12 to 24 VDC (Allowable voltage
fluctuation range: 10 to 30 VDC)
(Class 2 Power Supply only)
・
K7L-AT50
0
Ω
to 50 M
Ω
, variable
Range 0: 0 to 250 k
Ω
Range 1: 0 to 600 k
Ω
Range 2: 0 to 5 M
Ω
Range 3: 0 to 50 M
Ω
Note: Set pins 1,2, or 3 of the DIP
switch on the side of the Sensor
Amplifier to the upwards position
according to the range to be
selected. These pins, which are
arranged in numerical order from
left to right, correspond to
ranges 1 through 3. Be sure to
set only the corresponding pin to
the upward position. For range
0, set all these switches
downwards. The adjuster
(ADJUST) on the front panel
allows resistance changes from
0 Ω to the upper limit of the set
range. The adjuster is set to the
upper limit as default. (Normally,
the adjuster should be set to the
upper limit).
・
K7L-U
0
Ω to 1 M Ω , variable.
Note :
The adjuster on the front panel
allows resistance changes from
0 Ω to the
upper limit of the set
range. The adjust
er is set to the
upper limit as default. (Normally,
the adjuster should be set to the
upper limit).
Rated
power
supply
voltage
Operation
resistance
Model
K7L-AT50/K7L-U
Liquid Leakage Sensor
Amplifier
4375510-7 C
INSTRUCTION MANUAL
Thank you for purchasing this OMRON product. Read
this instruction manual and thoroughly familiarize
yourself with the functions and characteristics of the
product before using it. Keep this instruction manual
for future reference.
Precautions for Safe Use
1.Environmental Precautions
・
Use and preserve within the proper temperature
and humidity described in the specifications.
・
Avoid preserving (including during
transportation) and using in a humid place, in a
corrosive gas environment, outdoors and in a
place which receives direct sunlight.
(To detect liquids with high impedances, do not
use in locations with high humidity.)
・
Preserve and use without exposing to danger of
explosion, flammable dust, gas and vapor,
excessive dust, and saline spray or droplets.
・
Avoid preserving (including during
transportation) and using in a place where
vibration and shock are strong.
・
Do not store or use (including during
transportations) where an influence of a static
electricity or an electric field.
・
Do not install the product near devices
generating strong high-frequency waves or
surges.
・To prevent inductive noise, separate Product
as far as possible from high-voltage or
high-current lines. Do not place Product wiring
in parallel with or in the same path as
high-voltage or high-current lines.
・Do not install near devices that generate heat,
such as a coil or a device contains winding
part, etc.
・This is a class A product. In residential areas it
may cause radio interference,in which case
the user may be required to take adequate
measures to reduce interference.
2.Usage Precautions
・
Read the instruction manual and catalog before
operating and maintaining the product.
・
For items such as control power supply or power
supply to provide input power, as well as
distribution cable, use proper specified items.
[Recommended cable: three-core cabtire cable(s)
of completely insulated 600V 0.75mm2 VCT]
・
Use the product within the rated load.
・
Check the usage, the wiring system and the
power source of this product again before using it.
・Please wipe off the electrode area soaked in
the liquid.
・Do not touch the terminals while power is
being supplied. Not doing so may result in
electric shock.
・Do not clean the Product with paint thinner or
other organic solvents. Use commercial
alcohol.
・Do no hold and pull the cable
*In the case of using a Leakage point sensor
(Model F03-16PS/16PS-F), please beware
additionally of description below.
・If you fix a sensor, please use either M5
screw or dedicated attachment (F03-26PS).
・When you use M5 screw,please aware not to
tighten excessively. Doing so, the products
may be transformed or broken.
Recommended screw torque : 0.25N・m to
0.3N・m
Safety Precautions
Indicates a potentially hazardous
situation which, if not avoided, may
result in minor or moderate injury or in
property damage.
Do not touch the terminals.
Doing so may possibly result in electric
shock.
Do not allow pieces of metal or wire
clippings to enter the product while
power is being supplied. Electrical shock,
fire or malfunction may result.
