7
E5CN-H
Characteristics
*1.
The indication accuracy of K thermocouples in the
−
200 to 1300
°
C range, T and N thermocouples at a temperature of
−
100
°
C max., and U
and L thermocouples at any temperatures is
±
2
°
C
±
1 digit max. The indication accuracy of the B thermocouple at a temperature of 400
°
C max.
is not specified. The indication accuracy of B thermocouples in the 400 to 800
°
C range is
±
3
°
C max. The indication accuracy of the R and S
thermocouples at a temperature of 200
°
C max. is
±
3
°
C
±
1 digit max. The indication accuracy of W thermocouples is
±
0.3 of PV or
±
3
°
C,
whichever is greater,
±
1 digit max. The indication accuracy of PL II thermocouples is
±
0.3 of PV or
±
2
°
C, whichever is greater,
±
1 digit max.
*2.
Ambient temperature:
−
10
°
C to 23
°
C to 55
°
C, Voltage range:
−
15% to 10% of rated voltage
*3.
K thermocouple at
−
100
°
C max.:
±
10
°
C max.
*4.
External communications (RS-232C or RS-485) and cable communications for the Setup Tool can be used at the same time.
*5.
Refer to information on maritime standards in
Safety Precautions for E5
@
N/E5
@
N-H
for compliance with Lloyd's Standards.
*6.
Industrial electromagnetic environment (EN/IEC 61326-1 Table 2)
Indication accuracy
Thermocouple: (
±
0.1% of indicated value or
±
1
°
C, whichever is greater)
±
1 digit max.
*
1
Platinum resistance thermometer: (
±
0.1% of indicated value or
±
0.5
°
C, whichever is greater)
±
1 digit max.
Analog input:
±
0.1% FS
±
1 digit max.
CT input:
±
5% FS
±
1 digit max.
Transfer output accuracy
±
0.3% FS max.
Influence of temperature
*
2
Thermocouple input (R, S, B, W, PLII): (
±
1% of PV or
±
10
°
C, whichever is greater)
±
1 digit max.
Other thermocouple input: (
±
1% of PV or
±
4
°
C, whichever is greater)
±
1 digit max.
*
3
Platinum resistance thermometer: (
±
1% of PV or
±
2
°
C, whichever is greater)
±
1 digit max.
Analog input: (
±
1%FS)
±
1 digit max.
Influence of voltage
*
2
Influence of EMS.
(at EN 61326-1)
Input sampling period
60 ms
Hysteresis
Temperature input: 0.1 to 3240.0
°
C or
°
F (in units of 0.1
°
C or
°
F)
Analog input: 0.01% to 99.99% FS (in units of 0.01% FS)
Proportional band (P)
Temperature input: 0.1 to 3240.0
°
C or
°
F (in units of 0.1
°
C or
°
F)
Analog input: 0.1% to 999.9% FS (in units of 0.1% FS)
Integral time (I)
0.0 to 3240.0 s (in units of 0.1 s)
Derivative time (D)
0.0 to 3240.0 s (in units of 0.1 s)
Control period
0.5, 1 to 99 s (in units of 1 s)
Manual reset value
0.0 to 100.0% (in units of 0.1%)
Alarm setting range
−
19999 to 32400 (decimal point position depends on input type)
Affect of signal source
resistance
Thermocouple: 0.1
°
C/
Ω
max. (100
Ω
max.)
Platinum resistance thermometer: 0.1
°
C/
Ω
max. (10
Ω
max.)
Insulation resistance
20 M
Ω
min. (at 500 VDC)
Dielectric strength
2,300 VAC, 50 or 60 Hz for 1 min (between terminals with different charge)
Vibration
resistance
Malfunction
10 to 55 Hz, 20 m/s
2
for 10 min each in X, Y, and Z directions
Destruction
10 to 55 Hz, 0.75-mm single amplitude for 2 hrs each in X, Y, and Z directions
Shock
resistance
Malfunction
100 m/s
2
, 3 times each in X, Y, and Z directions
Destruction
300 m/s
2
, 3 times each in X, Y, and Z directions
Weight
Controller: Approx. 150 g, Mounting Bracket: Approx. 10 g
Degree of protection
Front panel: IP66, Rear case: IP20, Terminals: IP00
Memory protection
Non-volatile memory (number of writes: 1,000,000 times)
Setup Tool
CX-Thermo version 4.0 or higher
Setup Tool port
Provided on the bottom of the E5CN-H. Use this port to connect a computer to the E5CN-H.
An E58-CIFQ1 USB-Serial Conversion Cable is required to connect the computer to the E5CN-H.
*
4
Standards
Approved
standards
UL 61010-1, CSA C22.2 No. 1010-1
Conformed
standards
EN 61010-1 (IEC 61010-1): Pollution level 2, overcurrent category II, Lloyd's standards
*
5
EMC
EMI: EN
61326-1
*
6
Radiated Interference Electromagnetic Field Strength: EN 55011 Group 1, class A
Noise Terminal Voltage:
EN 55011 Group 1, class A
EMS: EN
61326-1
*
6
ESD Immunity:
EN 61000-4-2
Electromagnetic Field Immunity:
EN 61000-4-3
Burst Noise Immunity:
EN 61000-4-4
Conducted Disturbance Immunity:
EN 61000-4-6
Surge Immunity:
EN 61000-4-5
Power Frequency Magnetic Field Immunity:
EN 61000-4-8
Voltage Dip/Interrupting Immunity:
EN 61000-4-11
Buy Now: www.ValinOnline.com | Phone: 800-774-5630 | Email: [email protected]