E5CD-800/E5CD-B-800
10
Characteristics
*1.
The indication accuracy of K thermocouples in the
−
200 to 1,300°C range, T and N thermocouples at a temperature of
−
100°C max., and U and
L thermocouples at any temperatures is
±
2°C
±
1 digit max. The indication accuracy of the B thermocouple at a temperature of 400°C max. is not
specified. The indication accuracy of B thermocouples at a temperature of 400 to 800°C is
±
3°C max. The indication accuracy of the R and S
thermocouples at a temperature of 200°C max. is
±
3°C
±
1 digit max. The indication accuracy of C/W thermocouples is (
±
0.3% of PV or
±
3°C,
whichever is greater)
±
1 digit max. The indication accuracy of PL II thermocouples is (
±
0.3% of PV or
±
2°C, whichever is greater)
±
1 digit max.
*2.
Ambient temperature:
−
10°C to 23°C to 55°C, Voltage range:
−
15% to 10% of rated voltage
*3.
K thermocouple at
−
100°C max.:
±
10°C max.
*4.
The unit is determined by the setting of the Integral/Derivative Time Unit parameter.
*5.
Industrial electromagnetic environment (EN/IEC 61326-1 Table 2)
Indication accuracy
(at the ambient temperature of 23°C)
Thermocouple: (
±
0.3% of indication value or
±
1°C, whichever is greater)
±
1 digit max.
*
1
Platinum resistance thermometer:
(
±
0.2% of indication value or
±
0.8°C, whichever is greater)
±
1 digit max.
Analog input:
±
0.2% FS
±
1 digit max.
CT input:
±
5% FS
±
1 digit max.
Influence of temperature
*
2
Thermocouple input (R, S, B, C/W, PL II):
(±1% of indication value or ±10°C, whichever is greater) ±1 digit max.
Other thermocouple input:
(
±
1% of indication value or
±
4°C, whichever is greater)
±
1 digit max.
*
3
Platinum resistance thermometer:
(
±
1% of indication value or
±
2°C, whichever is greater)
±
1 digit max.
Analog input:
±
1% FS
±
1 digit max.
CT input:
±
5% FS
±
1 digit max.
Influence of voltage
*
2
Influence of EMS. (at EN 61326-1)
Input sampling period
50 ms
Hysteresis
Temperature input: 0.1 to 999.9°C or °F (in units of 0.1°C or °F)
Analog input: 0.01% to 99.99% FS (in units of 0.01% FS)
Proportional band (P)
Temperature input: 0.1 to 999.9°C or °F (in units of 0.1°C or °F)
Analog input: 0.1% to 999.9% FS (in units of 0.1% FS)
Integral time (I)
0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s)
*
4
Derivative time (D)
0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s)
*
4
Proportional band (P) for cooling
Temperature input: 0.1 to 999.9°C or °F (in units of 0.1°C or °F)
Analog input: 0.1% to 999.9% FS (in units of 0.1% FS)
Integral time (I) for cooling
0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s)
*
4
Derivative time (D) for cooling
0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s)
*
4
For
adaptive
control
SP response proportional band
Temperature input: 0.1 to 999.9°C or °F (in units of 0.1°C or °F)
SP response integral time
0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s)
*
4
SP response derivative time
0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s)
*
4
Disturbance proportional band
Temperature input: 0.1 to 999.9°C or °F (in units of 0.1°C or °F)
Disturbance integral time
0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s)
*
4
Disturbance derivative time
0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s)
*
4
Control period
0.1, 0.2, 0.5, 1 to 99 s (in units of 1 s)
Manual reset value
0.0 to 100.0% (in units of 0.1%)
Alarm setting range
−
1999 to 9999 (decimal point position depends on input type)
Influence of signal source resistance
Thermocouple: 0.1°C/
Ω
max. (100
Ω
max.)
Platinum resistance thermometer: 0.1°C/
Ω
max. (10
Ω
max.)
Insulation resistance
20 M
Ω
min. (at 500 VDC)
Dielectric strength
3,000 VAC, 50/60 Hz for 1 min between terminals of different charge
Vibration
Malfunction
10 to 55 Hz, 20 m/s
2
for 10 min each in X, Y, and Z directions
Resistance
10 to 55 Hz, 20 m/s
2
for 2 hrs each in X, Y, and Z directions
Shock
Malfunction
100 m/s
2
, 3 times each in X, Y, and Z directions
Resistance
300 m/s
2
, 3 times each in X, Y, and Z directions
Weight
Controller: Approx. 120 g, Mounting Adapter: Approx. 10 g
Degree of protection
Front panel: IP66, Rear case: IP20, Terminals: IP00
Memory protection
Non-volatile memory (number of writes: 1,000,000 times)
Standards
Approved standards
cULus: UL 61010-1/CSA C22.2 No.61010-1,
Korean wireless regulations (Radio law: KC Mark)
Conformed standards
EN 61010-1 (IEC 61010-1) and RCM standards
EMC
EMI: EN
61326-1
*5
Radiated Interference Electromagnetic Field Strength: EN 55011 Group 1, class A
Noise Terminal Voltage:
EN 55011 Group 1, class A
EMS:
EN 61326-1
*5
ESD Immunity:
EN 61000-4-2
Electromagnetic Field Immunity:
EN 61000-4-3
Burst Noise Immunity:
EN 61000-4-4
Conducted Disturbance Immunity:
EN 61000-4-6
Surge Immunity:
EN 61000-4-5
Voltage Dip/Interrupting Immunity:
EN 61000-4-11
Summary of Contents for E5CD-B-800 Series
Page 38: ...MEMO 38 ...
Page 54: ...MEMO 54 ...