An expert who is well trained in safety measures, standards, and specifications should be asked to
perform the installation.
• Do not install EtherCAT network equipment near sources of noise.
If the network must be installed in an area subject to noise, take steps to address the noise, such as
placing equipment in metal cases.
Precautions when Installing Communications Cables
• Check the following items on the communications cables that are used in the network.
a) Are there any breaks?
b) Are there any shorts?
c) Are there any connector problems?
• When you connect the cable to the communications connectors on devices, firmly insert the commu-
nications cable connector until it locks in place.
• Do not lay the communications cables together with high-voltage lines.
• Do not lay the communications cable near devices that generate noise.
• Do not lay the communications cables in locations subject to high temperatures or high humidity.
• Do not lay the communications cables in locations subject to excessive dirt and dust or to oil mist or
other contaminants.
• There are limitations on the bending radius of communications cables. Check the specifications of
the communications cable for the bending radius.
4-5-3
Installing EtherCAT Communications Cables
Ethernet communications cables and connectors are used to connect the EtherCAT port of the Motion
Controller with EtherCAT slaves.
Use a straight, shielded twisted-pair cable (double shielding with aluminum tape and braiding) of
Ethernet category 5 (100BASE-TX) or higher.
The following products are recommended.
Cable with Connectors
Sizes and Conductor Pairs: AWG 26 × 4 Pairs
Product name
Manufac-
turer
Cable
length
Model
Contact in-
formation
Cable with Connectors on Both
Ends
(RJ45/RJ45)
Standard RJ45 connector type
OMRON
Corpora-
tion
0.3
XS6W-6LSZH8SS30CM-Y
OMRON Cus-
tomer Service
Center
0.5
XS6W-6LSZH8SS50CM-Y
1
XS6W-6LSZH8SS100CM-Y
10
XS6W-6LSZH8SS1000CM-Y
*1.
For the latest list of the Cables, refer to the
Industrial Ethernet Connectors Catalog (Cat. No. G019)
.
*2.
The Cables are single-shielded, but the communications and noise characteristics are ensured to satisfy
the standard values.
4 Mounting and Wiring
4-13
CK3E-series Programmable Multi-Axis Controller User’s Manual Hardware (I610)
4-5 Laying the EtherCA
T Network
4
4-5-3
Installing EtherCA
T Communications Cables
Summary of Contents for CK3E Series
Page 6: ...Manual Structure 4 CK3E series Programmable Multi Axis Controller User s Manual Hardware I610 ...
Page 110: ...Appendices A 12 CK3E series Programmable Multi Axis Controller User s Manual Hardware I610 ...
Page 111: ...I Index I 1 CK3E series Programmable Multi Axis Controller User s Manual Hardware I610 I ...