Omron F03-15 Brochure & Specs Download Page 7

 

Liquid Leakage Sensor Amplifier with Disconnection Detection Function

 K7L-AT50D/-AT50D-S

7

Liquid Leakage Sensor Amplifier with 
Disconnection Detection Function
K7L-AT50D/-AT50D-S

Detect Disconnections between the Sensor 
Amplifier and a Terminator Connected to the End 
of the Sensing Band.

• Constantly monitors for disconnections between the Sensor Ampli-

fier and the Sensing Band.

• Failure to detect liquid leakage due to disconnection in the Sensing 

Band prevented.

• Notification of disconnection detection made using LED indicator 

and transistor output. 

• After a disconnection is detected, the operating status is held to 

avoid instability due to further contact of the disconnected part.

• This model retains all the characteristics of the K7L-AT50 (detection 

sensitivity, sensing ranges, and AC detection method).

• Meets UL/CSA standards. (See information on standards on 

page 7.)

Ordering Information

Note:

The Sockets, Terminal Blocks, Stickers, and Sensing Bands are the same as for the K7L-AT50.

Specifications

Ratings

Note:

UL

File No. E138234

CSA

File No. LR95291-21

Characteristics

The characteristics are the same as for the K7L-AT50. Refer to page 4 for details.

Nomenclature

The nomenclature and DIP switch settings are the same as for the K7L-AT50. Refer to page 5 for details.

Name

Model number

Liquid Leakage Sensor Amplifier with Disconnection Detection Function Set

K7L-AT50D

Liquid Leakage Sensor Amplifier with Disconnection Detection Function Sensor Amplifier Only

K7L-AT50D-S

Terminator (2P)

F03-20T

Rated power supply 
voltage

12 to 24 VDC (Allowable voltage fluctuation range: 10 to 30 VDC)

Operate resistance

 to 50 M

, variable

Range 0:

0 to 250 k

Range 1:

0 to 600 k

Range 2:

0 to 5 M

Range 3:

0 to 50 M

Note:

The range is set using the DIP switch on the side of the Sensor Amplifier. (Refer to 

DIP Switch Settings

.) Set the corresponding pin

of the DIP switch in the up position. (For range 0, set all 3 pins in the down position.) The adjuster (ADJUST) on the top of the Sensor
Amplifier sets the resistance value for detection within the set range. It is factory-set to the upper limit. (Normally, use with the adjuster
set to the upper limit.) With any range, resistance values can be set from 0 

.

Disconnection 
detection function

Detection signal: 10 VDC max., 200 ms
Detection time: 10 s max.
Release: Released by resetting the power supply.

Release resistance

105% min. of operate resistance

Output configuration

NPN open-collector transistor output with 100 mA at 30 VDC max. for both liquid leakage detection and disconnection detection.

Note:

If the rightmost pin of the DIP switch on the side of the Sensor Amplifier is set to the down position, the output turns ON when liquid/
disconnection is detected; if it is set to the up position, the output turns OFF when liquid/disconnection is detected.

Wiring distance

Connecting cable: 50 m max.
Sensing Band length: 10 m max.

Note:

These values are possible on condition that a completely insulated 3-conductor VCT cable with a thickness of 0.75 mm

2

 and a dielec-

tric strength of 600 V is used together with a Liquid Sensing Band specified by OMRON. (A 0.2-mm

2

 cable can also be used.)

Accessories

F03-20 Terminal Block (for connecting the connecting cable and Sensing Band)
Screwdriver for ADJUST setting.
F03-20T Terminator (provided with K7L-AT50D only)
(Purchase the Sensing Band, Sensing Band Stickers, connecting cable, and Socket separately. The Terminal Block is 3P; the Terminator is 
2P.)

Summary of Contents for F03-15

Page 1: ...sitivity detects impedances of up to 50 M Polyethylene makes the Sensing Band more resistant to chemicals Series includes models with disconnection detection The color of the Sensing Band shown here i...

Page 2: ...istance SUS316 and polyethylene are used for the Sensing Band s core and sheath to ensure high resistance to both acidic and alkaline liq uids Application Examples Liquid Leakage Detection for Measuri...

