5 - 13
5 Monitoring and Setting with the EtherNet/IP Communications
K6PM-TH Thermal Condition Monitoring Device User’s Manual (H231)
5-3
Monit
o
rin
g
an
d Sett
ing
Usin
g th
e CIP
Messag
e Com
m
u
n
icat
ion
s and
Exam-
p
les o
f Co
mm
unic
ation
s In
struct
ion
s
5
5-
3-3 K6PM-
T
H Sensor Mo
nitor
Object (C
lass ID: 375 hex)
• K6PM-TH sensor status per sensor
The monitor target (bit 0) of the K6PM-TH sensor status is a target for the registration sensor in the
monitoring mode.
The user can recognize which sensor is the monitor target in the monitoring mode by checking the
monitor target (bit 0).
The bit that is updated in the KP6M-TH sensor search mode or the K6PM-TH sensor position adjust-
ment mode is only the K6PM-TH sensor type and the K6PM-TH sensor angle deviation error.
6A hex
Current value of the K6PM-TH
sensor 1 segment 0 temperature
Current value of the segment tempera-
ture
:
:
6B hex
Current value of the K6PM-TH
sensor 1 segment 1 temperature
Current value of the segment tempera-
ture
Read
UINT
:
:
:
Read
UINT
79 hex
Current value of the K6PM-TH
sensor 1 segment 15 tempera-
ture
Current value of the segment tempera-
ture
Read
UINT
7A hex
Maximum value of the K6PM-TH
sensor 1 segment 0 temperature
Past maximum value of the segment
temperature
:
:
7B hex
Maximum value of the K6PM-TH
sensor 1 segment 1 temperature
Past maximum value of the segment
temperature
Read
UINT
:
:
:
:
:
89 hex
Maximum value of the K6PM-TH
sensor 1 segment 15 tempera-
ture
Past maximum value of the segment
temperature
Read
UINT
8A hex
K6PM-TH sensor 1 segment 0
predicted value
Arrival prediction value of the segment
temperature
Read
UINT
8B hex
K6PM-TH sensor 1 segment 1
predicted value
Arrival prediction value of the segment
temperature
Read
UINT
:
:
:
:
:
99 hex
K6PM-TH sensor 1 segment 15
predicted value
Arrival prediction value of the segment
temperature
Read
UINT
Bit position
Status
Bit contents
0
1
0
Monitor target
Not supported
Supported
1
Reserved
2
Reserved
3
Reserved
4
K6PM-TH sensor type
00: Not determined
01: 32 × 32
5
6
Reserved
7
Reserved
8
K6PM-TH sensor communications error
Not occurred
Occurred
9
K6PM-TH sensor angle deviation
Not occurred
Occurred
10
Temperature measurement range exceeded
Not occurred
Occurred
11
Reserved
12
Reserved
13
Reserved
14
Reserved
15
Reserved
Attribute ID
Parameter name
Description
Attri-
bute
Data
Data type
Summary of Contents for K6PM-TH
Page 56: ...2 Installation and Wiring 2 20 K6PM TH Thermal Condition Monitoring Device User s Manual H231...