What can be done by the setting tool
E
Override Function
Overview
Configures override function.
The override function disables safety functions of the device. You must ensure safety
using other measures during this function is enabled.
All external indicators that indicate state of override function must be installed where
workers can see them from all the operating positions.
Install the switch that activates the override and that uses hold-to-run device, such as
spring-return key switch, in a location that provides a clear view of the entire hazardous
zone and where it cannot be activated from within the hazardous zone. Make sure that
nobody is in the hazardous zone before activating the override function.
Override time must be properly configured for its application by a sufficiently trained and
qualified person.
Example
•To extend override continuance time
Functional Description
• Override Function
The setting tool can disable override function. (Enabled for factory shipment)
• Override Time Limit
Override continuance time at the function’s activation can be changed. (60s for factory shipment)
Setting Change
Configure in a bulk in case of a series connection. (to be written into the primary sensor only)
If override function is enabled, we recommend either output mode of external indicator output 1, 2, or auxiliary output
1 should be configured as shown below.
- Override information
- Muting/override information
Setting Zone Adjacent Conditions
If any two functions of muting, fixed blanking, floating blanking, or warning zone functions are used at
the same time, the setting zones have limitations.
This section describes the limitations for following points:
1. Zone adjacent condition: If zones for multiple functions are configured adjacently
2. Zone overlap condition: If zones for multiple functions are configured as overlapped
Function
Initial Setting
Available Setup Item
Setting Console
PC Tool For F3SJ
Override Function
Enabled
Enable/disable
–
Override Time Limit
60s
1s to 600s (by 1s)
Summary of Contents for F3SJ Series
Page 1: ...F3SJ A N Series Version 2 Safety Light Curtain User s Manual Cat No SCHG 719K...
Page 19: ...xvii F3SJ A User s Manual Introduction Contents E Revision History 202...
Page 20: ...xviii Introduction Contents F3SJ A User s Manual...
Page 184: ...164 Chapter 4 Wiring F3SJ A User s Manual Wiring Installation...
Page 192: ...172 Chapter 5 Wiring Examples F3SJ A User s Manual Input Output Circuit and Applications...