●
Definition of Precautionary Information
●
Precautionary Information
CAUTION
CAUTION
■
Specifications
・
The resistance value adjuster is a precision component. Do not apply a torque to the resistance value adjuster
in excess of the specified one. Doing so may cause the resistance value adjuster to be damaged.
Applicable torque:
・
Rotational torque : 9.81 m N
・
m max.
・
Detent strength : 29.4 m N
・
m min.
・
Use the same Electrodes , Sensing Band and Point Sensor as the ones uesd with OMRON's 61F Floatless Level
Controller OMRON's F03-16PE, F03-15, F03-16PT and F03-16SF Sensing Band OMRON's F03-16PS/16PS-F Point
Sensor. (Read the precaution in the Sensing Band/Point Sensor datasheet.)
・
Use OMRON socket, P2RF-08/P2RF-08-E Surface Socket.
・
Use the F03-20 Terminal Block included with the product.
To make connections, insert the cable from the side of the Terminal Block with a screwdriver inserted in the
top.
After work has been completed, ensure that the devices are still electrically connected.
The Terminal Block made with 66 nylon. Be sure to securely mount the Terminal Block with M3 scerws in a
place where it will not come into contact with chemicals.
・
Applicable torque : M3 scerws : 0.49 N
・
m type.
・
This product has been designed to limit the influence of noise.
However, in order to limit the influence of noise when the location to be monitored is far away, position the
Sensor and the Sensing Band/Point Sensor as close together as power supply and outputs far away.
Omron Companies shall not be responsible for conformity with
any standards, codes or regulations which apply to the
combination of the Product in the Buyer’s application or use of
the Product. At Buyer’s request, Omron will provide applicable
third party certification documents identifying ratings and
limitations of use which apply to the Product. This information by
itself is not sufficient for a complete determination of the
suitability of the Product in combination with the end product,
machine, system, or other application or use. Buyer shall be solely
responsible for determining appropriateness of the particular
Product with respect to Buyer’s application, product or system.
Buyer shall take application responsibility in all cases.
NEVER USE THE PRODUCT FOR AN APPLICATION INVOLVING
SERIOUS RISK TO LIFE OR PROPERTY OR IN LARGE QUANTITIES
WITHOUT ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN
DESIGNED TO ADDRESS THE RISKS, AND THAT THE OMRON
PRODUCT(S) IS PROPERLY RATED AND INSTALLED FOR THE
INTENDED USE WITHIN THE OVERALL EQUIPMENT OR SYSTEM.
Suitability for Use
2 3 4
2
3
29.1
23.1
3
3
4
3.2
3.2
25
2
1
3
2 3 4
5
×
3=15
2.5
3.5
3.5
17.5
5.8
17
5.8
TYPE F03-20
23
±
0.2
2-M3
■
Terminal Block
Mounting holes
12.8
28.8
46
■
Sockets
P2RF-08-E
16
4
85.5
max.
3.5-dia. hole
2
1.5
M3 screw
11.5
61 max.
35.5
39.5
3 dia.
2
48 max.
84 max.
(
Including height of DIN track
)
■
Liquid Leakage Sensor Amplifier
■
Connections
23
4
42
3
5
6
7
8
4
3
2
1
K7L-AT50/K7L-U
12 to 24 VDC
Signal
transmission
OUT
+
Open collector output
OUT
−
100 mA at 30 VDC max.
Level input 1
Level input 2
+
−
Wiring cable
(0.2 mm
2
min.)
Terminal Block
F03-20
Leakage Sensing Band
F03-16PE
OUT
−
100 mA at 30 VDC max.
Wiring cable
(0.2 mm
2
min.)
Signal
transmission
Level input 1
Level input 2
Terminal Block
F03-20
12 to 24 VDC
23
4
42
3
5
6
7
8
4
3
2
1
K7L-AT50/K7L-U
OUT
+
Open collector output
+
−
Leakage Point Sensor
F03-16PS
OUT
−
100 mA at 30 VDC max.
Wiring cable
(0.2 mm
2
min.)
