LED indicator

Wiring

Recommended driver:

 Type XW4Z-00B manufactured by Omron

 Type SZF0-0.4mmx2.5mm 

               manufactured by Phoenix contact

8

   - Insulated ferrule: AWG24 to AWG16 (0.25 to 1.5 mm

2

)

   - Crimp height(H): 2.0 mm max          Width(W): 2.7 mm max.          Conductor length: 8 to 10 mm

  When using the twin type ferrule, use equal-sized wires and preferred insulated ferrule.

  The twin type ferrule should not be above the adjoining release hole.

How to insert solid wire and insulated ferrule

The wire should be pushed into the terminal block straight. No need to use the driver.

After inserting, make sure wire is fastened on to terminal block.

How to release wire

Use the following minus drive to release wire from terminal block.  

And When releasing wire, the power source should be disconnected first.

1. Push the driver lightly into the taper of release hole.

2. Pull out the wire while the driver is pushed into release hole.

3. Pull out the driver.

Terminal block may be damaged.

1. Not push the driver into the release hole straight.

2. Not push the driver into the release hole by force of 30N and over.

3. Not tip or twist the driver pushed into release hole. 

Precautions for Correct wiring

Fault Detection

When G9SE detects a fault, LED indicators blink to show the information of the fault.

When PWR indicator blinks, check and take needed measures referring to the following table. And then 

apply supply voltage to G9SE.

7

PWR

1) Failures involving the wiring of

Safety input 1

1) Failures involving the wiring of

Safety input 2

1) Supply voltage outside the 

rated value.

Expected causes of 

the faults

Checking points and

measures to take

1) Check the wiring to T11 and T12.

When using stranded wire, insulated ferrule should be used. Use below insulated ferrule.

But do not use ferrule terminals if G9SE is used as UL Listing. Insert the strand or solid wire directly into the

holes on the terminal block.

Recommended insulated ferrule: manufactured by Phoenix contact

Type

Single AI 0,34-8TQ

AI 0,5-10WH
AI 0,75-10WH
AI 1-10RD
AI 1.5-10BK

Twin

AI TWIN2x0.75-10WH

Wire size

Cross section(mm

2

) AWG

0,34

0,5

0,75

1,0
1,5

2 x 0.75

22
20
18
18
16

Type G9SE-221-T

Guard lock safety door switch (Mechanical Lock)

 2-channel Safety limit switch inputs

 / Manual reset

A1

A2

T11 T12

T32 T33

13 23

14 24

T21 T22

T31

X1

24V

PLC etc.

M

KM2

KM1

S1 

S3

M

:Safety limit switch

:Contactor
:3-phase motor

Device

Guard lock safety 

door switch S2

Operation command

KM1,KM2  N.C. contact

KM1,KM2  N.O. contact

Reset switch S3

Timing chart

37 47

38 48

KM1 KM2

KM2

KM1

S2

KM1,KM2

:Guard lock safety

 door switch

 (Mechanical Lock)
:Reset switch

S3

Safety limit switch S1

14

Motor controller

Motor controller

(Operation command)

OFF-delay time

Rotation of motor

Blink

2) Failures of the parts of the circuits 

of Safety input 1.

2) Failures of the parts of the circuits

of Safety input 2.

2) Replace with a new product.

H

W

Release hole

Wire

Front

φ2.5mm

2.5mm

Side

0.4mm

8

12°

Driver

Performance level and safety category 

(EN ISO13849-1)

Type  G9SE can construct the condition conforming to PL=e and category 4 requested by EN ISO13849-1 

European standard. This category class is recognized and based on the circuits we made, so we would like you 

to conform the category class with G9SE at your application once. Category is judged by the condition of the 

whole control system.

 In order to category 4

EN ISO13849-1

  1) Input the signals to both of the Safety inputs (T11-T12 and T21-T22)

  2) Input a signal to the Safety inputs (T11-T12 and T21-T22) through switches with Direct Opening 

      Mechanism. When using limit switches, at least one of them must have Direct Opening Mechanism.

