78
Timer and Counter Instructions
Section 3-4
3-4
Timer and Counter Instructions
Instruction
Mnemonic
Code
Symbol/Operand
Function
Location
Execution
condition
TIMER
TIM(BCD)
Output
Required
TIMX
(Binary)
(CS1-H, CJ1-H, or
CJ1M only)
HIGH-SPEED
TIMER
TIMH
015
(BCD)
Output
Required
TIMHX
551
(Binary)
(CS1-H, CJ1-H, or
CJ1M only)
ONE-MS TIMER
TMHH
540
(BCD)
TMHH(540) operates a decrementing timer with units of 1-ms. The setting
range for the set value (SV) is 0 to 9.999 s.
The timing charts for TMHH(540) are the same as those given above for
TIMH(015).
Output
Required
TMHHX
552
(BCD)
(CS1-H, CJ1-H, or
CJ1M only)
N: Timer number
S: Set value
TIM
N
S
Timer input
Timer PV
SV
Completion
Flag
Timer input
Timer PV
SV
Completion
Flag
TIM operates a decrementing timer with units of 0.1-s. The setting
range for the set value (SV) is 0 to 999.9 s.
Timer input turns OFF before Completion Flag turns ON.
N: Timer number
S: Set value
TIMX(550)
N
S
N: Timer number
S: Set value
TIMH(015)
N
S
Timer input
Timer PV
SV
Completion
Flag
Timer input
Timer PV
SV
Completion
Flag
TIMH(015) operates a decrementing timer with units of 10-ms. The
setting range for the set value (SV) is 0 to 99.99 s.
Timer input turns OFF before Completion Flag turns ON.
N: Timer number
S: Set value
TIMHX(551)
N
S
N: Timer number
S: Set value
TMHH(540)
N
S
N: Timer number
S: Set value
TMHHX(552)
N
S
Summary of Contents for CJ1G-CPU series
Page 3: ...iv...
Page 5: ...vi...
Page 21: ...xxii Conformance to EC Directives 6...
Page 169: ...148 Task Control Instructions Section 3 32...
Page 203: ...182 Programming Device Operations for Tasks Section 4 4...
Page 253: ...232 Using File Memory Section 5 3...
Page 337: ...316 Other Functions Section 6 11...
Page 347: ......
Page 369: ......
Page 373: ......
Page 379: ......
Page 381: ...360 Revision History...