A Standard System Protocol
R-38
CJ-series Serial Communications Units Operation Manual for NJ-series CPU Unit(W494)
Connection methods between a Serial Communications Board or Unit and the K3N
@
-series Intelligent
Signal Processor are shown below.
RS-232C
•
RS-232C connections are one-to-one.
•
The max. cable length is 15 m. Use OMRON RS-232C optical interface (Z3RN) when extend-
ing the transmission line beyond 15 m.
•
Use shielded, twisted-pair cable.
R-2-9
Connections
FG
SG
SD
RD
RTS
CTS
DSR
DTR
RS-232C
Serial Communications
Unit/Board
Shielded wire
Abbrevi-
ation
TX
RX
FG
SG
SD
RD
RTS
CTS
DSR
DTR
RS-232C
1
3
2
3
4
5
6
20
Intelligent
Signal
Processor
Pin
No.
Abbrevi-
ation
MAX232C or equivalent
9
2
3
4
5
7
8
Pin
No.
K3N
@
-
@@@@
-FLK1
RS-232C
Abbrevi-
ation
Pin
No.
RS-232C
Pin
No.
Abbrevi-
ation
MAX232C or equivalent
Shielded wire
K3N
@
-
@@@@
-FLK4
Serial
Communications
Unit/Board
SG
SD
RD
RTS
CTS
DSR
DTR
5
2
7
8
6
4
2
9
3
4
5
7
8
SG
SD
RD
RTS
CTS
DSR
DTR
TX
RX
Intelligent
Signal
Processor
7
FG
1/
Shell
1/
Shell