Temperature Meter 

K3MA-L

Operation/Adjustment Lockouts

Restricts key operations for operation level and adjustment level.

Initial setting is 0.

This cannot be displayed on models not equipped with the compar-
ative output function.

Setting Level Lockouts

Restricts shifting to initial setting level or advanced-function setting
level.

Setting Change Lockout

Restricts setting changes by key operation. When this lockout is set,
it is no longer possible to shift to a setting change mode.

However, all protect level parameters can still be changed.

Initial Settings

/ /

/ /

/

MODE

MODE

MODE

Operation/adjustment  
lockouts

Setting level lockouts

Setting change lockout

Operation Level

Protect level

Press             Level Key +           Mode Key for more than 1 s.

Press           Level Key +           Mode Key 
for more than preset time.

Paramet

er

Setting

Operation level

Moving to 

adjustment 

level

Process value 

display

Set value 

display

oapt

0

Allowed

Allowed

Allowed

1

Allowed

Allowed

Prohibited

2

Allowed

Prohibited

Prohibited

Parameter

Setting

Shift to initial 

setting level

Shift to 

advanced-

function 

setting level

icpt

0

Allowed

Allowed

1

Allowed

Prohibited

2

Prohibited

Prohibited

Parameter

Setting

Setting change by key 

operation

wtpt

off

Allowed

on

Prohibited

If required, shift to the advanced-function setting level to set the 
number of measurements for averaging, hysteresis values, 
auto-zero time, display color change, display auto-return time, 
or move-to-protect-level time.

Power ON

Press the Level Key        for 3 s min. to move to the initial setting  
level.

Select the input type.

If desired, shift to the adjustment level to set the temperature 
input shift value.

Set the OUT values.

Press the Level Key        for less than 1 s min. to return to the  
operation level.

Measurement starts.

Summary of Contents for K3MA-L

Page 1: ...EMA4X IP66 equivalent front panel Recognized to conform to U S and Canadian requirements un der the Component Recognition Program of UL CE marking Model Number Structure Model Number Legend 1 Input Type L Platinum resistance thermometer or thermocouple 2 Output Type None No output C With relay contact output SPDT 3 Supply Voltage 100 240VAC 100 to 240 VAC 24VAC VDC 24 VAC VDC Ordering Information ...

Page 2: ...X Y and Z directions for 10 sweeps Shock resistance 150 m s2 100 m s2 for relay contact outputs 3 times each on 3 axes 6 directions Ambient temperature Operating 10 C to 55 C with no condensation or icing Storage 25 C to 65 C with no condensation or icing Ambient humidity Operating 25 to 85 with no condensation Approved safety standards UL3121 1 conforms to EN61010 1 Pollution degree 2 overvoltage...

Page 3: ...rity display is displayed automatically with a negative input signal Zero display Leading zeros are not displayed Input shift Input shift equivalent to the setting value supported for all points within the sensor measurement range Hold function Max hold maximum value Min hold minimum value Hysteresis setting Programmable with front panel key inputs 0001 to 9999 Other functions Display color change...

Page 4: ...re of 20 C 100 000 times min at a rated load switching frequency of 10 time min Power supply Output terminals Input terminals 100 to 240 VAC type or 24 VAC VDC type No polarity for 24 VDC connection Models with comparative output For thermocouple input For platinum resistance thermometer input OUT1 A B B A1 A2 E1 E2 E3 E4 E5 E6 E4 E5 E6 Recommended DC power supply eg OMRON S8VS Terminal No Name De...

Page 5: ...300 to 1500 F 1 199 9 to 500 0 C 1999 to 900 0 F 2 0 0 to 100 0 C 0 0 to 210 0 F 3 JPt100 199 9 to 500 0 C 199 9 to 900 0 F 4 0 0 to 100 0 C 0 0 to 210 0 F 5 Thermocouple K 200 to 1300 C 300 to 2300 F 6 20 0 to 500 0 C 0 0 to 900 0 F 7 J 100 to 850 C 100 to 1500 F 8 20 0 to 400 0 C 0 0 to 750 0 F 9 T 200 to 400 C 300 to 700 F 10 199 9 to 400 0 C 199 9 to 700 0 F 11 E 0 to 600 C 0 to 1100 F 12 L 10...

Page 6: ...o either red or green For comparative output models the display color can be set to change from green to red or from red to green according to the status of the comparison criterion Display Auto return Time This function automatically returns the display to the operation level s current value if no keys are pressed for a preset time called the dis play auto return time Move to Protect Level Time T...

Page 7: ...X and MIN values when a measurement value is being displayed 5 Level Key Used to change the level 6 Mode Key Used to allow the main indicator to indicate parameters sequentially 7 Shift Key Used to enable a set value to be changed When changing a set value this key is used to move along the digits 8 Up Key Used to change a set value Used to set or clear a forced zero function when a measurement va...

Page 8: ...oring the temperature of an industrial furnace Monitoring the bearing temperature for a generator motor E5EN K3MA L Alarm output Molding equipment K3MA L K3MA L Industrial furnace PID control Generator motor Alarm output Monitoring the temperature of an indus trial furnace sintering furnace Monitoring alarm function for disinfect ing equipment Monitoring failsafe checking abnormal temperatures in ...

Page 9: ...cts the panel to secure the K3MA L Wiring Precautions Use crimp terminals Tighten the terminal screws to a torque of approximately 0 5 N m To avoid the influence of noise route signal lines and power lines separately Wiring Use the following M3 crimp terminals Unit Labels Provided The unit labels are not attached to the K3MA L Select the desired labels from the provided sheet Note For scales and g...

Page 10: ...roduct during use or storage Doing so may deform or deteriorate the product 7 Do not use paint thinner for cleaning Use commercially available alcohol Mounting Mount the product to a panel that is 1 to 8 mm thick Install the product in a horizontal position Use crimp terminals that match screw sizes Noise Prevention Install the product as far as possible from devices that generate strong high freq...

Page 11: ...inue Operation Displaying current values and setting OUT 1 value Continue Adjustment Setting communications writing control Continue Initial setting Making initial settings of input type output operating action and other parameters Stopped Advanced function setting Setting average processing display color settings and other ad vanced function parameters Stopped 123 4 Power ON Operation level Prote...

Page 12: ...eters are not displayed for certain models 2 The K3MA L will stop measurement if the level is changed to the initial setting level or the advanced function setting level 3 If the input range is changed some parameters are set to default values Therefore set the input range first 4 Settings displayed in reversed colors are defaults Power ON Operation level Adjustment level Press Level Key for less ...

Page 13: ...alization Average processing OUT1 type Temperature unit Temperature unit OUT1 type Upper Limit Lower Limit Upper Lower Limits Models with the compara tive out put function MODE MODE MODE MODE Models with the compar ative out put function Display color change Display auto return time Move to protect level time Green red Green Red green Red Unit s Unit s OUT1 Hysteresis Unit times MODE MODE MODE MOD...

Page 14: ... than preset time Paramet er Setting Operation level Moving to adjustment level Process value display Set value display oapt 0 Allowed Allowed Allowed 1 Allowed Allowed Prohibited 2 Allowed Prohibited Prohibited Parameter Setting Shift to initial setting level Shift to advanced function setting level icpt 0 Allowed Allowed 1 Allowed Prohibited 2 Prohibited Prohibited Parameter Setting Setting chan...

Page 15: ...ain indicator Error contents Countermeasures Not lit e111 RAM memory error Repair is necessary Consult your OMRON sales repre sentative 5 e111 EEPROM memory error When this error is displayed press the Level Key for 3 seconds and the settings will be restored to the factory settings If the error cannot be recovered re pair is necessary Consult your OMRON sales repre sentative Not lit Flashes s err...

Page 16: ...pplication or use of the products At the customer s request OMRON will provide applicable third party certification documents identifying ratings and limitations of use that apply to the products This information by itself is not sufficient for a complete determination of the suitability of the products in combination with the end product machine system or other application or use The following ar...

Reviews: