12 to 24 VDC (Allowable voltage 
 fluctuation range: 10 to 30 VDC)
 (Class 2 Power Supply only)

K7L-AT50

   0 

Ω

 to 50 M

Ω

, variable

   Range 0: 0 to 250 k

Ω

                

   Range 1: 0 to 600 k

Ω

 

   Range 2: 0 to 5 M

Ω

   Range 3: 0 to 50 M

Ω

Note: Set pins 1,2, or 3 of the DIP

           switch on the side of the Sensor

           Amplifier to the upwards position

     according to the range to be

           selected. These pins, which are

           arranged in numerical order from

           left to right, correspond to

           ranges 1 through 3. Be sure to

           set only the corresponding pin to

           the upward position. For range

           0, set all these switches

           downwards. The adjuster

           (ADJUST) on the front panel

           allows resistance changes from

           0 Ω to the upper limit of the set

           range. The adjuster is set to the

           upper limit as default. (Normally,

           the adjuster should be set to the

           upper limit).

K7L-U

   0 

Ω to 1 M Ω , variable.

Note : 

The adjuster on the front panel

           allows resistance changes from

           0 Ω to the 

upper limit of the set

           range. The adjust

er is set to the

           upper limit as default. (Normally,

           the adjuster should be set to the

           upper limit). 

Rated 
power
supply
voltage

Operation
resistance

Model

 

K7L-AT50/K7L-U 

Liquid Leakage Sensor 
Amplifier

4375510-7 C

INSTRUCTION MANUAL

Thank you for purchasing this OMRON product. Read 
this instruction manual and thoroughly familiarize 
yourself with the functions and characteristics of the 
product before using it. Keep this instruction manual 
for future reference.

Precautions for Safe Use

1.Environmental Precautions

Use and preserve within the proper temperature 

and humidity described in the specifications.

Avoid preserving (including during 

transportation) and using in a humid place, in a 
corrosive gas environment, outdoors and in a 
place which receives direct sunlight.

   (To detect liquids with high impedances, do not 

use in locations with high humidity.)

Preserve and use without exposing to danger of 

explosion, flammable dust, gas and vapor, 
excessive dust, and saline spray or droplets.

Avoid preserving (including during 

transportation) and using in a place where 
vibration and shock are strong.

Do not store or use (including during 

transportations) where an influence of a static 
electricity or an electric field.

Do not install the product near devices 

generating strong high-frequency waves or 
surges. 

・To prevent inductive noise, separate Product 

as far as possible from high-voltage or 

high-current lines. Do not place Product wiring 

in parallel with or in the same path as 

high-voltage or high-current lines.

・Do not install near devices that generate heat, 

such as a coil or a device contains winding 

part, etc.

・This is a class A product. In residential areas it

   may cause radio interference,in which case

   the user may be required to take adequate

   measures to reduce interference.

2.Usage Precautions

Read the instruction manual and catalog before 

operating and maintaining the product.

For items such as control power supply or power 

supply to provide input power, as well as 
distribution cable, use proper specified items.
[Recommended cable: three-core cabtire cable(s) 
of completely insulated 600V 0.75mm2 VCT]

Use the product within the rated load.

Check the usage, the wiring system and the 

power source of this product again before using it.

・Please wipe off the electrode area soaked in 

the liquid.

・Do not touch the terminals while power is 

being supplied. Not doing so may result in 

electric shock.

・Do not clean the Product with paint thinner or 

other organic solvents. Use commercial 

alcohol.

・Do no hold and pull the cable

 *In the case of using a Leakage point sensor 

(Model F03-16PS/16PS-F), please beware 

additionally of description below.

   ・If you fix a sensor, please use either M5     

      screw or dedicated attachment (F03-26PS).

  ・When you use M5 screw,please aware not to     

      tighten excessively. Doing so, the products   

      may be transformed or broken.

      Recommended screw torque : 0.25N・m to

      0.3N・m

Safety Precautions

Indicates a potentially hazardous 
situation which, if not avoided, may 
result in minor or moderate injury or in 
property damage.

Do not touch the terminals.
Doing so may possibly result in electric 
shock.

Do not allow pieces of metal or wire 
clippings to enter the product while 
power is being supplied. Electrical shock, 
fire or malfunction may result.

