64
Editing Parameters
Section 3-1
3-1-5
Test Output Parameter Groups
This section describes parameters in the test output groups.
The test output parameters are grouped by terminal number.
Note
The time and count maintenance counter modes (contact operation counter
and total ON time monitor function) cannot be used for the test output termi-
nals of the DST1-XD0808SL-1.
Item
Settings
Description
Default
S
Test Output Mode
Not Used.
The corresponding test output is not used.
Not Used.
Standard Output
Specifies connecting to the input for a muting
lamp or PLC. Used as a monitor output.
Pulse Test Output
Specifies connecting a device with a contact
output in combination with the safety input.
Power Supply Output
Specifies connecting to the power supply ter-
minal of a safety sensor.
The voltages supplied to the IO power from
the test output are output.
Muting Lamp Output
(Setting supported only
for T3 terminal.)
Specifies a muting lamp output.
When the output is ON, disconnection of the
muting lamp can be detected.
Fault Action
Clear off
Sets the output state of the test output when
a communications error occurs.
This parameter is enabled when the Test
Output Channel Mode is set to
Standard
Output or Muting Lamp Output
.
Clear off
Hold last data
I/O Comment
32 characters max.
Sets an I/O comment for the test output. The
I/O comment set here is used as the I/O tag
in the Logic Editor.
None
Maintenance Counter
Mode Choice
Time (cumulative ON
time monitor)
Sets the operating mode for the mainte-
nance counter.
Time
Count (contact opera-
tion counter)
Threshold Mainte-
nance Counter
0 to 4,294,967,295
hours
Sets the threshold value for the maintenance
counter.
0
Summary of Contents for DST1-ID12SL-1
Page 1: ...OPERATION MANUAL Cat No Z904 E1 06 DeviceNet Safety DST1 series Safety I O Terminals...
Page 2: ......
Page 3: ...DST1 series Safety I O Terminals Operation Manual Revised June 2011...
Page 4: ...iv...
Page 10: ...x...
Page 14: ...xiv...
Page 110: ...86 Remote I O Allocations Section 3 2...
Page 116: ...92 Indicators Section 4 2...
Page 134: ...110 DST1 XD0808SL 1 Section 5 4...
Page 146: ...122 Maintenance Section 7 4...
Page 159: ...135 Logic Terminal Wiring Examples Section 8 3...
Page 160: ...136 Logic Terminal Wiring Examples Section 8 3...
Page 178: ...154 Index...
Page 181: ...157 Revision History...