Signal
transmission
Level input 1
Level input 2
12 to 24 VDC
5
6
7
8
4
3
2
1
K7L-AT50/K7L-U
OUT
+
Open collector output
+
−
Leakage Point Sensor
F03-16PS
Leakage Point Sensor
F03-16PS
4
4
3
3
2
2
4
4
3
3
2
2
4
4
3
3
2
2
K7L-AT50 : Total 60m max.
(NOTE. Sensing Band length : 10m max.)
K7L-U : Total 400m max.
Leakage Sensing Band
F03-16PE
Terminal Block
F03-20
・
To wire correctly, please make sure terminal numbers.
・
Check the application and power supply.
・
Use DC power supply of "Class 2 Power Supply" as a condition of UL/CSA approval.
P r e c a u t i o n s f o r C o r r e c t u s e
105 % min. of operae resistance
Release
resistance
NPN open-collector transistor output
with 100mA at 30VDC max.
Note: For output ON when liquid
leakage is detected:
Set pin 4 of the DIP swich
located on the side of the
Sensor Amplifier in the down
position.
For output OFF when liquid
leakage is detected:
Set pin 4 of the DIP swich
located on the side of the
Sensor Amplifier in the up
position.
Operation : -10 to +55
℃
Operation : 45 to 85%RH
Output
configuration
Ambient
temperature
Ambient
humidity
Frequency : 10 to 150 Hz; Acceleration :
15m/s
2
, 10 sweeps of 8 min each in X, Y,
and Z directions.
Vibration
resistance
150 m/s
2
3 times each in 3 axes, 6
directions.
Shock
resistance
・
K7L-AT50
Wiring cable : 50 m max.
Sensing Band : 10 m max.
Any number of F03-16PS Sensors
can be connected in parallel up to
overall cable length of 60 m.
・
K7L-U
Overall cable length (wiring cable
and Sensing Band length total) : 400
m max.
Any number of F03-16PS Sensors
can be connected in parallel up to
overall cable length of 400 m.
Note: These values are possible on
condition that a completely
insulated 3-conductor VCT cable
with a thickness of 0.75 mm
2
and dielectric strength of 600 V
is used together with Liquid
Sensing Band Type F03-16PE
specified by OMRON. (A0.2-
mm
2
cable can also be used.)
Note: When using K7L by CE marking
or Safety Category 1 approved,
a power supply line is wired by
less than 10m.
Wiring
distance
Terminal block (for connecting wiring
cable and Sensing Band/Point Sensor)
Screwdriver for ADJUST setting.
(Purchases the Sensing Band, Sensing
Band Sticker, Point Sensor, Wiring
cable, and Socket etc separately.)
Accessories
Operate, Release : 800 ms max.
Disconnection detection : 10 s max.
Reset the
power supply to stop
disconnection detection.
Response
time
Lit when power is being supplied :
PW LED (Green)
Lit when Liquid Leakage is detected :
OUT LED (Red)
Indicator
●
Wiring
●
Installation
●
Adjuster
●
Leakage Sensing Band/Leakage Point Sensor
●
Surface Socket
●
Terminal Block
●
Wiring Cable
・
Attach to a panel of thickness 1 to 5mm.
・
In case of DIN rail clamping, attach the slider to the product and fasten it to the slider with the projecting
points of unit-side matched to the rail.
・
When removing the product from the rail, insert screwdriver into the groove of slider and slide it outward.
OMRON ELECTRONICS LLC.
One Commerce Drive Schaumburg, IL 60173-5302 U.S.A
Phone: 1-847-843-7900 Fax: 1-847-843-7787
OMRON EUROPE B.V.
Wegalaan 67-69, 2132 JD Hoofddorp The Netherlands
Phone: 31-23-56-81-300 Fax: 31-23-56-81-388
OMRON ASIA-PACIFIC PTE. LTD.
No.438A Alexandra Road #05-05/08(Lobby 2), Alexandra
Technopark, Singapore 119967
Phone: 65-6835-3011 Fax: 65-6835-2711
OMRON CORPORATION
3-4-10 Toranomon Minato-ku, Tokyo, 105-0001 Japan
Phone: 81-3-3436-7260 Fax: 81-3-3436-7261
Contact Information