 Definition of Precautionary Information

 Precautionary Information

CAUTION

CAUTION

 Specifications

The resistance value adjuster is a precision component. Do not apply a torque to the resistance value adjuster 

in excess of the specified one. Doing so may cause the resistance value adjuster to be damaged.

    Applicable torque:
        

 Rotational torque : 9.81 m N

m max.

        

 Detent strength    : 29.4 m N

m min.

Use the same Electrodes , Sensing Band and Point Sensor as the ones uesd with OMRON's 61F Floatless Level 

Controller OMRON's F03-16PE, F03-15, F03-16PT and F03-16SF Sensing Band OMRON's F03-16PS/16PS-F Point 
Sensor. (Read the precaution in the Sensing Band/Point Sensor datasheet.)

Use OMRON socket, P2RF-08/P2RF-08-E Surface  Socket.

Use the F03-20 Terminal Block included with the product.

   To make connections, insert the cable from the side of the Terminal Block with a screwdriver inserted in the 

top.

   After work has been completed, ensure that the devices are still electrically connected.
   The Terminal Block made with 66 nylon. Be sure to securely mount the Terminal Block with M3 scerws in a 

place where it will not come into contact with chemicals.

Applicable torque : M3 scerws : 0.49 N

m type.

This product has been designed to limit the influence of noise.

   However, in order to limit the influence of noise when the location to be monitored is far away, position the 

Sensor and the Sensing Band/Point Sensor as close together as power supply and outputs far away.

Omron Companies shall not be responsible for conformity with 
any standards, codes or regulations which apply to the 
combination of the Product in the Buyer’s application or use of 
the Product. At Buyer’s request, Omron will provide applicable 
third party certification documents identifying ratings and 
limitations of use which apply to the Product. This information by 
itself is not sufficient for a complete determination of the 
suitability of the Product in combination with the end product, 
machine, system, or other application or use. Buyer shall be solely 
responsible for determining appropriateness of the particular 
Product with respect to Buyer’s application, product or system. 
Buyer shall take application responsibility in all cases. 

NEVER USE THE PRODUCT FOR AN APPLICATION INVOLVING 
SERIOUS RISK TO LIFE OR PROPERTY OR IN LARGE QUANTITIES 
WITHOUT ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN 
DESIGNED TO ADDRESS THE RISKS, AND THAT THE OMRON 
PRODUCT(S) IS PROPERLY RATED AND INSTALLED FOR THE 
INTENDED USE WITHIN THE OVERALL EQUIPMENT OR SYSTEM.

Suitability for Use

2 3 4

2

3

29.1
23.1

3

3

4

3.2

3.2

25

2

1

3

2 3 4

5

×

3=15

2.5

3.5

3.5

17.5

5.8

17

5.8

TYPE F03-20

23

±

0.2

2-M3

 Terminal Block

Mounting holes

12.8

28.8

46

 Sockets 

P2RF-08-E

16

4

85.5

max.

3.5-dia. hole

2

1.5

M3 screw

11.5

61 max.

35.5

39.5

3 dia.

2

48 max.

84 max.

Including height of DIN track

 Liquid Leakage Sensor Amplifier

 Connections

23

4

42

3

5

6

7

8

4

3

2

1

K7L-AT50/K7L-U

12 to 24 VDC

Signal 

transmission

OUT

+ 

Open collector output

OUT

    100 mA at 30 VDC max.

Level input 1

Level input 2

Wiring cable 
(0.2 mm

min.)

Terminal Block 
F03-20

Leakage Sensing Band
F03-16PE

OUT

    100 mA at 30 VDC max.

Wiring cable 
(0.2 mm

min.)

Signal 

transmission
Level input 1

Level input 2

Terminal Block 
F03-20

12 to 24 VDC

23

4

42

3

5

6

7

8

4

3

2

1

K7L-AT50/K7L-U

OUT

+ 

Open collector output

Leakage Point Sensor

F03-16PS

OUT

    100 mA at 30 VDC max.

Wiring cable 
(0.2 mm

min.)

