background image

 

187

Unit Descriptions

DeviceNet Wireless Link

WD30

Wireless Interface Specifications

Note: 1.

The actual transmission distance depends on many factors in the installation environment.

2.

The wireless system is not suitable for applications requiring real-time control.

DeviceNet Interface Specifications (Summary)

Note:

FINS message communications are not supported. Explicit messages must be handled in the ladder program. Refer to the 

WD30 DeviceNet

Wireless Units Operation Manual

 for details.

I/O Points

Note:

Relay Stations can be used to create up to 3 levels and DeviceNet Slaves can be connected in each level. Terminators are required when
Slaves are connected to a Relay Station or Slave Station. Refer to the 

WD30 DeviceNet Wireless Units Operation Manual

 for details on Ter-

minator installation.

Item

Specifications

Wave type

Spread Spectrum (direct sequence; DS-SS)

Communication method

Simplex (half duplex)

Frequency band

2.4 GHz (2401 MHz to 2480.2 MHz)

Number of channels

34 channels (based on frequency division)

Antenna power 

10 mW

Data transfer speed between wireless units

100 kbps

Transmission distance (See note 1.)

Indoors: 60 m (approx. 50 m with magnetic base antennas)

Outdoors: 300 m (unobstructed)

Relay stations

3 repeaters max.

Max. number of sets in the same area (See note 1.)

10 sets max.

Max. number of wireless Slaves

64 max.

Item

Specifications

Communications functions 
(See note.)

Master/Slave connections

Remote I/O functions and Explicit message communications functions

Self-diagnostic functions

Unit

WDT error, hardware errors (such as memory and CAN errors), and setting er-
rors

DeviceNet communications

Duplicate node address errors, Bus OFF detection, and connection timeout

Device profiles

Communication control unit

Refer to Appendix A of the 

WD30 DeviceNet Wireless Units Operation Manual

 

for various DeviceNet IDs (vendor, device type = communication adapter, prod-
uct code, product revision, product name, serial number, status, and I/O unit 
IDs.)

Name

Number of I/O points (words used)

DeviceNet Wireless Master

1,600 inputs max. (100 words)
1,600 outputs max. (100 words)

DeviceNet Wireless Slave

512 inputs max. (32 words)
512 outputs max. (32 words)

Reviews: