![Omron E5ED-82 Series Instruction Manual Download Page 2](http://html1.mh-extra.com/html/omron/e5ed-82-series/e5ed-82-series_instruction-manual_742641002.webp)
• Up and Down keys
Each press of
U
key increments or advances
the values displayed on the No.2 display.
Each press of
D
key decrements or returns the
values displayed on the No.2 display.
Operation indicators
• SUB1: Auxiliary output 1 indicator
• SUB2: Auxiliary output 2 indicator
• OUT1: Control output 1 indicator
• OUT2: Control output 2 indicator
• No.1 display
Process value or set data type
• No.2 display
Set point, set data read-out value or changed
input value
• Mode key
Press this key to change the contents of the display.
Press this button for 1 s or longer for reverse scroll.
• Press the
O
key and the
M
key
together for at least 3 seconds to switch to protect level.
• No. 3 display
(Nothing is displayed at the default settings.)
MV, Soak Time Remain, and Multi-SP.
• °C / °F : temperature unit
The temperature unit is displayed when
the displayed value is a temperature.
Either
C
or
F
is displayed according to the
set value of the temperature unit.
• Shift key (PF key)
The default PF Setting parameter is for
shifting the digit. This is a function key.
When it is pressed, the function set for the
PF Setting parameter will operate.
• Level key
Use this key to change levels:
• STOP: Control stop indicator
Lit when “Run/Stop” is stopped during operation.
• TUNE:
Lit during auto-tuning.
• : Protection indicator
Lit when Setting Change Protect is ON (disables the
Up and Down Keys).
• MANU: Manual output indicator
Lit when the Auto/Manual Mode is set to Manual
Mode.
During control stop, functions other than control output
are valid.
• CMW: Communications writing enable/ disable indicator
Lit when communications writing is “enabled” and is
out when it is “disabled”.
Precautions for Safe Use
CAUTION
Safety Precautions
Key to Warning Symbols
Wiring
Specifications
Dimensions
Installation
Side-by-side mounting (mm)
• Insert the main unit through the mounting hole in the panel
(1 to 8 mm thickness). Insert the mounting brackets (supplied)
into the fixing slots located on the top and bottom of the rear
case.
• Tighten the two mounting screws on the top and bottom of
the adapter to keep them balanced, and finally tighten them
to a torque of between 0.29 and 0.39 N·m.
• When more than one machine is installed, make sure that the
ambient temperature does not exceed the specified limit.
Waterproofing is
impossible with
side-by-side installation.
When waterproofing is
required, fit watertight
packing on the
backside of front panel.
ni
m
0
2
1
45
2
9
+ 0.6
0
8.
0
+
0
(48 x number of units–2.5) + 1.0
0
29
8.
0
+
0
Names of Parts on Front Panel
Operation Menu
Input Type
3102754-8B (Side-B)
CAUTION
Minor injury due to electric shock may occasionally occur.
Do not touch the terminals while power is being supplied.
Electric shock, fire, or malfunction may occasionally occur. Do not allow metal objects, conductors, debris
(such as cuttings) from installation work, moisture, or other foreign matter to enter the Digital Controller.
Do not use the product where subject to flammable or explosive gas. Otherwise, minor injury
from explosion may occasionally occur.
Never disassemble, modify, or repair the product or touch any of the internal parts. Minor
electric shock, fire, or malfunction may occasionally occur.
CAUTION - Risk of Fire and Electric Shock
a) This is the product UL Listed as Open Type Process Control Equipment. It must be mounted in an enclosure
that does not allow fire to escape externally.
b) More than one disconnect switch may be required to de-energize the equipment before servicing.
c) Signal inputs are SELV, limited energy.
d) Caution: To reduce the risk of fire or electric shock, do not interconnect the outputs of different Class 2 circuits.
If the output relays are used past their life expectancy, contact fusing or burning may occasionally
occur. Always consider the application conditions and use the output relays within their rated load
and electrical life expectancy. The life expectancy of output relays varies considerably with the
output load and switching conditions.
Warning Symbols
Suitability for Use
Omron Companies shall not be responsible for conformity with any standards, codes or regulations which
apply to the combination of the Product in the Buyer’s application or use of the Product.
