97
Inverter Settings
Chapter 7-2
7-2-4
Setting the Multi-function Inputs (n36 to n39)
• In addition to the methods described above, the RUN command and
frequency reference can be input through RS-422A/485 communications
by setting the value 18 in any one of the parameters from n36 to n39
(multi-function input).
• Subsequently, the following operations are selectable in remote mode.
None of these parameters, however, can be changed while the operation
command is being input.
When the function-set input terminal is OFF, the RUN command will be
executed according to the setting in n02 (operation command selection)
and the frequency reference will be executed according to the setting in
n03 (frequency reference selection).
When the function-set input terminal is ON, the Inverter will operate
according to the RUN command and frequency reference through RS-
422A/485 communications.
n36
Multi-function input 1 (S2)
Register
0124 Hex
Changes during
operation
No
Setting
range
2 to 8, 10 to 22
Unit of
setting
1
Default setting
2
n37
Multi-function input 2 (S3)
Register
0125 Hex
Changes during
operation
No
Setting
range
0, 2 to 8, 10 to 22
Unit of
setting
1
Default setting
5
n38
Multi-function input 3 (S4)
Register
0126 Hex
Changes during
operation
No
Setting
range
2 to 8, 10 to 22
Unit of
setting
1
Default setting
3
n39
Multi-function input 4 (S5)
Register
0127 Hex
Changes during
operation
No
Setting
range
2 to 8, 10 to 22, 34, 35
Unit of
setting
1
Default setting
6
Summary of Contents for J7 series
Page 12: ...XII...
Page 15: ...1 CHAPTER 1 Overview 1 1 Function 2 1 2 Nomenclature 3...
Page 54: ...40 Outline of Operation Chapter 3 2...
Page 102: ...88 Other Functions Chapter 6 7...
Page 158: ...144 Option Specifications Chapter 9 3...
Page 159: ...145 CHAPTER 10 List of Parameters List of Parameters 146...
Page 172: ...158 List of Parameters Chapter 10...
Page 173: ...159 CHAPTER 11 Using the Inverter for a Motor Using the Inverter for a Motor 160...