123
Using the Message Service
Section 6-3
CVM1 and CV-series PLCs
Network Status
The nodes on the network are shown in the following illustrations.
CS-series, CVM1, and CV-series PLCs
Communications Flag Operations
• The Network Instruction Enabled Flag turns OFF during transmission or
reception, and ON after the data transmission or reception has been com-
pleted (regardless of whether an error occurs).
• The Network Instruction Error Flag retains its status until the next data
transmission or reception.
• Even when there is an abnormal end, the Network Instruction Error Flag
turns OFF when the next communications instruction is executed.
Example
Name
Address
Contents
Word
Bit
Network
Instruction
Enabled Flag
A502
Port number corresponds
to bit number, i.e., port 0:
bit 00, port 1, bit 00, etc.
0: Execution not enabled (executing)
1: Execution enabled (not executing)
Network
Instruction
Error Flag
A502
Port number corresponds
to bit number plus 8, i.e.,
port 0: bit 08, port 1, bit 09,
etc.
0: Normal end
1: Abnormal end
*1 When Optical Bus Controller Link Units/Boards (CLK11) are combined in a
network with Optical Ring Controller Link Units/Boards in token-bus mode,
only node addresses 1 to 32 are checked for their participation status.
N: Unit number
-: Not used
0: Not participating in network.
1: Participating in network.
(The numbers in the grid are the node numbers for the corresponding bit.)
Network Instruction Enabled Flag
Communications instruction
(SEND/RECV/CMND)
Network Instruction Error Flag
Communications instruction response code
Instruction 2
being executed
Instruction 3
being executed
Previous
end
1
0
1
0
Instruction 1
being executed
00
00
00
00
04
00
(Normal
end)
(Normal
end)
(Busy)
Summary of Contents for CS1W-CLK12-V1
Page 3: ...iv ...
Page 5: ...vi ...
Page 9: ...x TABLE OF CONTENTS ...
Page 11: ...xii ...
Page 59: ...42 Component Names and Functions Section 3 1 Dimensions Unit mm ...
Page 62: ...45 Component Names and Functions Section 3 1 Dimensions Unit mm ...
Page 91: ...74 CVM1 and CV series Optical Ring Controller Link Units Section 4 2 ...
Page 108: ...91 Setting Data Links Section 5 2 Device Information Setting Data Link Tables ...
Page 125: ...108 Checking Data Link Status Section 5 4 ...
Page 181: ...164 Setting Routing Tables Section 7 4 ...
Page 199: ...182 Memory Areas Related to Duplex Operation Section 8 6 ...
Page 275: ...258 Handling Precautions Section 10 7 ...
Page 298: ...281 CS series Optical Bus Controller Link Units Appendix C Dimensions Unit mm 101 35 130 ...