At Buyer’s request, Omron will provide applicable third party certification documents identifying ratings and
limitations of use which apply to the Product. This information by itself is not sufficient for a complete
determination of the suitability of the Product in combination with the end product, machine, system, or other
application or use. Buyer shall be solely responsible for determining appropriateness of the particular Product
with respect to Buyer’s application, product or system. Buyer shall take application responsibility in all cases.
NEVER USE THE PRODUCT FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR
PROPERTY WITHOUT ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO
ADDRESS THE RISKS, AND THAT THE OMRON PRODUCT(S) IS PROPERLY RATED AND INSTALLED
FOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT OR SYSTEM.
E5ED-82
Digital Controller
INSTRUCTION MANUAL
Thank you for purchasing the OMRON E5ED Digital Controller.
This manual describes the functions, performance, and
application methods needed for optimum use of the product.
Please observe the following items when using the product.
• This product is designed for use by qualified personnel with
a knowledge of electrical systems.
• Before using the product, thoroughly read and understand
this manual to ensure correct use.
• Keep this manual in a safe location so that it is available for
reference whenever required.
OMRON Corporation
©All Rights Reserved
EN
Be sure to observe the following precautions to prevent operation failure, malfunction, or adverse affects on theperformance
and functions of the product. Not doing so may occasionally result in unexpected events. Use theproduct within specifications.
(
1
)
The product is designed for indoor use only. Do not use the product outdoors. Do not use or store the product in any of
the following locations.
• Places directly subject to heat radiated from heating equipment.
• Places subject to splashing liquid or oil atmosphere.
• Places subject to direct sunlight.
• Places subject to intense temperature change.
• Places subject to icing and condensation.
• Places subject to vibration and large shocks.
• Places subject to dust or corrosive gas (in particular, sulfide gas and ammonia gas).
(2) Use and store the Digital Controller within the rated ambient temperature and humidity. Provide forced-cooling if required.
(3) To allow heat to escape, do not block the area around the product. Do not block the ventilation holes on the product.
(4) Be sure to wire properly with correct signal name and polarity of terminals.
(5) Use the specified size of crimped terminals (M3, width 5.8 mm or less) for wiring. To connect bare wires to the terminal
block, use copper braided or solid wires with a gage of AWG24 to AWG18 (equal to a crosssectional area of 0.205 to
0.823 mm
2
). (The stripping length is 6 to 8 mm.). Up to two wires of same size and type, or two crimped terminals can
be inserted into a single terminal.
(6) Do not wire the terminals which are not used.
(7) Allow as much space as possible between the controller and devices that generate a powerful high-frequency or surge.
Separate the high-voltage or large-current power lines from other lines, and avoid parallel or common wiring with the
power lines when you are wiring to the terminals.
(8) Use the Digital Controller within the rated load and power supply.
(9) Make sure that the rated voltage is attained within two seconds of turning ON the power using a switch or relay
contact. If the voltage is applied gradually, the power may not be reset or output malfunctions may occur.
(10) Make sure that the Digital Controller has 30 minutes or more to warm up after turning ON the power before starting
actual control operations to ensure the correct temperature display.
(11) When using adaptive control, turn ON power for the load at the same time as or before supplying power to the Digital Controller.
(12) During tuning, ensure that the power for the load (e.g., heater) is ON. Otherwise, the correct tuning result cannot be
calculated and optimal control will not be possible. Tuning is used in the following functions:
AT, adaptive control, automatic filter adjustment, and water-cooling output adjustment.
(13) A switch or circuit breaker should be provided close to this unit. The switch or circuit breaker should be within easy
reach of the operator, and must be marked as a disconnecting means for this unit.
(14) Wipe off any dirt from the Digital Controller with a soft dry cloth. Never use thinners, benzine, alcohol, or any cleaners
that contain these or other organic solvents. Deformation or discoloration may occur.
(15) Design system (control panel, etc) considering the 2 second of delay that the controller’s output to be set after power ON.
(16) The output will turn OFF when you move to the Initial Setting Level. Take this into consideration when performing control.
(17) The number of non-volatile memory write operations is limited. Therefore, use RAM write mode when frequently
overwriting data during communications or other operations.
(18) When disassembling the Digital Controller for disposal, use suitable tools.
(19) Do not exceed the communications distance that is given in the specifications and use the specified communications cable.