  And wiring must be done in a way that a short circuit between the wires of safety input can be     

  excluded.

  3) When connecting Safety sensor with G9SE, use TYPE 4 safety sensor.

  4) Input the signal through a NC contact of the contactor to Feedback/Reset input (T31-T32 for manual   

      reset or T31-T33 for auto reset).(Refer to '5.Examples of Application')

  5) Be sure to connect 

the negative terminal  of DC power supply

 to ground.

  6) Use two safety outputs (e.g. 13-14 and 23-24) for the system construction.

6

To set Safety outputs in ON state, HIGH 

state signals must be input to both of 

Safety input 1 and Safety input 2.

Otherwise Safety outputs cannot be 

inON state.

To set Safety outputs in ON state, ON 

state signal must be input to T33.

Otherwise Safety outputs cannot be in 

ON state.

To set Safety outputs in ON state, the 

signal input to T32 must change from 

OFF state to ON state, and then to OFF 

state. Otherwise Safety outputs cannot 

be in ON state.

Turns ON/OFF according to the state of 

safety inputs, Feedback/Reset inputs.

During off-delay state, safety outputs 

are not able to turn ON.

Off-delayed safety outputs.

(See Note1)

Off-delay time is set by off-delay preset 

switch.

When the delay time is set to zero, 

these outputs can be used  as 

non-delay outputs.

Outputs a signal of the same logic as 

Safety outputs

Wiring  of inputs and outputs

Signal

Name

Safety

input 1

Power

supply

input

Terminal 

Name

T11,
T12

A1,

A2

Safety

input 2

T21,
T22

Reset/

Feedback

input

T31,
T32,
T33

Wiring

Description of operation

1-channel
Safety input

2-channel
Safety input

Auto reset

Manual

reset

Safety 

output

13-14,

Off-

delayed 

Safety 

output

Auxiliary 

output

X1

Keep these outputs Open when NOT used.

Keep these outputs Open when NOT used.

Keep these outputs Open when NOT used.

The input terminals for power supply.

Connect the power source to the A1 and A2

 terminals.

Connect the power supply plus to the A1 

terminal.

Connect the power supply minus to the 

A2 terminal.

Feedback loop

Feedback loop

T11 T12 T21 T22

+24V

T11 T12 T21 T22

T11 T12 T21 T22

KM

+24V

T31

T33

T32

KM +24V

T31

T33

T32

Reset

Switch

23-24,
33-34,
43-44,

37-38,
47-48

Connecting Safety Sensors and G9SE

640 

µ

s Max.

In many case, Safety Sensor outputs include the off-shot pulse for its self test.

The following condition of test pulse is applicable as safety inputs for G9SE.

  

- Off-shot pulse width of the sensor, during the ON-state : 640 μs 

(1) When the inputs of G9SE-221-T

 are restored during off-delay time, G9SE-221-T

 will operate

      as below. Depending on the reset mode.

        - Auto reset mode: Outputs turn off after off-delay time, then immediately turens on.

        - Manual reset mode: Outputs turn off after off-delay time, then turn on when reset input is given.

IN1

IN2

OUT

OUT1

OUT2

Blink

Blink

Blink

Blink

The all indicators Blink

Blink

Safety inputs: ON-state

Light Light

Safety inputs: OFF-state

Light Light

Blink

LED indicator

PWR

IN1

IN2

OUT

OUT1

OUT2

Use the following to wire to G9SE.

   - Solid wire: AWG24 to AWG16 (0.25 to 1.5 mm

2

)

   - Stranded wire: AWG24 to AWG16 (0.25 to 1.5 mm

2

)

   Strip the cover of wire no longer than 8 to 10 mm

Blink

Blink

L

Safety sensor

OSSD1

OSSD2

S2

OPEN

S4

S1

KM2

KM1

Guard

Stop signal

Lock

release

signal

S4

:Lock release switch

Lock release signal

Lock release switch S4

Stop signal

Guard closed 

 opened

Guard can be opened.

