5 Monitoring and Setting with the EtherNet/IP Communications
K6PM-TH Thermal Condition Monitoring Device User’s Manual (H231)
5-3
Monit
o
rin
g
an
d Sett
ing
Usin
g th
e CIP
Messag
e Com
m
u
n
icat
ion
s and
Exam-
p
les o
f Co
mm
unic
ation
s In
struct
ion
s
5
5-
3-5 Main Unit Setting Object (
C
lass ID: 377 h
ex)
This object writes the setting parameters (such as the existence of alarm latch, transistor output
method, enabling or disabling of "Use predicted arrival time", etc.) of the Main Unit.
Alternatively, it performs each operation instruction (such as K6PM-TH sensor registration, K6PM-TH
sensor location registration, reset of the maximum temperature of all sensors connected to the corre-
sponding Main Unit, etc.).
Note Software reset uses the Identity object (Class ID: 01 hex).
5-3-5
Main Unit Setting Object (Class ID: 377 hex)
Service Codes
Service
code
Service name
Description
Supported services
Classes
Instances
01 hex
Get_Attributes_All
Reads the values of all attributes.
Not supported
Supported
02 hex
Set_Attributes_All
Write values to all attributes.
Not supported
Supported
0E hex
Get_Attribute_Single Reads the value of the specified attribute.
Not supported
Supported
10 hex
Set_Attribute_Single Write the value of the specified attribute.
Not supported
Supported
4B hex
Sensor_Registration K6PM-TH sensor registration
Request data
*1
...
1: Cancel sensor registration. (Change to sen-
sor search mode),
2: Register sensor. (Change to monitoring
mode)
(0001 to 0002 hex, Data type: UINT)
*1. Reset occurs after the command ends normally.
If the mode is already a transition target, an error response (0B hex) is returned.
If 0 sensors are registered for K6PM-TH sensor type registration, an error response (0C hex) is returned.
Not supported
Supported
4C hex
Sensor_-
Mode_Change
Change the K6PM-TH sensor mode
Request data
*2
...
0: K6PM-TH sensor search mode,
1: K6PM-TH sensor 1 position adjustment
mode,
2: K6PM-TH sensor 2 position adjustment
mode,
:
31: K6PM-TH sensor 31 position adjustment
mode (0000 to 001F hex, Data type: UINT)
*2. The K6PM-TH sensor number in the position adjustment mode is reflected in the "Target sensor in position
adjustment mode" of the Main Unit monitor object.
At the same time, bits 5 and 6 of the Main Unit status are updated.
An error response (10 hex) is returned when in the monitoring mode.
Not supported
Supported
Summary of Contents for K6PM-TH
Page 56: ...2 Installation and Wiring 2 20 K6PM TH Thermal Condition Monitoring Device User s Manual H231...
Page 76: ...3 Initial Setting 3 20 K6PM TH Thermal Condition Monitoring Device User s Manual H231...
Page 156: ...7 Troubleshooting 7 8 K6PM TH Thermal Condition Monitoring Device User s Manual H231...
Page 195: ...I 1 I K6PM TH Thermal Condition Monitoring Device User s Manual H231 Index...
Page 197: ......