Refer to the
E5
D Digital Controllers User’s Manual (Cat. No. H224)
for the communications distance and cable specifications.
(20) Always turn OFF the power supply before pulling out the interior of the product, and never touch nor apply shock to the
terminals or electronic components.
When inserting the interior of the product, do not allow the electronic components to touch the case.
When you insert the interior body into the case, confirm that the hooks on the top and bottom are securely engaged with the case.
If the terminals are corroded, replace the rear case as well.
(21) Do not use the Temperature Controller if the front sheet is peeling.
Power supply voltage
Operating voltage range
Power consumption
Option 820:
All other specifications:
Indication accuracy
(Ambient temperature: 23°C)
Event input
Contact
input
No-contact input
Control output 1
Control output 2
Control method
Auxiliary outputs
Ambient temperature
Ambient humidity
Storage temperature
Altitude
Recommended fuse
Weight
Degree of protection
Installation environment
Memory protection
100 to 240 VAC, 50/60 Hz or
24 VAC, 50/60 Hz / 24VDC
85 to 110% of the rated voltage
6.6 VA max. (100 to 240 VAC)
4.1 VA max. (24 VAC)/2.3 W max. (24 VDC)
8.3 VA max. (100 to 240 VAC)
5.5 VA max. (24 VAC)/3.2 W max. (24 VDC)
Thermocouple:
(±0.3 % of indication value or ±1°C,
whichever is greater) ±1 digit max.
Platinum resistance thermometer:
(±0.2 % of indication value or ±0.8°C,
whichever is greater) ±1 digit max.
Analog input: ±0.2 % FS ±1 digit max.
Output current: approx. 7 mA per contact.
ON:1 k
Ω
max., OFF: 100 k
Ω
min.
ON: residual voltage 1.5 V max.,
OFF: leakage current 0.1 mA max.
Relay output :SPST-NO
250VAC, 5A (resistive load)
Electrical life of relay: 100,000 operations
Voltage output (for driving SSR):
12 VDC ±20%, 40 mA for one control output,
21 mA if there are two control outputs
Relay output: SPST-NO,
250 VAC, 5 A (resistive load)
Electrical life of relay: 100,000 operations
ON/OFF or 2-PID control
Relay outputs: 250 VAC, 3 A (resistive load)
Electrical life of relay: 100,000 operations
–10 to 55°C
(Avoid freezing or condensation)
25 to 85%
–25 to 65°C
(Avoid freezing or condensation)
Max. 2,000 m
T2A, 250 VAC, time-lag, low-breaking capacity
Approx. 210 g (Digital Controller only)
Front panel: IP66
Rear case: IP20, Terminal section: IP00
Overvoltage category II, pollution
degree 2 (as per IEC61010-1)
Non-volatile memory
(Number of write operations: 1,000,000)
Indicates a potentially hazardous situation which, if
not avoided, is likely to result in minor or moderate
injury or property damage. Read this manual
carefully before using the product.
Refer to the
E5
D Digital Controllers User’s Manual (Cat. No. H224)
for detailed
application procedures.
Dimensions (mm)
* You can remove only the interior body of the Digital Controller from the case with the Draw-out Jig to perform maintenance without
removing the terminal leads. Refer to the
E5
D Digital Controllers User’s Manual (Cat. No. H224)
for instructions.
* Do not remove the terminal block. Doing so may result in failure or malfunction.
Sold Separately
• Terminal cover (E53-COV24)
• Draw-out Jig (Y92F-59)
• Front-panel Setup Tool port cover (Y92S-P7)
In the pack:
• Main unit
• Instruction manual
• Watertight packing (Y92S-P9):
• Two adapters (Y92F-51):
•
The default is“5”.
•
s.err
will be displayed when a platinum resistance thermometer is mistakenly connected while
input type is not set for it. To clear the
s.err
display, correct the wiring and cycle the power supply.
*1: Upper and lower limits can be set for parameters 1, 4 and 5 to provide for different types
of alarm. These are indicated by the letter "L" and "H".
• The default alarm type is "2"
Alarms
(Alarms are output from auxiliary outputs.)