●Terminal arrangement and LED indicators

T33

T32

T31

X1

24

14

T21

23

T22

13

T12

T11

A1

A2

Type 

G9SE-401

Type 

G9SE-221-T

Type 

G9SE-201

PWR
IN1
IN2
OUT

PWR
IN1
IN2
OUT

PWR
IN1
IN2
OUT

1

OUT2

T33

T32

T31

X1

44

34

T21

43

T22

33

T12

T11

A1

A2

24

14

23

13

T33

T32

T31

X1

48

38

T21

47

T22

37

T12

T11

A1

A2

24

14

23

13

5

Examples of application

Type G9SE-201

2-channel emergency stop switch input / Manual reset

A1

A2

T11 T12

T32 T33

13 23

Safety

Output

(Instant

aneous)

14 24

T21 T22

Reset/

Feedback

Input

Safety

Input1

Power

supply

circuit

Safety

Input2

T31

X1

Auxiliary

output 

KM1 KM2

24V

PLC 

etc.

S1

KM2

KM1

Feedback loop

S2

M

KM2

KM1

S1 

KM1,KM2
M

:Emergency stop switch

S2

:Reset switch
:Contactor
:3-phase motor

Device

Note1 : This example is corresponding to category 4

Emergency stop switch S1

KM1,KM2  NC contact

KM1,KM2  NO contact

Reset switch S2

Timing chart

Type G9SE-401

2-channel safety sensor / Auto reset

A1

A2

T11 T12

T32 T33

13 23

Safety

Output

(Instant

aneous)

14 24

T21 T22

Reset/

Feedback

Input

Safety

Input1

Power

supply

circuit

Safety

Input2

T31

X1

Auxiliary

output 

KM1 KM2

24V

PLC 

etc.

KM4

KM3

Feedback loop

M1

KM2

KM1

KM1

KM

4

M1,M2

Safety sensor

:Contactor
:3-phase motor

Device

Note1 : This example is corresponding to category 4

Safety sesor outputs

KM1

KM4  NC contact

KM1

KM4  NO contact

Timing chart

33 43

34 44

KM

3

KM

4

M2

KM4

KM3

KM2

KM1

NC

NC

Safety

sensor

Receiver

Emitter

OSSD

1

OSSD

2

Reset/

Feedback

Input

Safety

Input1

Power

supply

circuit

Safety

Input2

Auxiliary

output 

Safety

Output

(Instant

aneous)

Safety

Output

(OFF-

delay)

Feedback loop

Note1 : This example is corresponding to category 4

The all indicators Light off

up

up

off

off

1) Check the wiring to T21 and T22.
2) Replace with a new product.

2) Failures of the parts of the circuits

of Feedback/Reset input.

1) Failures involving the wiring of 

Feedback/Reset input.

1) Check the wiring to T31, T32, and T33

2) Replace with a new product.

1) Replace with a new product.

1) Failures of the parts or relays of the

circuits of instantaneous Safety 

Output.
1) Mismatch of the two Off-delay

 Time Preset Switches.

2) Failures of the parts or relays of the

circuits of OFF-delay Safety Output.

1) Check both of the two Off-delay Time

Preset Switches.

2) Replace with a new product.

1) Check the supply voltage to G9SE.

1) By excessive electro-magnetic 

disturbance.

2) Failures of the parts of internal 

circuits

2) Replace with a new product.

1) Check the disturbance level around 

G9SE and its related system.

When indicators other than PWR indicator blink while PWR indicator lights up, check and take needed 

measures referring to the following table. After removing the fault, turn both safety inputs to OFF state.

Light

up

Safety inputs: ON-state

Light

off

Light

off

Expected causes of 

the faults

Checking points and

measures to take

1) Mismatch between Safety input 1 

and Safety input 2.

(OFF timing)

1) Check the wiring from safety input devices

to G9SE. Or check the inputs sequence of 

safety input devices.