Page 3: ...Stickers or Mounting Brackets Available Sensing Band Lengths Note 1 To place an order for 1 m of the F03 16PE for example specify F03 16PE 1M 2 If you cannot find the length you need please order the...

Page 4: ...sistor output with 100 mA at 30 VDC max Note If the rightmost pin of the DIP switch on the side of the Sensor Amplifier is set to the down position the output turns ON when liquid is detected if it is...

Page 5: ...nd connects to the Sensing Band through a cable that can be extended up to 50 meters Countermeasures against external noise are especially important for the Sensing Band and connecting cable because t...

Page 6: ...nection Examples NPN Output PNP Output K7L AT50 Signal transmission Level input 1 Level input 2 12 to 24 VDC Connecting cable 0 2 mm2 min F03 20 Terminal Block Sensing Band OUT Open collector output O...

Page 7: ...ance 0 to 50 M variable Range 0 0 to 250 k Range 1 0 to 600 k Range 2 0 to 5 M Range 3 0 to 50 M Note The range is set using the DIP switch on the side of the Sensor Amplifier Refer to DIP Switch Sett...

Page 8: ...mal i e there is no disconnec tion Operation at Disconnection Detection If there is a disconnection the signals will be interrupted at the place where the disconnection occurred and will not return to...

Page 9: ...te The shape of the adhesive tape shown above is for securing the F03 16PE Name Model number Remarks Liquid Leakage Sensing Band F03 16PE Sensing Band Stickers F03 26PES F03 26PEN 30 Stickers per set...

Page 10: ...The shape of the adhesive tape shown above is for securing the F03 16PE Name Model number Remarks Fluoroplastic Sensing Band F03 16PT Fluoroplastic Sensing Band Stickers F03 26PTN 10 Stickers per set...

Page 11: ...me Model number Remarks Liquid Leakage Sensing Band F03 15 Sensing Band Stickers F03 25 30 Stickers per bag Sheath Flexible transparent vinyl chloride Core SUS304 stainless steel Ambient operating tem...

Page 12: ...ductor VCT cable with a thickness of 0 75mm2 and a dielectric strength of 600 V is used Name Model number Remarks Sensing Band F03 16SF Without color indication F03 16SFC With color indication Sticker...

Page 13: ...lectric strength of 600 V is used Dimensions Unit mm Sensing Band 0 m 10 m 50 m 100 m 150 m 200 m Wiring Cable Note 0 m 10 m 50 m 100 m 150 m F03 16SF F03 16SFC Appearance Structure F03 25 Appearance...

Page 14: ...h down the top of the termi nal with a screwdriver and insert the core from the side Refer to Dimensions on page 9 More Sensing Bands can be connected simply by wiring in an arch shape Note Check that...

Page 15: ...intervals on the floor and around equipment Cover the Sensing Band with plastic or metal molding to protect it from contact with other objects and from being stepped on by workers Leave a 50 to 100 m...

Page 16: ...cation Can a different terminal block e g a commercially available terminal block or a terminal block constructed by the user be used instead of the one provided Yes When using another terminal block...

Page 17: ...m Leakage areas cannot be specified with the K7L AT50 Mounting Methods Product name Main material Cable material Electrode material Model Liquid Leakage Point Sensor Polyethylene Outer sheath PVC Inne...

Page 18: ...28 8 46 K7L AT50D LIQUID LEAKAGE SENSOR K7L AT50D PW OUT ADJUST 2 3 4 2 3 29 1 23 1 3 3 4 3 2 3 2 25 2 3 4 5 3 15 2 5 3 5 17 5 5 8 17 5 8 3 2 3 2 25 18 0 2 Two M3 Mounting Hole Dimensions 2 4 4 2 24 1...

Page 19: ...ci fied range or where condensation is likely to occur To detect liq uids with high impedances do not use in locations with high humidity Locations subject to dust Locations subject to corrosive gases...

Page 20: ...bserve all prohibitions of use applicable to this product NEVER USE THE PRODUCTS FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY WITHOUT ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN DESI...