72
Section 4
Using th
e Dist
ribut
ed Sen
s
or Unit
E3NW-CRT
User’s Manual
Section 4
Distributed Sensor Unit Power Supply Specifications and Connections
Connecting the Unit Power Supply
Connect a cable from the Unit power supply (24 VDC) to the power supply connectors on
each Distributed Sensor Unit.
Securely attach ferrules to the Unit power supply cable wires.
●
Recommended Parts
We recommend using the following ferrules for the Unit power supply cable.
We recommend the following screwdriver for the removal of ferrules.
To 24-VDC Unit
power supply
Unit power
supply cable
Ferrule
+V terminal
−
V terminal
Model number
Applicable wire size
Crimp tool
Manufacturer
AI0,5-10WH
0.5 mm
2
/AWG20
CRIMPFOX UD6 (product
No. 1204436) or
CRIMPFOX ZA3 Series
Phoenix Contact Co., Ltd.
H0.5/16 orange
0.5 mm
2
/AWG20
Crimper PZ1.5 (product
No. 900599)
Weidmueller Japan Co., Ltd.
Model number
Manufacturer
XW4Z-00C
OMRON Corporation