V AC DC V3 COM K8DT VW3 20 to 200 V AC DC V1 COM 30 to 300 V AC DC V2 COM 60 to 600 V AC DC V3 COM A1 A2 Power supply voltage Voltage input Single phase power C ...

Page 6: ...imum setting range will be 600 VAC VDC and the setting range will be 60 to 600 V Operating Time The operating time is set using the operating time knob T The operating time can be set to between 0 1 and 30 s If the input exceeds or drops lower than the voltage set value the alarm indicator will start flashing for the set period and then stay lit Dimensions Unit mm Optional Parts for DIN Track Moun...

Page 7: ... How to Measure the Operating Time Overvoltage Change the input suddenly from 0 to 120 of the set value and measure the time until the Unit operates Undervoltage Change the input suddenly from 120 to 0 of the set value and measure the time until the Unit operates Questions and Answers Q Input voltage Set value Alarm indicator Flashing 5 s Lit Contact output or transistor output V 200 VAC A1 Input ...

Page 8: ... alarm outputs may fail to operate This may result in physical damage to the facilities equipment or other devices that are connected to it To reduce this risk inspect the Relay regularly To maintain safety in the event of malfunction of the Relay take appropriate safety measures such as installing a monitoring device on a separate line If the wire insertion length is insufficient fire may occasio...

Page 9: ...o operation check the wiring before you supply power to the product 22 Do not install the product immediately next to heat sources 23 Perform periodic maintenance 24 Do not wire anything to the release holes 25 Do not tilt or twist a flat blade screwdriver while it is inserted into a release hole on the terminal block The terminal block may be damaged 26 Insert a flat blade screwdriver into the re...

Page 10: ...ove the flat blade screwdriver from the release hole Checking Connections After the insertion pull gently on the wire to make sure that it will not come off and the wire is securely fastened to the terminal block If you use a ferrule with a conductor length of 10 mm part of the conductor may be visible after the ferrule is inserted into the terminal block but the product insulation distance will s...

Page 11: ...on and other factors There is basic insulation between the power supply terminals and input terminals There is basic insulation between the power supply terminals and output terminals There is basic insulation between the input terminals and output terminals Operating section must have reinforced or double insulation The sides of the case are not isolated Connect the output contacts contacts with ...

Page 12: ...MEMO 12 ...

Page 13: ... CONNECTED WITH THE PRODUCTS WHETHER SUCH CLAIM IS BASED IN CONTRACT WARRANTY NEGLIGENCE OR STRICT LIABILITY Further in no event shall liability of Omron Companies exceed the individual price of the Product on which liability is asserted Suitability of Use Omron Companies shall not be responsible for conformity with any standards codes or regulations which apply to the combination of the Product i...

Page 14: ...69 U S A Tel 1 847 843 7900 Fax 1 847 843 7787 Regional Headquarters OMRON EUROPE B V Wegalaan 67 69 2132 JD Hoofddorp The Netherlands Tel 31 2356 81 300 Fax 31 2356 81 388 Contact www ia omron com Kyoto JAPAN OMRON ASIA PACIFIC PTE LTD No 438A Alexandra Road 05 05 08 Lobby 2 Alexandra Technopark Singapore 119967 Tel 65 6835 3011 Fax 65 6835 2711 OMRON CHINA CO LTD Room 2211 Bank of China Tower 20...