*1
*1
*1
Alarm type
Vary with
"L", "H" values
Vary with
"L", "H" values
Vary with
"L", "H" values
No alarm function
Output off
Deviation upper/lower limit
standby sequence ON
Absolute value upper limit
Absolute value lower limit
Absolute value upper limit
standby sequence ON
Absolute value lower limit
standby sequence ON
LBA (only for alarm 1)
Deviation lower limit
standby sequence ON
Deviation upper limit
standby sequence ON
Deviation upper/lower range
Deviation upper limit
Deviation lower limit
Alarm output function
Positive alarm value (X) Negative alarm value (X)
Setting
PV Change Rate Alarm
X
ON
OFF
SP
X
ON
OFF
SP
ON
OFF
SP
X
X
ON
OFF
SP
L H
ON
OFF
SP
X
ON
OFF
SP
X
ON
OFF
SP
X
ON
OFF
0
ON
OFF
X
0
X
ON
OFF
0
X
ON
OFF
0
ON
OFF
X
0
X
ON
OFF
0
X
ON
OFF
0
X
ON
OFF
0
X
ON
OFF
0
X
ON
OFF
0
ON
OFF
X
0
ON
OFF
X
0
ON
OFF
X
0
ON
OFF
X
0
L H
ON
OFF
SP
SP
ON
OFF
X
ON
OFF
X
0
1
0
2
3
4
5
6
7
8
9
SP absolute value upper limit
SP absolute value lower limit
14
15
MV absolute value upper limit
MV absolute value lower limit
16
17
10
11
12
13
SP
X
ON
OFF
ON
OFF
X
0
L H
ON
OFF
SP
4 to 20mA
0 to 20mA
1 to 5V
0 to 5V
0 to 10V
Setting range
Input type
Input
Pt100
JPt100
Thermocouple
Infrared
Thermosensor
ES1B
K
J
T
E
L
U
N
R
S
B
C/W
PL II
Setting
10 to 70°C
60 to 120°C
115 to 165°C
140 to 260°C
-200 to 850
-199.9 to 500.0
0.0 to 100.0
-199.9 to 500.0
0.0 to 100.0
-200 to 1300
-20.0 to 500.0
-100 to 850
-20.0 to 400.0
-200 to 400
-199.9 to 400.0
-200 to 600
-100 to 850
-200 to 400
-199.9 to 400.0
-200 to 1300
0 to 1700
0 to 1700
0 to 1800
0 to 2300
0 to 1300
0 to 90
0 to 120
0 to 165
0 to 260
-300 to 1500
-199.9 to 900.0
0.0 to 210.0
-199.9 to 900.0
0.0 to 210.0
-300 to 2300
0.0 to 900.0
-100 to 1500
0.0 to 750.0
-300 to 700
-199.9 to 700.0
-300 to 1100
-100 to 1500
-300 to 700
-199.9 to 700.0
-300 to 2300
0 to 3000
0 to 3000
0 to 3200
0 to 3200
0 to 2300
0 to 190
0 to 240
0 to 320
0 to 500
Platinum
resistance
thermometer
Temperature inputs
°C
°F
Use the following ranges for scaling: -1999
to 9999, -199.9 to 999.9, -19.99 to 99.99,
-1.999 to 9.999
Analog
input type
Current input
Voltage input
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
Connections
Do not connect anything to the terminals that are shaded gray.
The E5ED is set for a K thermocouple
(input type of 5) by default. If a different
sensor is used, an input error
(
s.err
)
will
occur. Check the setting of the Input Type
parameter.
E5ED-
@@@@
DM-82
@
Options
Input Power Supply
Auxiliary Outputs
Control Outputs 1, 2
(
−
)
(The applicability of the electric terminals varies with the type of machine.)
Refer to the
E5
D Digital Controllers User’s Manual (Cat. No. H224)
for information on the
Advanced Function Setting Level, Manual Control Level, and other functions.
Refer to the
E5
D Digital Controllers Communications Manual
(Cat.No. H225)
for information
on communications.
Other functions
OMRON EUROPE B.V. (Importer in EU)
Wegalaan 67-69, NL-2132 JD Hoofddorp The Netherlands
Phone 31-2356-81-300
FAX 31-2356-81-388
OMRON ELECTRONICS LLC
2895 Greenspoint Parkway, Suite 200 Hoffman Estates, IL 60169 U.S.A.
Phone 1-847-843-7900
FAX 1-847-843-7787
OMRON ASIA PACIFIC PTE. LTD.
