7 Troubleshooting and Maintenance
7 - 8
E3NW-CCL CC-Link Digital Sensor Communications Unit User’s Manual (E431)
Check that the following items are within the criteria.
If they do not meet the criteria, improve the surrounding environment so that the affected items are
within the acceptable standard range or adjust the Communications Unit as required.
Every Unit (the CC-Link master and E3NW-CCL Units) is part of the network.
If a Unit malfunctions, this can affect the entire network and therefore must be repaired as soon as
possible.
We recommend keeping replacement Units available in order to minimize the time needed to restore
network functionality if required.
Be aware of the following points when replacing a malfunctioning Communications Unit.
•
After replacement, check to confirm that there are no problems with the new Unit.
•
If you are returning a defective Unit for repair, be sure to write down any details of the problem and
send the information along with the defective Unit to your nearest OMRON representative.
•
For poor contacts, wipe down the contacts with a clean 100% cotton cloth soaked in industrial
alcohol.
After replacing a Unit, be sure to set all switches and other settings to be the same those in the
previous Unit.
Inspection Items
Inspection
Items
Inspection details
Criteria
Inspection
method
Environmental
status
Are the ambient and internal panel
temperatures normal?
0 to 55
°
C
Thermometer
Are the ambient and internal panel
humidity normal?
25% to 85% (with no
condensation or icing)
Hygrometer
Is there any build-up of dust?
There must be no dust.
Visual inspection
Installation
status
Is the E3NW-CCL securely mounted into
place?
The Communications Unit
must not be loose.
Phillips screwdriver
Are the communications cable
connectors completely inserted?
The communications cable
connectors must not be loose.
Visual inspection
Are there any loose screws on external
wiring?
The screws on external wiring
must not be loose.
Phillips screwdriver
Are any connection cables loose or
about to be disconnected?
There must be no visual
anomalies.
Visual inspection
7-2-3
Handling Communications Units for Replacement
Precautions when Replacing Units
Settings after Replacing Units
Summary of Contents for E3NW-CCL
Page 1: ...E3NW CCL CC Link Digital Sensor Communications Unit User s Manual Cat No E431 E1 08 ...
Page 114: ...A Appendices A 34 E3NW CCL CC Link Digital Sensor Communications Unit User s Manual E431 ...
Page 116: ...B B 2 E3NW CCL CC Link Digital Sensor Communications Unit User s Manual E431 ...
Page 117: ......