4. Setting (Air Flow Station Operation)
4-22
(3)
Leak Detection Flow Rate (NN.CUT)
Specify the threshold value for zero flow rate. A value between the lower threshold and zero
flow rate values must be specified.
If the specified threshold is exceeded, the status indication of the Air Flow Sensor changes.
D6FZ-FGS1000
The range of selection (Numeric input):
0 L/min to 1000 L/min
Initial value:
0 L/min
D6FZ-FGT500
The range of selection (Numeric input):
0 L/min
~
500 L/min
Initial value:
0 L/min
D6FZ-FGT200
The range of selection (Numeric input):
0 L/min
~
200 L/min
Initial value:
0 L/min
(4)
Alarm Hold Setting (HOLD)
Specifies if the alarm output is held when a measured value outside the upper and lower
threshold range (Alarm status) returns to a normal value within the range during RUN
operation.
The range of selection (Options):
ON / OFF
Initial value:
OFF
4.3.5 Changing Set Value
Follow the same procedure as in FUN mode.
To change Air Flow Sensor set values, display the ID of the target Air Flow Sensor unit and
enter THR mode.
(Refer to "4.2.5 Changing Air Flow Station Set Value" and "4.2.6 Changing Air Flow Sensor
Set Value")
D6FZ-FGT
displays “REMOTE” and key operations are not available.
When mode of the Air Flow Station is returned to RUN-mode, “REMOTE” is canceled.