Signal 

transmission
Level input 1

Level input 2

12 to 24 VDC

5

6

7

8

4

3

2

1

K7L-AT50/K7L-U

OUT

+ 

Open collector output

Leakage Point Sensor

F03-16PS

Leakage Point Sensor

F03-16PS

4

4

3

3

2

2

4

4

3

3

2

2

4

4

3

3

2

2

K7L-AT50 : Total 60m max. 
                   (NOTE. Sensing Band length : 10m max.)
K7L-U       : Total 400m max.

Leakage Sensing Band
F03-16PE

Terminal Block 
F03-20

To wire correctly, please make sure terminal numbers.

Check the application and power supply.

Use DC power supply of "Class 2 Power Supply" as a condition of UL/CSA approval.

P r e c a u t i o n s   f o r   C o r r e c t   u s e

105 % min. of operae resistance

Release
resistance

NPN open-collector transistor output 

with 100mA at 30VDC max.

Note: For output ON when liquid

           leakage is detected: 

           Set pin 4 of the DIP swich

           located on the side of the

           Sensor Amplifier in the down

           position.

           For output OFF when liquid

           leakage is detected:

           Set pin 4 of the DIP swich

           located on the side of the

           Sensor Amplifier in the up 

           position.

Operation : -10 to +55 

Operation : 45 to 85%RH

Output
configuration

Ambient

temperature
Ambient

humidity

Frequency : 10 to 150 Hz; Acceleration :  
15m/s

2

, 10 sweeps of 8 min each in X, Y, 

and Z directions.

Vibration 
resistance

150 m/s

2

  3 times each in 3 axes, 6 

directions.

Shock
resistance

K7L-AT50

    Wiring cable : 50 m max.
    Sensing Band : 10 m max.
    Any number of F03-16PS Sensors      
    can be connected in parallel up to 
    overall cable length of 60 m.

K7L-U

    Overall cable length (wiring cable 
    and Sensing Band length total) : 400   
    m max.
    Any number of F03-16PS Sensors      
    can be connected in parallel up to 
    overall cable length of 400 m.
Note: These values are possible on 
           condition that a completely 
           insulated 3-conductor VCT cable
           with a thickness of 0.75 mm

2

           and dielectric strength of 600 V
           is used together with Liquid
           Sensing Band Type F03-16PE
           specified by OMRON. (A0.2-
           mm

2

 cable can also be used.)

Note: When using K7L by CE marking
           or Safety Category 1 approved,
           a power supply line is wired by
           less than 10m. 

Wiring
distance

Terminal block (for connecting wiring
cable and Sensing Band/Point Sensor)
Screwdriver for ADJUST setting.
(Purchases the Sensing Band, Sensing 
Band Sticker, Point Sensor, Wiring 
cable, and Socket etc separately.)

Accessories

Operate, Release                 : 800 ms max.
Disconnection detection : 10 s max.
Reset the 

power supply to stop 

disconnection detection.

Response 
time

Lit when power is being supplied :
  PW LED (Green) 
Lit when Liquid Leakage is detected : 
  OUT LED (Red)

Indicator

● 

Wiring

● 

Installation

● 

Adjuster

● 

Leakage Sensing Band/Leakage Point Sensor

● 

Surface Socket

● 

Terminal Block

● 

Wiring Cable

Attach to a panel of thickness 1 to 5mm.

In case of DIN rail clamping, attach the slider to the product and fasten it to the slider with the projecting   

points of unit-side matched to the rail.

When removing the product from the rail, insert screwdriver into the groove of slider and slide it outward.

OMRON ELECTRONICS LLC.

One Commerce Drive Schaumburg, IL 60173-5302 U.S.A
Phone: 1-847-843-7900    Fax: 1-847-843-7787

OMRON EUROPE B.V.

Wegalaan 67-69, 2132 JD Hoofddorp The Netherlands
Phone: 31-23-56-81-300    Fax: 31-23-56-81-388

OMRON ASIA-PACIFIC PTE. LTD.

No.438A Alexandra Road #05-05/08(Lobby 2), Alexandra
Technopark, Singapore 119967
Phone: 65-6835-3011   Fax: 65-6835-2711

OMRON CORPORATION

3-4-10 Toranomon Minato-ku, Tokyo, 105-0001 Japan
Phone: 81-3-3436-7260    Fax: 81-3-3436-7261

Contact Information

Reviews: