background image

1

Weekly Time Switch

H5S

Weekly Time Switch for Various Time
Controls

A different program possible each day.

Easy-to-program using the interactive menu
system.

Multiple-day operation, cyclic and pulse-output
operation possible.

ON/OFF operations can be set in 24 steps.

Timing chart display for operation monitoring.

Two circuits can be controlled independently.

Supply voltage from 100 to 240 VAC.

Surface, flush, or track mounting possible.

RC

Ordering Information

Wiring

Mounting style

Model

Screw terminals

Flush mounting

H5S-B

Surface mounting/track mounting

H5S-FB

Specifications

 Time Ranges

Rated time

Time setting range

Time division

1 week

00:00 a.m. to 11:59 p.m.

1 min

 Ratings

Rated supply voltage

100 to 240 VAC (50/60 Hz), 24 VDC

Operating voltage range

85% to 110% of rated supply voltage (85 to 264 VAC (50/60 Hz))

Power consumption

AC: Approx. 3 VA
DC: Approx. 0.8 W

Control outputs

SPST-NO x 2 circuits: 15 A at 250 VAC, resistive load

Summary of Contents for H5S-B

Page 1: ...y voltage from 100 to 240 VAC Surface flush or track mounting possible RC Ordering Information Wiring Mounting style Model Screw terminals Flush mounting H5S B Surface mounting track mounting H5S FB Specifications Time Ranges Rated time Time setting range Time division 1 week 00 00 a m to 11 59 p m 1 min Ratings Rated supply voltage 100 to 240 VAC 50 60 Hz 24 VDC Operating voltage range 85 to 110 ...

Page 2: ...d Approved standards UL File No E52800 CSA File No LR22310 10 A at 250 VAC general use 15 A at 125 VAC resistive load Weight Approx 200 g Note The total error including the repeat accuracy setting error variation due to voltage change and variation due to temperature change is 0 01 0 05 s max 0 01 indicates an error in the time interval of a set time Operation Operation method Digital quartz Opera...

Page 3: ...ey Operations No Function 1 Shifts the cursor B specifying a day to the right 2 Sets or cancels a specified day 3 4 Sets a time or ON OFF time width 5 Monitors the parameters set for an operation during an operation 6 Sets parameters 7 Sets a time adjustment mode 8 Specifies a cyclic operation or sets a pulse width 9 Specifies a day substitution operation 10 Cancels the parameters set for each cir...

Page 4: ...tion is automatically started on power recovery MANUAL Operation is started by applying an external signal after power recovery Day override operation Executes a day s operation on another day The specified new operation is performed only for one week Programming Before setting the parameters necessary for each operation the operation of circuits outputs 1 and 2 must be determined Also whether the...

Page 5: ...Shaded portion indicates blinking of the indicator 1 Move the cursor B with the Shift Key Press the Set Key so that of a desired day turns on Select Monday through Friday Display and key operation Shaded portion indicates blinking of the indicator 4 Set the time to 5 45 p m with the h and m Keys Press the Write Key 2 Set the time to 9 00 a m with the h and m Keys 5 The set times are dis played for...

Page 6: ... the Write Key 6 Press the Write Key The display returns to the initial screen 1 s lat er The Mode Switch to RUN Initial screen Multiple day Operation Set the Mode Switch to P1 or P2 Example ON at 9 00 p m Monday and OFF at 3 15 a m Tuesday Display and key operation Shaded portion indicates blinking of the indicator 1 Specify Monday with the Shift and Set Keys Display and key operation Shaded port...

Page 7: ...Wednesday Display and key operation Shaded portion indicates blinking of the indicator 1 Press the Check Key To check the operation of a day other than today Example To check Monday s opera tion on Wednes day Display and key operation Shaded portion indicates blinking of the indicator 1 Move the cursor to the Monday position using the Shift and Set Keys 2 The first item of today s operation set fo...

Page 8: ...Setting To cancel the setting of each circuit Display and key operation Shaded portion indicates blinking of the indicator 1 Set the Mode Switch to the position of the circuit whose setting is to be canceled 2 Press the CLR Key To cancel the operating day shift program Display and key operation Shaded portion indicates blinking of the indicator 1 Set the Mode Key to RUN Depress the Copy Key for at...

Page 9: ...1 to 5 mm When mounting the time switch on a soft iron panel using the M4 tapping screws the diameter of the mounting holes drilled into the panel vary according to the panel thickness as follows If the panel is die cast aluminum the hole diameter should be slightly larger Panel thickness 0 8 1 0 1 2 1 6 2 0 2 6 3 2 4 0 Hole diameter 3 6 3 7 Accessories Order Separately Y92A 72C Protective Cover Y...

Page 10: ...IN EN 50022 This dimension applies to the PFP 50N Mounting Track Installation Terminal Arrangement H5S B Flush Mounting Models Rear View H5S FB Surface Mounting Models Front View Note The terminal screws are M3 5 Connections H5S B Flush Mounting Models H5S FB Surface Mounting Models Power source Power source ...

Page 11: ... operation indica tor lights The set data may be erased if the OUT switch is moved between the TIMER and PULSE positions after the data has been set Backup Power Supply for Memory Protection during Power Failure The H5S Time Switch has a built in battery This backup power sup ply allows continuous operation of the internal timer circuit and re stores the user program during a power failure If the ...

Page 12: ... 03527 Cat No L014 E1 4E In the interest of product improvement specifications are subject to change without notice Printed in Japan 0700 0 1M 0696 OMRON Corporation Industrial Automation Company Measuring and Supervisory Controls Department 28th Fl Crystal Tower Bldg 1 2 27 Shiromi Chuo ku Osaka 540 6028 Japan Tel 81 6 6949 6035 Fax 81 6 6949 6069 ...

Reviews: