background image

 

6.

  Securely connect the battery connectors. 

For the BN150R, fit the battery cables into the clamps on the battery cover.

7.

  Attach the front panel.

Insert the front panel from the left side (for the BN75R) or right side (for the BN150R and 

BN300R), and fix it with the 2 screws.

Battery replacement is complete.

5.

  Attach the battery cover.

<BN75R>

Insert the battery cover from the right side, slide it to the left to align the screw holes, and then 

fix the battery cover with the 2 removed screws.

<BN150R and BN300R>

Insert the battery cover from the top side, and slide it to the right to fit into the tabs on the side 

of the UPS. Fix the battery cover with the 2 removed screws. Be careful not to tighten the 

screws too much; may strip the screw heads.

You may hear a “pop” sound when you connect the battery if it is replaced after the UPS’s 

operation is stopped, but this sound is not abnormal.

① 

① 

<Be sure to reset the battery life counter after replacing the battery.>

After replacing the battery, reset the battery life counter from the “Control” - “Reset B.life 

counter” screen in the LCD menu of the UPS.
If you do not reset the battery life counter, a battery replacement alarm may occur earlier 

than the expected battery life.

Write the battery replacement date on the included battery replacement date label, and 

attach the label to the UPS. 

Or, enter the battery replacement date from the “Setting” - “Battery Settings” - “Battery 

Installation” screen in the menu on the LCD.

Summary of Contents for BNB75R

Page 1: ...For example indicates that grounding is necessary Misuse may cause death or serious injury Warning Caution Safety precautions The safety symbols and their meaning used in this manual are as follows P...

Page 2: ...ot disassemble or modify the battery Doing so could cause dilute sulfuric acid leak which could cause blindness and burns Do not drop the battery and do not expose it to strong impact Dilute sulfuric...

Page 3: ...as a power failure occurs when replacing the battery while in operation backup cannot be performed and output stops Do not replace the battery during backup operation Output will stop UPS battery rep...

Page 4: ...ed and black battery cables are clamped to the unit hold and pull them out towards you Pull the battery connectors apart BN300R Hold the battery connectors with both hands and then while pressing down...

Page 5: ...olding the battery pack handle for the BN150R and BN300R 4 Insert the new battery upright into the UPS as far as it will go Replacement battery pack For BN75R Model BNB75R For BN150R Model BNB150R For...

Page 6: ...the battery cover with the 2 removed screws Be careful not to tighten the screws too much may strip the screw heads You may hear a pop sound when you connect the battery if it is replaced after the U...

Page 7: ...7 3 Notes of Chinese UPS Instruction Manual 1 UPS Instruction Manual 2 Instruction Manual 3 UPS 4 UPS 5 6 UPS UPS AC...

Page 8: ...8 K1L D 13038B UPS LCD Control Reset B life counter URL http www fa omron com cn UPS LCD Setting Battery Settings Battery Installation 6 25 40 2 6 UPS 8 6 Instruction Manual 25 40 6 2...

Reviews: