59
Optical Wiring
Section 3-3
4.
Use a dedicated power supply for the backup power supply. Do not share
a power supply being used for I/O, motors, or control systems.
5.
When two or more nodes are connected to a single power supply, wire
each node separately.
6.
When using Controller Link Units in duplex operation in a CS1D System,
provide backup power supplies for both the active and standby Controller
Link Units. If the backup power supply for the standby Unit is stopped, com-
munications will be interrupted at that point and a disconnection will be de-
tected.
3-3-4
Connecting Optical Fiber Cable to Connectors for H-PCF Cable
A special connector is used to connect the Optical Fiber Cable to the Control-
ler Link Unit.
This manual does not provide details on Optical Fiber Cable preparation.
Connect the Optical Fiber Cables to the nodes in order from higher to lower
nodes. (When a ring topography is being used, connect the last node to the
first node, too.)
Observe the following precautions when connecting the Optical Fiber Cables.
• Always turn OFF the PLC power supply before connecting Optical Fiber
Cables (except for online replacement).
• Special tools are required to attach Optical Fiber Cables to the connec-
tors. The cable may disconnect from the connector if the proper tools and
methods are not used during cable assembly.
Connection Procedure
Use the following procedure to connect Optical Fiber Cables to a Unit.
1,2,3...
1.
Tighten screws in the mounting brackets so that the through-holes on the
terminal are on the top and bottom and then affix hexagonal nuts from the
opposite side of the terminal.
2.
Insert bushing to the mounting bracket and secure the Unit with screws.
3.
Pass the tension member through the through-holes, and tighten the ter-
minal screws to affix the tension member.
4.
Affix the cable to the mounting bracket so that it is clamped by the bracket.
Two cables can be attached at the same time.
5.
Move the cable connector so that the loose ends are on the left-hand side,
and insert the Unit’s optical connector as far as it will reach.
Power source
Power source
OK
Wrong
Summary of Contents for CS1W-CLK12-V1
Page 3: ...iv ...
Page 5: ...vi ...
Page 9: ...x TABLE OF CONTENTS ...
Page 11: ...xii ...
Page 59: ...42 Component Names and Functions Section 3 1 Dimensions Unit mm ...
Page 62: ...45 Component Names and Functions Section 3 1 Dimensions Unit mm ...
Page 91: ...74 CVM1 and CV series Optical Ring Controller Link Units Section 4 2 ...
Page 108: ...91 Setting Data Links Section 5 2 Device Information Setting Data Link Tables ...
Page 125: ...108 Checking Data Link Status Section 5 4 ...
Page 181: ...164 Setting Routing Tables Section 7 4 ...
Page 199: ...182 Memory Areas Related to Duplex Operation Section 8 6 ...
Page 275: ...258 Handling Precautions Section 10 7 ...
Page 298: ...281 CS series Optical Bus Controller Link Units Appendix C Dimensions Unit mm 101 35 130 ...
Page 299: ...282 CS series Optical Bus Controller Link Units Appendix C ...