Frequency inverters
Inverter heat loss
Three-phase 200 V class
Single-phase 200 V class
Three-phase 400 V class
Installation conditions for IP65
Model CIMR-V7AZ
20P1
20P2
20P4
20P7
21P5
22P2
24P0
25P5
27P5
Inverter capacity kVA
0.3
0.6
1.1
1.9
3.0
4.2
6.7
9.5
13
Rated current A
0.8
1.6
3
5
8
11
17.5
25
33
Heat
lo
ss W
Fin
3.7
7.7
15.8
28.4
53.7
60.4
96.7
170.4
219.2
Inside unit
9.3
10.3
12.3
16.7
19.1
34.4
52.4
79.4
98.9
Total heat loss
13.0
18.0
28.1
45.1
72.8
94.8
149.1
249.8
318.1
Model CIMR-V7AZ
B0P1
B0P2
B0P4
B0P7
B1P5
B2P2
B4P0
Inverter capacity kVA
0.3
0.6
1.1
1.9
3.0
4.2
6.7
Rated current A
0.8
1.6
3
5
8
11
17.5
Hea
t
lo
ss
W
Fin
3.7
7.7
15.8
28.4
53.7
64.5
98.2
Inside unit
10.4
12.3
16.1
23.0
29.1
49.1
78.2
Total heat loss
14.1
20.0
31.9
51.4
82.8
113.6
176.4
Model CIMR-V7AZ
40P2
40P4
40P7
41P5
42P2
44P0
45P5
47P5
Inverter capacity kVA
1.4
2.6
3.7
4.2
5.5
7.0
11
14
Rated current A
1.8
3.4
4.8
5.5
7.2
8.6
14.8
18
He
a
t
lo
ss W
Fin
15.1
30.3
45.8
50.5
58.2
73.4
168.8
209.6
Inside unit
15.0
24.6
29.9
32.5
37.6
44.5
87.7
99.3
Total heat loss
30.1
54.9
75.7
83.0
95.8
117.9
256.5
308.9
W =
Inverter
Inverter
Inverter
50 mm min. (5.5 and 7.5 KW)
30 mm min. (0.1 to 4.0 KW)
100 mm min.
100 mm min.
Side
Air
Air
Install the inverter vertically in order to ensure proper cooling. When installing the inverter,
always provide the following minimum installation space to allow normal heat dissipation.
1. Always provide enough space for the main circuit or control lines including cable gland.
2. If installing inverters next to one another, provide a minimum spacing of 60mm
.
50 mm or more
50 mm or more
120 mm or more
120 mm or more
40 mm or more
40 mm
or more
Side spaces
Top and bottom spaces
Air
Air