No. 438A Alexandra Road # 05-05/08 (Lobby 2),
Alexandra Technopark, Singapore 119967
Phone 65-6835-3011
FAX 65-6835-2711
OMRON Corporation (Manufacturer)
Shiokoji Horikawa, Shimogyo-ku, Kyoto 600-8530 JAPAN
M
lcr1
0.0
Leakage Current 1
Value Monitor
(Unit: A)
M
M
Protect Level
M
sp-0
0
oapt
0
pmsk
on
icpt
1
wtpt
off
M
M
M
pfpt
off
M
M
*3
Operation / Adjustment Protect
Restricts displaying and
modifying menu items in
Operation, Adjustment, and
Manual Control Levels.
Initial Setting /
Communication Protect
Restricts movement to the
Initial Setting, Communications
Setting, and Advanced Function
Setting Levels.
Setting Change Protect
Restricts changes to settings
by operating the front panel keys.
PF Key Protect
Restricts PF
key operation.
POWER ON
in-t
5
in-h
100
in-l
0
dp
0
d-u
c
sl-h
1300
sl-l
-200
cntl
pid
s-hc
h-c
cp
20
c-cp
20
at
off
ct1
0.0
Communications Writing
cmwt
off
Heater Burnout
Detection 1
(Unit: A)
hb1
0.0
MV Upper Limit
ol-h
100.0
SP Ramp Set Value
sprt
off
Hysteresis
(Cooling)
chys
1.0
Leakage Current 1
Value Monitor
(Unit: A)
lcr1
0.0
Integral Time
(Unit: Seconds)
i
233
Derivative Time
(Unit: Seconds)
d
40
MV Lower Limit
ol-l
-100.0
HS Alarm 1
(Unit: A)
hs1
5
0.0
25
0
AT Execute/Cancel
100%AT Execute
at-2
40%AT Execute
at-1
Dead Band
c-db
0.0
Manual Reset Value
Clears the offset
during P or PD control.
of-r
50.0
Hysteresis
(Heating)
hys
1.0
Proportional
Band
p
8.0
Integral Time
(Cooling)
(Unit: Seconds)
c-i
233
Derivative Time
(Cooling)
(Unit: Seconds)
c-d
40
Proportional
Band (Cooling)
c-p
300.0
Alarm 1 to 4
Hysteresis
Operation stopped.
(Both control and auxiliary outputs are stopped.)
Input Type *
2
Scaling Upper Limit
(only when setting
analog input)
Scaling Lower Limit
(only when setting
analog input)
Decimal Point
(only when setting
analog input)
Temperature
Unit
SP Upper Limit
SP Lower Limit
PID•ON/OFF
In ON/OFF control =
onof
In 2-PID control =
pid
Standard or Heating/Cooling
Standard control =
stnd
Heating and cooling control =
h-c
Control Period (Heating)
(Unit: Seconds)
*Voltage output
(for driving SSR): 2
Alarm 1 to 4 Type
Control Period (Cooling)
(Unit: Seconds)
*Voltage output
(for driving SSR): 2
°C=
c
°F=
f
Direct/Reverse Operation
In Reverse operation
(Heating) =
or-r
In Direct operation
(Cooling) =
or-d
*2
Initial Setting Level
(No.1 display flashes,
then the control stops.)
Hold
O
down
for at least
3 seconds
Hold
O
down
for at least
1 second
(The No.3 display
has been omitted.)
Press
O
(less than
1 second)
Operation Level
Check the wiring before turning ON the power supply.
Process Value/Set Point
s.err
is displayed when
connected sensor is
different from input type.
sp-m
0
ct1
0.0
Multi-SP
Set Point Selection
m-sp
0
Set Point During
SP Ramp
Heater Current 1
Value Monitor
(Unit: A)
Operation level should normally be used during operations.
Hold
O
and
M
keys
down for at least 1 second
Hold
O
and
M
keys
down for at least 3 seconds
Restricts which settings can be displayed or changed, and restricts
change by key operation.
Adjustment Level
Heater Current 1
Value Monitor
(Unit: A)
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
Communications
Monitor
plcm
0
orev
or-r
M
alt1
2
alh1
0.2
M
Event Input
Assignment 1
ev-1
msp0
Event Input
Assignment 2
ev-2
stop
M
M
M
M
Move to Advanced
Function Setting
Level
amov
0
M
run
stop
r-s
run
When control start
=
When control stop
=
RUN/STOP
M
Alarm Value
Lower Limit
1 to 4
Alarm Value
1 to 4
Alarm Value
Upper Limit
1 to 4
al1l
0
al-1
0
al1h
0
M
M
*2: Refer to the adjoining tables for details of input types and alarm types.
*3: Operation is stopped when moved to the initial setting level. (Both control and auxiliary outputs are stopped.)
*4: The grayed-out setting items are not displayed for some models and some settings of other setting items.
Typical example: The parameters are not displayed under the following conditions.
• AT Execute/Cancel: Not displayed if
PID ON/OFF
is set to ON/OFF.
• Alarm 1 Type: The default setting is for Controllers that are not equipped with HB/HS alarms.
For a Controller equipped with HB/HS alarms, the Auxiliary Output 1 Assignment parameter (Advanced Function
Setting Level) is set to a heater alarm. If you set alarm 1, the Alarm 1 Type parameter will be displayed.
Refer to the
E
5
D Digital Controllers User’s Manual (Cat. No. H224)
for the setting method.
PV
Input Shift
ins
0.0
M
M
SP 0 to 7
Only the value set to the
ins
: Temperature Input Shift parameter is applied to the entire
temperature input range. When the process value is 200°C, the process value is treated as
201.2°C after input shift if the input shift value is set to 1.2°C. The process value is treated
as 198.8°C after input shift if the input shift value is set to -1.2°C.
M
M
Adjustment level is for entering set values and
shift values for control.
Auxiliary output 1, 2
Voltage output (for driving SSR)
12 VDC, 40 mA
21 mA if there are
two control outputs
Relay output
250 VAC, 5A (resistive load)
Control output 1
Relay output
250 VAC, 5A
(resistive load)
Control output 2
Relay output
250 VAC, 3 A
(resistive load)
Sensor Temperature/Analog Input
Options
V
−
23
V
24
+
22
TC
22
+
−
mA
−
+
23
22
23
24
Pt
I
24
22
23
24
A
B
B
21
19
20
21
19
20
17
18
16
17
18
13
14
15
15
16
820
828
13
14
EV1
EV2
B(+)
A(
−
)
RS-485
CT1
(
−
)
21
19
20
17
18
15
16
13
14
EV1
EV2
CT1
100 to 240 VAC
24 VAC/DC
Input Power Supply
A
D
7
8
11
12
Auxiliary outputs 1 to 2
9
10
(no polarity)
Communications, two
event inputs, and one CT
821
Two event inputs,
and one CT
Individual mounting (mm)
Bar Display Data
bar
mv
M
Bar Display Scaling
Upper Limit
barh
100.0
M
Bar Display Scaling
Lower Limit
barl
0.0
M
Initial setting level enables users to specify their preferred operating
conditions (input type, alarm type, control method, etc.)
Auxiliary output 2
Auxiliary output 1
(64)
4
1
60
110
44
91
SP Response
Proportional Band
SP Response
Integral Time
(Unit: Seconds)
sp-i
233
SP Response
Derivative Time
(Unit: Seconds)
sp-d
40
sp-p
8.0
M
M
M
SP Response
Coefficient
Number
sp-n
0
M
Disturbance
Integral Time
(Unit: Seconds)
d-i
233
Disturbance
Derivative Time
(Unit: Seconds)
d-d
40
Disturbance
Proportional Band
d-p
8.0
M
M
M
Water-cooling
Output Adjustment
inf
0.0
PID Update
(Adaptive Control)
a-ud
off
Automatic Filter
Adjustment
fa
off
M
M
M
Water-cooling
Proportional Band
Increase Threshold
w-il
1.4
Water-cooling
Proportional
Band Decrease
Threshold
w-dl
0.6
Input Digital Filter
w-ht
off
Startup Operation
p-on
cont
M
Model Creation
OFF Time
m-of
0
Model Creation
PV Amplitude
m-pv
0.0
M
Model Creation
MV Amplitude
m-mv
0.0
M
Model Creation
ON Time
m-on
0
off
fix
info
auto
Adaptive Control
Disabled =
Fixed =
Notification =
Automatic update =
adpt
off
48
96
Deviation upper/lower limit
Conformance to Safety Standard
Due to UL Listing requirements, use the E54-CT1L or E54-CT3L current
transformer with the factory wiring (internal wiring).
Use a UL category XOBA or XOBA7 current transformer that is UL Listed
for field wiring (external wiring) and not the factory wiring (internal wiring).
Always externally connect the recommended fuse that is specified in the
Instruction Manual before you use the Digital Controller.
Analog Input
• If you input an analog voltage or current, set the Input Type parameter to
the correct input type.
• Do not use the Digital Controller to measure a circuit with Measurement
Category II, III, or IV.
• Do not use the Digital Controller to measure an energized circuit to which
a voltage that exceeds 30 Vrms or 60 VDC is applied.
The protection provided by the Digital Controller may be impaired if the Digital
Controller is used in a manner that is not specified by the manufacturer.
Conformance to EN/IEC Standards
This is a class A product.
In residential areas it may cause radio interference, in which case the user
may be required to take adequate measures to reduce interference.
A 급 기기 (업무용 방송통신기자재)
이 기기는 업무용(A 급) 전자파적합기기로서 판매자또는 사용자는 이 점을
주의하시기 바라며, 가정외의지역에서 사용하는 것을 목적으로 합니다.
*5: Error shown only for "Process value / Set point". Not shown for other status.
When an error has occurred, the No.1 display shows the error code. Take necessary measure
according to the error code, referring the table below.
If the input value exceeds the display limit (-9999 to 9999), though it is within the control
range,
[[[[
will be displayed under -1999 and
]]]]
above 9999.
Under these conditions, control outputs and alarms will operate normally.
Refer to the
E5
D Digital Controllers User’s Manual (Cat. No. H224)
for the controllable ranges.
Check the setting of the Input Type parameter,
check the input wiring, and check for broken or
shorts in the temperature sensor.
Turn the power OFF then back ON again. If the
display remains the same, the controller must be
repaired. If the display is restored to normal, then
a probable cause can be external noise affecting
the control system. Check for external noise.
After the check of input error, turn the power OFF
then back ON again. If the display remains the
same, the controller must be repaired. If the
display is restored to normal, then a probable
cause can be external noise affecting the control
system. Check for external noise.
No.1 display
Meaning
A/D converter error
*5
Memory error
Input error
*5
s.err
(S. Err)
e111
(E111)
Action
OFF
Alarm
Control
output
Status at error
OFF
OFF
Operates
as above the
upper limit.
OFF
OFF
e333
(E333)
Error Display (troubleshooting)
•
A:
Flashing or lit during adaptive control.
•
Bar Display: (The default value is heater current.
)
Displays the MV or heater current in 10 steps.
Set the parameters of the product so that they are suitable for the system being controlled. If they
are not suitable, unexpected operation may occasionally result in property damage or accidents.
Loose screws may occasionally result in fire.
Tighten the terminal screws to the specified torque of 0.43 to 0.58 N•m.
The maximum terminal temperature is 75°C. Use wires with a heat resistance of 75°C min to wire the terminals.
A malfunction in the Digital Controller may occasionally make control operations impossible
or prevent alarm outputs, resulting in property damage. To maintain safety in the event of
malfunction of the Digital Controller, take appropriate safety measures, such as installing a
monitoring device on a separate line.
23
24
19
20
21
22
17
13
14
15
16
18
2
1
2
1
~
Auxiliary Outputs
Control Outputs 1, 2
~
*1. When complying with EMC standards, the line connecting the sensor must be 30 m or less.
If the cable length exceeds 30 m, compliance with EMC standards will not be possible.
*2. Use non-voltage inputs for the event inputs. The polarity for a non-contact input is indicated by “(-).”
Parameter Mask
Enable
Press and hold the
M
Key to cycle through the parameters in reverse.
M
11
12
9
10
2
7
8
5
6
3
4
1
Crimp Terminal Sizes: M3
Two relay outputs
QR
RR
OUT2
R
+
-
OUT1
Q
OUT2
R
Voltage output
(for driving SSRs)
and relay output
5
6
+
-
3
4
5
6
3
4
5
6
3
4
OUT1
Q
+
-
OUT2
Q
Two voltage outputs
(for driving SSRs)
OUT1
R